background image

The Addi(on Residen(al Suite Thermostats User Manual 

Viconics Thermostat VT7300F5500-2969 

 

At THE ADDITION, the suite ven(la(on system can operate either in a HEATING or COOLING mode, not both 
at the same (me. The mode is determined by the opera(on of the Building Central System.  

COOLING MODE: Thermostat is automa(cally switched to cooling mode when the Building Central System is 
providing CHILLED water to the suite manifolds. 

 

On a call for COOLING 

 

The Cooling (snowflake) LED will come ON

 

The thermostat will signal the manifold 24vac zone valve to open.

 

ADer a 3 minute delay (Hme delay to allow Chilled Water to reach the Unit):

 

The Fan LED will come ON

 

The Thermostat will then modulate fan according to demand, from "Low Speed " to "High Speed" 

 

When the Building Central System is providing Chilled water and the suite has a call for HeaHng, the zone valve 
remains closed and the Thermostat 

does not

 turn the fan on. All LED’s stay off. 

When there is No call for heaHng or cooling, all LED’s stay off, zone valve is closed and fan is off.

 

The thermostat readout will scroll between room temperature and "SystMode Cool".  

HEATING MODE: Thermostat is automa(cally switched to hea(ng mode when the Building Central System is 
providing HEATING water to the suite manifolds. 

 

On a call for HEATING 

 

The HeaHng (flame) LED will come ON

 

The thermostat will signal the manifold 24vac zone valve to open.

 

ADer a 3 minute delay (Hme delay to allow Hot Water to reach the Unit):

 

The Fan LED will come ON

 

The Thermostat will then modulate fan according to demand, from "Low Speed" to "High Speed" 

 

When the Building Central System is providing Hot water, and the suite has a call for Cooling, the zone valve 
remains closed and the Thermostat 

does not

 turn the fan on. All LED’s stay off. 

When there is No call for heaHng or cooling, all LED’s stay off, zone valve is closed and fan is off.

 

Отзывы: