LaserCOMPACT Product Guide
VESDA
®
14
Default Settings
Table 3 - Default values for the LaserCOMPACT detector
Parameter Default
Value
Range
Minimum
Access
Level
Minimum
Maximum
Event Log - Events
•
Smoke Level
Enabled
N/A
N/A
Adm
•
Alarms
Enabled
N/A
N/A
Adm
•
Faults
Enabled
N/A
N/A
Adm
•
User Action
Enabled
N/A
N/A
Adm
Fire Threshold
0.2% obs/m
(0.062% obs/ft.)
0.015% obs/m
(0.0046% obs/ft.)
20% obs/m
(6.25% obs/ft.)
Adm
Pre-Alarm Threshold
0.14% obs/m
(0.044% obs/ft.)
0.010% obs/m
(0.0031 obs/ft.)
1.995% obs/m
(0.6234% obs/ft.)
Adm
Alert Threshold
0.08% obs/m
(0.025% obs/ft.)
0.005% obs/m
(0.0015 obs/ft.)
1.990% obs/m
(0.6218% obs/ft.)
Adm
Alarm Delays…Fire
10 seconds
0 seconds
60 seconds
Adm
Alarm Delays…Pre-Alarm
10 seconds
0 seconds
60 seconds
Adm
Alarm Delays…Alert
10 seconds
0 seconds
60 seconds
Adm
Delay Times
Simultaneous
Simultaneous
Cumulative
Adm
Instantaneous - Fire
Disabled
N/A
N/A
Adm
AutoLearn
14 days
0 Hours
0 Minutes
0 Days
0 Hours
15 minutes
15 days
23 Hours
59 Minutes
Adm
Adm
Adm
Air flow Thresholds:
•
High Urgent
•
High Minor
•
Low Minor
•
Low Urgent
130%
120%
80%
70%
105%
105%
25%
25%
200%
200%
95%
95%
Adm
Adm
Adm
Adm
Communications:
•
Open-ended loop
•
Preferred Port
•
Network Delay
•
Health Check
None
A
15 seconds
45 seconds
N/A
N/A
10 seconds
40 seconds
N/A
N/A
45 seconds
60 seconds
Adm
Dst
Dst
Dst
Device ID
Name/Location
N/A
N/A
Adm
Faults Latched
Latched
N/A
N/A
Adm
Filter Service Interval
1825 days (5
years)
1 day
(Dependent up
on environment)
1825 days
(5 years)
Adm
Содержание LaserCOMPACT
Страница 2: ...LaserCOMPACT Product Guide VESDA 2 ...
Страница 5: ...VESDA LaserCOMPACT Product Guide iii FCC Class B EN 61000 6 3 EN 50130 4 Document 10280_04 ...
Страница 6: ...LaserCOMPACT Product Guide VESDA iv ...
Страница 20: ...LaserCOMPACT Product Guide VESDA 12 Product Dimensions Figure 7 Dimensions in mm inches for LaserCOMPACT ...
Страница 40: ...LaserCOMPACT Product Guide VESDA 32 ...