background image

7.  Troubleshooting

When the motor is not running properly, try to find the problem in the following table. If you still cannot solve the problem, contact 

your nearest ORIENTAL MOTOR office.

22

Problem

Motor does not run

Speed does not 

change

Motor rotates in an 

opposite direction.

Starting is delayed

Reversing is 

delayed

Stopping is 

delayed

Alarm is output

What to Check

Is the power supply connected 

correctly?

Are the connector connections 

secure?

Are the CW and CCW inputs on 

(low)?

Is the speed potentiometer turned 

all the way in the counterclockwise 

direction?

Is the alarm signal being output?

Have you selected the desired 

speed setting method?

Have you selected the desired 

speed setting method?

Are you using a gearhead?

Is the setting of the acceleration 

duration potentiometer other than 

"0"?

Is the load inertia excessive?

Is the setting of the deceleration 

duration potentiometer other than 

"0"?

Is the load inertia excessive?

Is there an overload?

Does the driver's ambient 

temperature exceed 50

?

Are direction reversals or start/stops 

being repeated in short cycles?

Is applied voltage lower than 

10% of

specification voltage?

Is the motor cable connection 

broken?

Response

Connect the power supply and check to see that the 

POWER LED (green) lights.

Insert connectors firmly all the way in.

Turn on (switch to low) the input for the desired direction 

of rotation.

Turn the speed potentiometer to the clockwise. (This 

applies to both internal and external speed potentiometer.)

Turn off power, correct the problem that caused the alarm, 

and turn power back on (be sure that at least 1 minute 

has passed since turning power off).  The operating status prior

to alarm output will be restored.

Check the speed setting method. 

Check the speed setting method. 

Some gearhead speed ratios will cause rotation in 

the opposite direction to the motor shaft.

Set the acceleration time potentiometer to "0".

Reversing can be delayed if the load inertial is high.

Either turn off (switch to high) the SLOW DOWN input or 

set the deceleration time potentiometer to "0".

Check the load inertia.

Check that the load is no greater than the rated load and 

no greater than the permissible load inertia.

Use an appropriate cooling method to reduce ambient 

temperature to 50

or less.

Try lengthening the operating cycle or reducing the load.

Check the applied voltage.

If there is anything wrong with the motor cable (sensor 

signal), the motor will stop. Check for any damage to the 

motor cable.

Содержание FBL II Series

Страница 1: ...Installation P 5 4 Connection P 8 5 Operation P 16 6 Characteristics P 20 7 Troubleshooting P 22 8 Specifications P 23 Thank you for purchasing ORIENTAL MOTOR products Please read this operating manua...

Страница 2: ...ve the sheath of the cable and then ground or touch the shielded wire This may cause electric shock or trigger the ground fault interrupt circuit 1 2 Precautions for Operation The enclosure temperatur...

Страница 3: ...ards Recognized name and certified name are motor model name and driver name Application of EN standard for FBL575SW type and FBL5120SW type is pending Note The EMC measurements required under standar...

Страница 4: ...s at the position in the model number indicated by the box Note The unit combinations are as above the mentioned Note that it cannot be used in any other combinations Unit Model FBL575AW FBL575CW FBL5...

Страница 5: ...tor and driver are mounted requires overvoltage category and pollution degree 3 specifications install the motor in a cabinet that comply with IP54 and connect to power supply via an isolation transfo...

Страница 6: ...nd gearhead to machinery make installation holes in the mounting place Use screws provided with gearhead and secure the motor so that there are no gaps between the motor flange surface gearhead surfac...

Страница 7: ...When mounting the driver in a tightly close up place like the control panel and a place where there is a heating hearby be sure to when the driver ambient timperature exceeds 40 cool the driver with a...

Страница 8: ...h Alarm Indicator Red Alarm Indicator Indicates that an alarm signal has been output when either the overload overvoltage overheating or out of phase protection function is activated 16 For motor conn...

Страница 9: ...l input These are the connection terminals when controlling speed using the external speed potentiometer provided with the unit or by means of a DC power supply GND ground terminal for input output si...

Страница 10: ...minal cover after connecting Input power of single phase types 10 1 2 3 3 2 1 4 5 6 7 8 9 10 11 12 INPUT COM EXT VR CW CCW SLOW DOWN SW1 Speed selection SW2 Clockwise rotation input SW3 Counterclockwi...

Страница 11: ...ver External DC power supply 24V A connection to this terminal is not necessary when using the driver s built in power supply OFF ON OFF ON OFF ON OFF ON 1 3 2 S S S D SPEED FG L2 L3 L1 BRUSHLESS DC M...

Страница 12: ...ft Type FBL575AW GFB FBL5120AW GFB FBL575CW GFB FBL5120CW GFB FBL575SW GFB FBL5120SW GFB Note Keep the spacing between eath terminals more than 6 4 when U shape terminals are used 4 5 Methods of Speed...

Страница 13: ...40 1 57 7 5 295 9 5 374DIA External DC Voltage The external DC voltage can be selected by turning on switchd to low input to the EXT VR terminal To connect an external DC voltage connect the plus wir...

Страница 14: ...to INT Signals will not be input if it is set to EXT Cautions to observe when using a controller with an internal clamp diode When using a controller with an internal clamp diode the O power supply s...

Страница 15: ...signal is output terminals between ALARM OUT and GND is a electrified See page 16 for the descriptions of these protection functions 15 Reinforce photo coupler SPEED OUT ALARM OUT GND 2 7k min Photoc...

Страница 16: ...um or set speed 16 Alarm Signal Output No Alarm Signal Output Action Activated when a load exceeding the rated torque load torque or motor current of 130 max of rated load or rated motor current is ap...

Страница 17: ...page 10 11 Note To run or stop the motor do not turn power on or off Instead use the CW or CCW input Run speed change stop 3000r min 1000r min Run Instantaneous stop Change of direction instantaneous...

Страница 18: ...e motor decelerates for the length of time set on the deceleration time potentiometer and comes to a stop The acceleration deceleration time is set using the time potentiometers on the front panel of...

Страница 19: ...H M and L terminals of each driver The resistance of the speed set potentiometer is given by the following expression VRx 20 N k N 4 W where N is the number of drivers Thus if two drivers are used th...

Страница 20: ...lerating When a load that exceed the rated torque is applied continuously for approximately 5 seconds an overload protection is activated and the motor comes to a stop FBL575 FBL5120 20 Rated torque L...

Страница 21: ...0 3 N m 1000 r min 0 kgfcm Driver Input Current A Rated Torque Torque 3000 r min 2000 r min 1000 r min 300 r min 1 5 1 0 0 5 Rated Torque Driver Input Current A 0 1 2 3 0 0 1 0 2 0 3 Torque N m kgfcm...

Страница 22: ...tage Is the motor cable connection broken Response Connect the power supply and check to see that the POWER LED green lights Insert connectors firmly all the way in Turn on switch to low the input for...

Страница 23: ...erating Storage Transport 1000m max 3000m max 3000m max Item Insulation resistance Dielectric strength Temperature rise Insulation class 1 Temperature Humidity Altitude IP class 23 Specification 100M...

Страница 24: ...70 716 2800 Fax 770 719 8515 Canada Office Tel 905 502 5333 Fax 905 502 5444 ORIENTAL MOTOR EUROPA GmbH Headquarters and D sseldorf Office Tel 02131 95280 Fax 02131 952899 Munich Office Tel 08131 5988...

Отзывы: