1.9
Battery Back Up
The power supply for the LaserCOMPACT detector may be switched to a back up battery in the
event of the supply being disrupted. The size of the battery back up is determined by local
standards and codes, the total power required by the system, back up time required, allowance
for reduction in capacity with age and expected temperature variations.
Note:
It is recommended that batteries be changed as per the battery manufacturer’s
specifications or as per your local codes and standards.
Backup battery size calculation sheet
Table 6 - Calculating the size of backup battery
1.10 Starting Up
Note:
A LaserCOMPACT detector must be powered up by VESDA accredited personnel
only
Normal load @ 24 V DC
Full alarm load @ 24 V DC
Equipment
Load mA
Number
Total
Load mA
Number
Total
Detector @ 2490 rpm
170
190
Remote Display
90
110
Remote Programmer
50
(backlight off)
110
(backlight on)
Hand-held
Programmer
50
(backlight off)
110
(backlight on)
Other 24 V loads
Total mA
Total mA
X
X
Standby hours
Alarm hours
=
Standby capacity
Alarm capacity
Total capacity = S Alarm capacity
Divided by 1000 for standby capacity
Multiplied by battery factor (Normally 1.25)
Содержание LaserCOMPACT
Страница 2: ...LaserCOMPACT Product Guide VESDA 2 ...
Страница 5: ...VESDA LaserCOMPACT Product Guide iii FCC Class B EN 61000 6 3 EN 50130 4 Document 10280_04 ...
Страница 6: ...LaserCOMPACT Product Guide VESDA iv ...
Страница 20: ...LaserCOMPACT Product Guide VESDA 12 Product Dimensions Figure 7 Dimensions in mm inches for LaserCOMPACT ...
Страница 40: ...LaserCOMPACT Product Guide VESDA 32 ...