    EVH Hybrid Ventilation Unit

Installation, Operation and Maintenance Manual

Maintenance

6

Important

Continued

Ecovent

®

 EVH

 

units feature bulkhead-mounted fan plate assemblies.

Ensure that special care is taken when removing/replacing components/assemblies from
bottom-access units. Larger access panels may require the use of two or more persons.

THE CONTROL ACCESS COVER MUST BE REMOVED 

BEFORE 

THE UNIT ACCESS COVER

 to gain safe

access to the unit. Ensure all panels are safely replaced after access.

Supply Fan assembly
removal/installation

Fig.

16

Ecovent

®

 EVH 

units feature double inlet centrifugal fans mounted on an adapter plate.

The supply fans are clearly visible beneath the main access panel.
To remove/replace, unplug as per Fig.                , undo the fixing screws and carefully remove the
fan/adapter plate assembly, retaining all fixings.

To replace the fan assembly, secure one fixing leaving enough of a gap to allow the adapter
plate to slide into place. Fit the remaining fixing and tighten both. Ensure the impeller is free
running.  

Reconnect the supply plugs as in Fig.             ; if more than one plug is used, ensure the

correct plugs are reconnected as marked.

The fan mounting plates are slotted to aid plate alignment. It is important to keep the fan
assembly supported at all times; the fan assembly should not be considered supported until
all fixings are securely tightened.

Important

13

EVH1

Key components

Fig.

15

12

13

12

Содержание ecovent EVH

Страница 1: ...ates hazards associated with electric current and high voltages Indicates hazards that require safety advice for personnel or potential unit property damage Indicates important information page Introd...

Страница 2: ...e 7 Main Heating Null No Heating W LPHW Coil E Electric Heater Battery 8 Casework Lining Null Standard A1 Variant sequential 9 Handing LB Left Bottom Access RB Right Bottom Access 10 Main Filter Null...

Страница 3: ...lity of persons or objects coming into contact with the impeller whilst operational a guard should be fitted or steps taken to prevent this It is the installer s responsibility to ensure that access p...

Страница 4: ...ing detail Fig 3 Installation 4 Important Ecovent EVH units are intended to be connected to a wall or window mounted louvre This can be a direct connection from unit to louvre or via a specific transi...

Страница 5: ...ts Fix the bracket parts to both sides of unit and transition as shown using the M6 fixings provided Tape the joint using self adhesive rubber tape prior to assembly to prevent air leakage To finish t...

Страница 6: ...EVH LPHW units are fitted with a coil temperature sensor as standard ensuring that boilers run continuously in low ambient temperatures can help to prevent this On Ecovent EVH W units a Low Pressure...

Страница 7: ...that no internal components are damaged during this installation Make certain all swarf is removed before use It is the customer s responsibility to supply earth fault protection through the building...

Страница 8: ...t Eastleigh Hampshire SO53 4NF Tel 023 8046 1150 Fax 023 8026 1204 E mail vesltd ves co uk Web www ves co uk EVH Hybrid Ventilation Unit Installation Operation and Maintenance Manual Standard Wiring F...

Страница 9: ...t Eastleigh Hampshire SO53 4NF Tel 023 8046 1150 Fax 023 8026 1204 E mail vesltd ves co uk Web www ves co uk EVH Hybrid Ventilation Unit Installation Operation and Maintenance Manual Standard Wiring F...

Страница 10: ...witching by unauthorised operatives The Boost System Healthy indication will stop illuminating until the unit resumes normal operation The Open windows indication shall illuminate when the external te...

Страница 11: ...s the wind and elements may cause moving parts to windmill In general this series of units require little maintenance In the unlikely event of component failure spares are available from stock at VES...

Страница 12: ...bly removal installation Fig 16 Ecovent EVH units feature double inlet centrifugal fans mounted on an adapter plate The supply fans are clearly visible beneath the main access panel To remove replace...

Страница 13: ...o keep dampers clean could result in the damper becoming inoperative Clean damper blades and frames and lubricate with PTFE aerosol or equivalent For units with integrated heating the heating coil sho...

Отзывы: