![Vicruns VD530 Series Скачать руководство пользователя страница 142](http://html1.mh-extra.com/html/vicruns/vd530-series/vd530-series_user-manual_1013438142.webp)
Parameter Description VD530 Series Inverter User Manual
- 138 -
F5-35
Corresponding Setting of
AI Curve 3 Max Input
-100.0%~+100.0%
100.0%
○
F5-36
AI3 (expansion card)
Filter Time
0.00s~10.00s
0.10s
○
The function and using method of curve 3, please refer to the instructions of curve 1.
F5-37
Pulse Min Input
0.00kHz~F5-39
0.00kH
z
○
F5-38
Corresponding Setting of
Pulse Min Input
-100.0%~+100.0%
0.0%
○
F5-39
Pulse Max Input
F5-37~100.00kHz
50.00k
Hz
○
F5-40
Corresponding Setting of
Pulse Max Input
-100.0%~+100.0%
100.0%
○
F5-41
PULSE Filter Time
0.00s~10.00s
0.10s
○
The group function code is used to set the relationship between HDI1 pulse frequency set and
corresponding setting.
Pulse frequency can only be input into the inverter through the HDI1 channel.
The application of the group is simlar to the curve 1, please refer to the instructions of curve 1.
F5-42
Travel Switch Lock Time
0.00s~10.00s
1.00s
○
It used to terminal control operation mode 5 (back and forth control), please refer to the specific
instructions of back and forth control mode.
F5-43
AI2 Input Type
0: Voltage
1: Current
0
○
F5-44
AI3 Input Type
0: Voltage
1: Current
0
○
AI2 and AI3 there are two modes of voltage and current input, when In the selection of the
corresponding input types of hardware, the parameters are selected as the same type.
Содержание VD530 Series
Страница 2: ......
Страница 9: ...VD530 Series Inverter User Manual Safety and Precautions 5 damage or performance reduce...
Страница 230: ......