4A) (SA) Stand-Alone applications
When PAN ID is used with a range of 251 to 500, for (SA) Stand-Alone Systems.
In this application, the VZ76xx thermostat(s) act as the coordinators to their own system. I.E. they are the
network masters for each VZ72xx thermostat reporting to them when the whole zoning system(s) is self
sufficient and communication and no external communication is required.
•
Wireless thermostat factory default Channel and PAN ID = Thermostat(s) offline
•
VZ76xx RTU thermostat is the network coordinator
•
Range of PAN ID on all thermostats to use 251 to 500. This range is reserved for stand-alone system
operation
Examples:
Notes:
·
Each system with a VZ76xx RTU master will use a unique PAN ID and or channel settings
RTU VZ76 Coordinator
Channel
25
ID
200
Zone VZ72 Router
Channel
25
ID
200
Zone VZ72 Router
Channel
25
ID
200
Zone VZ72 Router
Channel
25
ID
200
Zone VZ72 Router
Channel
25
ID
200
System 1
RTU VZ76 Coordinator
Channel
25
ID
205
Zone VZ72 Router
Channel
25
ID
205
Zone VZ72 Router
Channel
25
ID
205
Zone VZ72 Router
Channel
25
ID
205
Zone VZ72 Router
Channel
25
ID
205
System 2