DIP SWITCH ADJUSTMENTS PER APPLICATIONS                                                                                                                 

INPUT SIGNAL

SWITCH #1

SWITCH #2

SWITCH #3

SWITCH #4

0 to 10 Vdc control signal ( 2 to 10 Vdc control range )

Off

Off

Off

On

4 to 20 mA control signal

Off

Off

On

Off

0 to 135 

 control signal

On

On

Off

Off

TYPICAL APPLICATIONS                                                                                                                                                         

0 To 10 Vdc Room Or Duct Thermostat Control

Dip switch position

S1

S2

S3

S4

0 to 10 Vdc control signal

Off

Off

Off

On

0 To 10 Vdc From a Building Automation System

Dip switch position

S1

S2

S3

S4

0 to 10 Vdc control signal

Off

Off

Off

On

Modulating Room Thermostat

0 to 10 Vdc

Modulating Supply Air Control Thermostat

0 to 10 Vdc

0 to 10 Vdc

Modulating Signal From BAS System

2 Vdc = 0% capacity

10 Vdc = 100% capacity

24 Vac

Common

Input

2nd SSR on 3 phase

models only

1
2
3

L1

L2

L3

To load

( controlled leg )

To load

( controlled leg )

To load

( uncontrolled leg )

Common

24 Vac

0 to 10 Vdc

output

-

+

2 Vdc = 0% capacity

10 Vdc = 100% capacity

24 Vac

Common

Input

2nd SSR on 3 phase

models only

1
2
3

L1

L2

L3

To load

( controlled leg )

To load

( controlled leg )

To load

( uncontrolled leg )