31
7.3
Honeywell V 4044F three-way valve technical data
Tab. no. 7
Honeywell V 4044F motor driven zonal three-way valve technical parameters
Maximum differential pressure for closing the valve
(max. pressure difference between the inlet and
outlet that the valve can work with)
mbar
550
Maximum ambient temperature
°C
50
Heating water temperature
°C
5 - 88
Mating dimensions (heating water inlet and outlet)
Js
Internal thread 1“
Connecting voltage
1/N/PE 230 V AC 50 Hz TN-S
Electric coverage
IP 40
Environment
according to
Č
SN 33 2000 - 7 – 701 ed. 2 the
boiler must not be installed in 0,1,2 zones
Note: A five-core connecting cable is delivered together with the valve
1
2
3
4
5
Pressure loss [m of water column]
Fig. no. 14
Honeywell V 4044F three-way valve characteristic
8.
Combustion products forced draw-off mechanism
The boiler can be equipped with a flue ventilator (only OSV hereinafter) which enables to install
boiler also in the space where it cannot be connected to a chimney and combustion products can be
led away into the outdoor space through the wall– according to TPG G 800 01 „Flue outfall from the
gas fuel appliances on the exterior wall (façade)
This complementary equipment can be used in the whole output range of boilers designated for natural gas
combustion. Two-sectional boilers can only be operated with rated output. OSV is offered in three sizes for
outputs according to the table as follows:
Tab. no. 8a)
OSV types assignment to VIADRUS GARDE G 42 boiler
Number of sections
2
3
4
5
6
7
boiler output– natural gas (kW)
8
12-17
18-26
27-34
35-41
42-49
boiler output – propane (kW)
7
14
21
26
33
40
OSV type
OSV 1-2
OSV 1-3
OSV 1-4
OSV 2-5
OSV 3-6
OSV 3-7
Neck diameter D (mm)
80
110
130
160
170
180
Tab. no. 8b)
OSV types assignment to VIADRUS GARDE G 42 ECO boiler
Number of sections
2
3
4
5
6
7
boiler output– natural gas (kW)
8
12-17
18-26
27-34
35-41
42-49
boiler output – propane (kW)
7
14
22,5
30
36
42
OSV type
OSV 1-2
OSV 1-3
OSV 1-4
OSV 2-5
OSV 3-6
OSV 3-7
Neck diameter D (mm)
80
110
130
160
170
180
The operation safety is ensured by a differential pressure switch which switches on the burner only
on condition of a proper exhaustion. Other safety element watching the combustion products escape
into the boiler room is the combustion products return flow TS fuse which is belongs to boilers
standard equipment.
Pressure loss dependence
on the flow rate
Flow rate (l/min)
100
80
60
40
20