The thermostat readout scrolls between "room temperature" and "SystMode heat". 

 

Adjus(ng OCCUPIED Temperature Set-points:

 

To adjust the occupied temperature, press the UP and DOWN arrows buXons on the thermostat to get to the 
desired temperature for your comfort. Please note that even though the buXons will allow you to set the 
thermostat set-points to the ranges idenHfied below for both heaHng and cooling, the system operaHng range 
will restrict the actual temperatures to the actual range of the Building Central System. 

The Thermostat provides a single occupied set-point adjustment 

 

When in HeaHng Mode the set-point range is: 4.5 to 24.0 °C.  

When in Cooling Mode the set-point range is: 19.0 to 37.5 °C. 

If desired, seWng Hea(ng Set-point to 4.5 or Cooling Set-point to 37.5 will basically disable the thermostat 

PIR Func(on:

 

The built-in Passive Infra-Red occupancy sensor (PIR) automaHcally selects the Thermostat 

Occupied

 Set-Points 

when any moHon is detected, If the PIR sees no moHon for >4 Hours then the 

Standby

 Set-Points will be 

acHvated. If the PIR sees no moHon for >24 Hours then the 

Unoccupied

 Set Points will be acHvated. As soon as 

any movement is detected the Thermostat will return to 

Occupied

 Set-Points that were previously set. 

Important:

 Typical moHon detecHon range is around 12-14 feet, with perpendicular normal walk speed. 

Default STANDBY and UNOCCUPIED Set-Points: 

The default set-points below are fixed in the Thermostat and are not user adjustable. They were designed to 
allow the system to be able to restore occupied set-points from standby within a relaHve short period of Hme 
and also to limit energy use when the space is unoccupied. 

OVERRIDE BuZon:

  

Override buXon is NOT FUNCTIONAL, and will display "Lockout" when override buXon pressed.

 

If the buXon is 

pressed for 8-10 seconds it will enter the configuraHon menu. The password is 1000 minus “Error code”. 

 This 

menu is intended for experienced technical configura(on and altering any seWngs inside of this menu can 
cause the thermostat to operate incorrectly and service calls to correct issues from these being pressed will 
not be covered under warranty 

HIDDEN BuZons: 

On some thermostats the manufacturer has inadvertently le] the plunger for some unused switches in place 
but these SHOULD NOT BE PRESSED. They are not iden(fied by a buZon symbol on the front cover of the 
thermostat and are not part of the specific configura(on of these thermostats. Pressing these buZons can 

Default Set-point for St-By HT

19.5 C

Default Set-point for St-By CL

25.5 C

Default Set-point for Unocc HT

17.5 C

Default Set-point for Unocc CL

27.5 C