The thermostat readout scrolls between "room temperature" and "SystMode heat".
Adjus(ng OCCUPIED Temperature Set-points:
To adjust the occupied temperature, press the UP and DOWN arrows buXons on the thermostat to get to the
desired temperature for your comfort. Please note that even though the buXons will allow you to set the
thermostat set-points to the ranges idenHfied below for both heaHng and cooling, the system operaHng range
will restrict the actual temperatures to the actual range of the Building Central System.
The Thermostat provides a single occupied set-point adjustment
When in HeaHng Mode the set-point range is: 4.5 to 24.0 °C.
When in Cooling Mode the set-point range is: 19.0 to 37.5 °C.
If desired, seWng Hea(ng Set-point to 4.5 or Cooling Set-point to 37.5 will basically disable the thermostat
PIR Func(on:
The built-in Passive Infra-Red occupancy sensor (PIR) automaHcally selects the Thermostat
Occupied
Set-Points
when any moHon is detected, If the PIR sees no moHon for >4 Hours then the
Standby
Set-Points will be
acHvated. If the PIR sees no moHon for >24 Hours then the
Unoccupied
Set Points will be acHvated. As soon as
any movement is detected the Thermostat will return to
Occupied
Set-Points that were previously set.
Important:
Typical moHon detecHon range is around 12-14 feet, with perpendicular normal walk speed.
Default STANDBY and UNOCCUPIED Set-Points:
The default set-points below are fixed in the Thermostat and are not user adjustable. They were designed to
allow the system to be able to restore occupied set-points from standby within a relaHve short period of Hme
and also to limit energy use when the space is unoccupied.
OVERRIDE BuZon:
Override buXon is NOT FUNCTIONAL, and will display "Lockout" when override buXon pressed.
If the buXon is
pressed for 8-10 seconds it will enter the configuraHon menu. The password is 1000 minus “Error code”.
This
menu is intended for experienced technical configura(on and altering any seWngs inside of this menu can
cause the thermostat to operate incorrectly and service calls to correct issues from these being pressed will
not be covered under warranty
HIDDEN BuZons:
On some thermostats the manufacturer has inadvertently le] the plunger for some unused switches in place
but these SHOULD NOT BE PRESSED. They are not iden(fied by a buZon symbol on the front cover of the
thermostat and are not part of the specific configura(on of these thermostats. Pressing these buZons can
Default Set-point for St-By HT
19.5 C
Default Set-point for St-By CL
25.5 C
Default Set-point for Unocc HT
17.5 C
Default Set-point for Unocc CL
27.5 C