3-6
|
Chapter 3 Wiring
For an Indoor or Outdoor/High-Impact Pendant Model Installation
Refer to the Figure at the end of this section for customer interface board
connections.
1. Route each cable from the inside top of the housing.
2. Remove terminal blocks from the accessory kit. The 2-pin is for
power (TB2), the 4-pin is for relays (TB5) and the 8-pin is for alarms
(TB1).
3. Strip approximately 1 inch (25 mm) of the cable outer jacket used for
power, control, alarms and relays. Then strip approximately 0.25
inches (6 mm) of insulation off of each individual wire.
4. Terminate the 8-conductor alarm cable and 4-pin relay/control signal
cable.
5. Make all connections to terminal blocks TB2 (power), TB1 (alarms),
TB5 (relays/control signals) with reference to Table 2.
6. Slide excess cable back up into the mount/pipe so that cable length is
flush with the bottom of the housing, approximately 8 to 9 inches (203
to 229 mm).
7. Install the terminal blocks TB1, TB2, TB5 into the customer interface
board at the proper block frames. Connect an RJ-45 connector to J6
on the board.