1) System Overview and Architecture  

 

 

 

The Viconics Zoning System product is comprised of 2 thermostat types. 

  The VZ7200F5x00W zoning thermostat 

  The VZ7656B1000W RTU thermostat 

 

When combined, they deliver a simple and efficient demand based system implementation which controls 
pressure dependent VAV zones with roof top units (RTU). The system is designed to work with small to 
medium sized RTU staged heating and cooling equipment (2 to 20 tons). 

 

The system can be used either in a stand-alone system mode or seamlessly integrated into Niagara AX

®

 

Workbench environment with the usage of a Viconics JACE communication and its associated driver. 

 

The Viconics VZ7200F5x00W Wireless Zone thermostat family is specifically designed for local pressure 
dependent VAV zone control within the Viconics zoning system product family. 

The primary damper output uses a common 0 to 10 Vdc VAV actuator for control. 

The product features a backlit LCD display with dedicated function menu buttons for simple user operation. 
Accurate temperature control is achieved due to the product’s PI proportional control algorithm, which 
virtually eliminates temperature offset associated with traditional, differential-based thermostats. 

 

The Zone thermostats are also compatible with the new Viconics PIR cover accessories. Thermostat is 
equipped with a PIR cover which provides advanced active occupancy logic. The system will automatically 
switch occupancy levels from occupied to stand-by and unoccupied as required when activity is detected or 
not detected by the unit. This advanced occupancy functionality provides valuable energy savings during 
occupied hours without sacrificing occupant comfort. All zone thermostats can be ordered with or without a 
factory installed PIR cover.  

The following hardware is required for operation of the zone thermostats but not included: 
 

  24 Vac power supply. Dedicated to a single zone or many zones 

  An analog 0 to 10 Vdc pressure dependent actuator 

  Terminal reheat if required by the design 

  Proper wiring of all components as per the installation manual 

  Proper network wires pulled through all devices communication connections 

 

The Viconics 

VZ7656B1000W Wireless Roof Top Unit (RTU) thermostat

 is specifically designed for 

equipment control based on the zone demands. 

The RTU thermostat has been designed for single stage or multi-stage control of heating and cooling 
equipment such as rooftop and self-contained units used in zoning systems.  

The product also features a backlit LCD display with dedicated function menu buttons for simple operation. 
Accurate temperature control is achieved through to the product’s PI proportional control algorithm, which 
virtually eliminates temperature offset associated with traditional, differential-based thermostats. 

The thermostat also contains extra digital inputs, which can be set by the user to monitor filter status or can 
be used as a general purpose service indicator. All models contain a SPST auxiliary switch, which can be 
used to control lighting or disable the RTU economizer function during unoccupied periods. It also features 
a discharge air sensor input. Proportional static pressure logic (input and output) has been integrated onto 
the thermostat to provide a complete single packaged unit for most small to medium size jobs. 

 

The following hardware is required for operation of the RTU thermostats, but not included: 
 

  24 Vac power supply. Typically taken directly from the RTU power supply (C & RC) 

  An outdoor air sensor (Viconics S2020E1000) 

  A supply air duct sensor (Viconics S2000D1000) 

  A return air duct sensor (Viconics S2000D1000) 

  A 0 to 5 Vdc static pressure sensor and transducer 

  An analog 0 to 10 Vdc by-pass damper actuator (spring-return or not)  

  Proper wiring of all components as per the installation manual 

  Proper network wires pulled through all devices communication connections 

Содержание VZ7200F5x00W

Страница 1: ...1 Viconics Zoning System Application Guide VZ7200F5x00W and VZ7656B1000W Thermostats Wireless_Zoning_System_Guide E10 028 6020 R1 Issue Date July 13 2010...

Страница 2: ...00W operation A Demand based heating and cooling systems B Overrides and user zone interface lockouts C Zone setpoint limits D Heating and cooling weight zone selection E Minimum maximum and maxheatfl...

Страница 3: ...ostats but not included 24 Vac power supply Dedicated to a single zone or many zones An analog 0 to 10 Vdc pressure dependent actuator Terminal reheat if required by the design Proper wiring of all co...

Страница 4: ...RTU thermostat please refer and read the VZ76xx Product Guide Installation and commissioning information is available on document LIT VZ7656_W Exx PIR cover installation information is available on do...

Страница 5: ...control system will attempt to deliver the loads required by master demanding zones by distributing the total available capacity of the installed equipment to the required demanding areas If the equip...

Страница 6: ...ll thermostats 1C Local Zone with Terminal Reheat or without Terminal Reheat Including or excluding use of terminal reheat is dictated by design criteria s of the installer The use of terminal reheat...

Страница 7: ...o the zone directly from the supply to the return on a pressure rise when the VAV zone dampers are closing The by pass damper should be sized to allow at least 70 to 80 of the nominal airflow of the R...

Страница 8: ...ir or cold air to satisfy the current zone demand point in time The following is an example of a RTU system mode calculation based on highest average of the three highest demands or the average of the...

Страница 9: ...Voting Zone 3 Voting Zone 4 Voting Zone 5 RTU Control Type Current heat demand Current heat demand Current heat demand Current heat demand Current heat demand Highest Average of 3 highest Average of 5...

Страница 10: ...hat have their function locked out will display a keypad lock message on the zone thermostat display If a global override is required for the whole system and all zones return to occupied mode then th...

Страница 11: ...nts of the total MAX CFM of the equipment then for sure this zone needs to be master to the system Zones or areas that are subject to temporarily larger occupancy need to be part of demand calculation...

Страница 12: ...nd energy consumption Adding many master voting zones including problematic ones to an RTU thermostat will provide better comfort at the expense of higher energy consumption Restricting the number of...

Страница 13: ...irectly move from 25 to a 75 position As soon as BO5 is de energized the damper will move back to 25 opening 1 10 seconds for Solid state relays Set to any value superior to the current selected minim...

Страница 14: ...60F or when the set point is at least 7 8 F lower than the current room temperature This will drive the VAV zone to its minimum value 5 Set the Max Pos configuration parameter to the desired value as...

Страница 15: ...ive Infra Red Motion Detector Cover PIR The Viconics zone thermostats are compatible with the new Viconics PIR Passive Infra Red cover accessory Thermostats equipped with a PIR cover provide advanced...

Страница 16: ...mances and control sequences much closer to what is normally found in DDC application specific control devices The operation of the RTU thermostat is linked with the operation of the attached zone the...

Страница 17: ...occupancy command This will disable the local schedule occupancy function to the zones For more information on BACnet please refer to global override section of the zoning system integration guide The...

Страница 18: ...ly set to keep heating or cooling equipment cycling to a minimum It is the responsibility of the installer to decide if priority of the system will be given to comfort or not The adjustments for both...

Страница 19: ...peration The RTU thermostat has a built in static pressure control loop with an analog 0 to 10 Vdc by pass damper output In order to operate the static pressure control loop needs to have a static pre...

Страница 20: ...long with ZigBee s Network and Application Support Layer provide Low cost installation deployment Ease of implementation Reliable data transfer Short range operation Very low power consumption Appropr...

Страница 21: ...at s offline VZ76xx RTU thermostat is the network coordinator Range of PAN ID on all thermostats to use 251 to 500 This range is reserved for stand alone system operation Examples Notes Each system wi...

Страница 22: ...iver is the network coordinator Any thermostats VZ72 s VZ76xx RTU s or any VT7xxx wireless thermostats act as routers Range of PAN ID on all thermostats to use 1 to 250 Reserved for networked system o...

Страница 23: ...y interfere with other channel selections allowed by 802 15 4 Channels 11 to 14 16 to 24 2 The maximum distance between each thermostat node should be 100 feet 30 M or less between two thermostat node...

Страница 24: ...or NS near the center of all associated VZ72xx zone thermostats installed 6 Always try to locate the coordinator VZ76xx for SA or VWG and Jace driver for NS near or in the line of sight to as many wir...

Страница 25: ...S or Networked Systems applications where the VWG and Jace Driver is used as a coordinator 1 x 200ms short blink Power on 2 x 200ms short blinks Power on Communicating with thermostat base 3 x 200ms s...

Страница 26: ...s expected then proper system commissioning should be done at all levels A zoning system has a huge dependency on the demand and response being fully functional both at the RTU and the zone level 5A P...

Страница 27: ...TU on board economizer operation 5C Operational System Checklist It is recommended to keep a checklist of all milestones and configuration settings during start up This list should be kept as a refere...

Страница 28: ...re Communication with zones is active Status LED manual scroll display Local time clock set Local schedule set Local system mode set to Auto System On Outdoor air sensor properly connected and display...

Страница 29: ...zone thermostats If using a single 24 Vac for each zone thermostat Use a 20 VA or more Class2 self protected transformer to power all components attached to the zone thermostat Be sure to respect the...

Страница 30: ...are mandatory 6C Balancing and Capacity It is not the mandate of a zoning control system to correct for an incorrect mechanical layout or improper load calculations of the mechanical zoning equipment...

Отзывы: