background image

 

 

 

 

16

In order for the PIR logic function to be enabled, the following settings must be enabled at the zone 
thermostat. 

-

 

If a local PIR cover is used, be sure to set the (

PIR Func

)

 

parameter to

 ON. 

-

 

If a remote PIR sensor is used on BI1, be sure to set the (BI1) parameter to 

Motion NO

 or 

Motion 

NC

PIR logic  

The PIR function is only used during occupied periods. If occupancy is desired during an unoccupied 
period, simply press the local override button (if allowed by the local lockout level configuration). Then local 
occupancy will toggle to Override (local occupied ) as per the ToccTimer time value for overrides. 

 

Zone commanded occupied by the RTU schedule 

Initial state when no movements 
are detected by the PIR sensor 

Stand-by 

Initial movement detected by the 
thermostat ( PIR cover or remote 
PIR ) 

Occupied for 60 minutes after the last movement has been 
detected. When the 60 minute timer value has expired and no new 
movements have been detected, the thermostat will resume the 
stand-by mode.  

 
3) RTU Thermostats VZ7656B1000W Operation 

 

 

The following information needs to be carefully read and properly understood if proper system 
commissioning is to be achieved.  
 
Unlike low end commercial or residential zoning thermostats which typically only use two position demand 
or non- demand logic to initialize heating and cooling functions, Viconics VZ7656B1000X uses local PI 
zone demand(s) to operate heating and cooling stages. Accurate temperature control in the zones is 
achieved by the time proportional control algorithm. This enables performances and control sequences 
much closer to what is normally found in DDC application specific control devices. 
 
The operation of the RTU thermostat is linked with the operation of the attached zone thermostats. 
Although the thermostat it will operate in a stand-alone mode if the communication network is down, normal 
operation of the system as a whole requires that communication with the attached zone thermostats is 
functional. 

 
3A) Operation Data Exchanged  

 

 

Independently of the network layer being BACnet MS-TP or Wireless, the flow of data exchanged between 
the zones and the RTU thermostat can be summarized as follow:  
 

Heating and cooling demand data is first exchanged from the ZN thermostats to the RTU 
thermostat: 

 

Current PI heating demand ( output value is based on PI heating weight configuration ) 

 

Current PI cooling demand ( output value is based on PI cooling weight configuration ) 

 

Each voting thermostat will also calculate is demand values based on their current occupancy mode and 
setpoints currently in use: Unoccupied, Stand-By or Occupied. 

 

Based on the control type configuration 

(CntrlTyp)

, the RTU thermostat will calculate the resulting heating 

and cooling zone demands. (See section 2A) Demand Based Heating and Cooling System. 
 
Proper action to the heating or cooling stages using the time proportional control algorithm is accomplished 
based on heating or cooling values. 
 

-

 

If resulting calculated PI heating demand > resulting calculated PI cooling demand, then ZN 
sequence is heating  

-

 

If resulting calculated PI cooling demand > resulting calculated PI heating demand, then zone 
sequence is cooling  

-

 

If resulting calculated PI cooling demand = resulting calculated PI heating demand, then zone 
sequence stays in last current mode  

 

 

Содержание VZ7200F5x00W

Страница 1: ...1 Viconics Zoning System Application Guide VZ7200F5x00W and VZ7656B1000W Thermostats Wireless_Zoning_System_Guide E10 028 6020 R1 Issue Date July 13 2010...

Страница 2: ...00W operation A Demand based heating and cooling systems B Overrides and user zone interface lockouts C Zone setpoint limits D Heating and cooling weight zone selection E Minimum maximum and maxheatfl...

Страница 3: ...ostats but not included 24 Vac power supply Dedicated to a single zone or many zones An analog 0 to 10 Vdc pressure dependent actuator Terminal reheat if required by the design Proper wiring of all co...

Страница 4: ...RTU thermostat please refer and read the VZ76xx Product Guide Installation and commissioning information is available on document LIT VZ7656_W Exx PIR cover installation information is available on do...

Страница 5: ...control system will attempt to deliver the loads required by master demanding zones by distributing the total available capacity of the installed equipment to the required demanding areas If the equip...

Страница 6: ...ll thermostats 1C Local Zone with Terminal Reheat or without Terminal Reheat Including or excluding use of terminal reheat is dictated by design criteria s of the installer The use of terminal reheat...

Страница 7: ...o the zone directly from the supply to the return on a pressure rise when the VAV zone dampers are closing The by pass damper should be sized to allow at least 70 to 80 of the nominal airflow of the R...

Страница 8: ...ir or cold air to satisfy the current zone demand point in time The following is an example of a RTU system mode calculation based on highest average of the three highest demands or the average of the...

Страница 9: ...Voting Zone 3 Voting Zone 4 Voting Zone 5 RTU Control Type Current heat demand Current heat demand Current heat demand Current heat demand Current heat demand Highest Average of 3 highest Average of 5...

Страница 10: ...hat have their function locked out will display a keypad lock message on the zone thermostat display If a global override is required for the whole system and all zones return to occupied mode then th...

Страница 11: ...nts of the total MAX CFM of the equipment then for sure this zone needs to be master to the system Zones or areas that are subject to temporarily larger occupancy need to be part of demand calculation...

Страница 12: ...nd energy consumption Adding many master voting zones including problematic ones to an RTU thermostat will provide better comfort at the expense of higher energy consumption Restricting the number of...

Страница 13: ...irectly move from 25 to a 75 position As soon as BO5 is de energized the damper will move back to 25 opening 1 10 seconds for Solid state relays Set to any value superior to the current selected minim...

Страница 14: ...60F or when the set point is at least 7 8 F lower than the current room temperature This will drive the VAV zone to its minimum value 5 Set the Max Pos configuration parameter to the desired value as...

Страница 15: ...ive Infra Red Motion Detector Cover PIR The Viconics zone thermostats are compatible with the new Viconics PIR Passive Infra Red cover accessory Thermostats equipped with a PIR cover provide advanced...

Страница 16: ...mances and control sequences much closer to what is normally found in DDC application specific control devices The operation of the RTU thermostat is linked with the operation of the attached zone the...

Страница 17: ...occupancy command This will disable the local schedule occupancy function to the zones For more information on BACnet please refer to global override section of the zoning system integration guide The...

Страница 18: ...ly set to keep heating or cooling equipment cycling to a minimum It is the responsibility of the installer to decide if priority of the system will be given to comfort or not The adjustments for both...

Страница 19: ...peration The RTU thermostat has a built in static pressure control loop with an analog 0 to 10 Vdc by pass damper output In order to operate the static pressure control loop needs to have a static pre...

Страница 20: ...long with ZigBee s Network and Application Support Layer provide Low cost installation deployment Ease of implementation Reliable data transfer Short range operation Very low power consumption Appropr...

Страница 21: ...at s offline VZ76xx RTU thermostat is the network coordinator Range of PAN ID on all thermostats to use 251 to 500 This range is reserved for stand alone system operation Examples Notes Each system wi...

Страница 22: ...iver is the network coordinator Any thermostats VZ72 s VZ76xx RTU s or any VT7xxx wireless thermostats act as routers Range of PAN ID on all thermostats to use 1 to 250 Reserved for networked system o...

Страница 23: ...y interfere with other channel selections allowed by 802 15 4 Channels 11 to 14 16 to 24 2 The maximum distance between each thermostat node should be 100 feet 30 M or less between two thermostat node...

Страница 24: ...or NS near the center of all associated VZ72xx zone thermostats installed 6 Always try to locate the coordinator VZ76xx for SA or VWG and Jace driver for NS near or in the line of sight to as many wir...

Страница 25: ...S or Networked Systems applications where the VWG and Jace Driver is used as a coordinator 1 x 200ms short blink Power on 2 x 200ms short blinks Power on Communicating with thermostat base 3 x 200ms s...

Страница 26: ...s expected then proper system commissioning should be done at all levels A zoning system has a huge dependency on the demand and response being fully functional both at the RTU and the zone level 5A P...

Страница 27: ...TU on board economizer operation 5C Operational System Checklist It is recommended to keep a checklist of all milestones and configuration settings during start up This list should be kept as a refere...

Страница 28: ...re Communication with zones is active Status LED manual scroll display Local time clock set Local schedule set Local system mode set to Auto System On Outdoor air sensor properly connected and display...

Страница 29: ...zone thermostats If using a single 24 Vac for each zone thermostat Use a 20 VA or more Class2 self protected transformer to power all components attached to the zone thermostat Be sure to respect the...

Страница 30: ...are mandatory 6C Balancing and Capacity It is not the mandate of a zoning control system to correct for an incorrect mechanical layout or improper load calculations of the mechanical zoning equipment...

Отзывы: