Installing Converter Modules
The converter module is hot swappable. It can be installed with the system operating.
WARNING!
To prevent damage to the latching mechanism, ensure the handle is in the open position
when installing or removing a converter module. NEVER hold the handle in the closed position when
installing a converter module into a shelf.
Procedure
1.
Place the module into an unoccupied mounting slot without sliding it in completely.
2.
Loosen the captive screw on the module handle. Pull the handle to pivot it out of the module front panel
(this will also retract the latch mechanism located at the right side of the module). Refer to
Figure 2
for
latch mechanism illustration.
3.
Push the converter module completely into the shelf.
4.
Push the handle into the front panel of the module. Tighten the captive screw on the handle. This will
lock the module securely to the shelf.
5.
Repeat the above steps for each converter module being installed in the system.
6.
After the converter modules are physically installed in the mounting shelf(s), they are ready for
operation immediately after power is supplied to them.
7.
Certain functions (i.e. converter current limit, converter addressing) may require adjustment when
adding or replacing a converter module. Refer to the Power System documentation for instructions.
Figure 2:
Converter Module Handle/Latch Mechanism
Screw
Note: Handle must be
open when installing
or removing module.
Handle in
Closed Position