Vertiv
|
NetSure DC/DC Converter Module User Manual (UM1C24481500 / 11WA6101WB)
|
Rev. G
11
Table 2:
Monitoring Function
Commands / signals that can be
received by the Converter Module
from the Controller.
Information gathered by the
Controller from the Converter
Module.
•
Turn On/Off
•
Voltage Walk-in On/Off
•
HVSD Reset
•
Current Limit Adjustment
•
Voltage Adjustment
•
Fan Speed Control Enable/Disable
•
HVSD Threshold
•
Output Voltage
•
Output Current
•
Current Limit Setting
•
Temperature
•
Over Voltage Setting
•
On/Off Status
•
Fault Alarms, such as:
HVSD,
Fan Fail,
EEPROM Failure
•
Protection Alarms, such as:
Input Voltage Protection,
High Temperature Protection
•
Thermal Derating
•
Address
•
Code
•
Date
•
Software Version
•
Hardware Version
Mechanical Specifications
•
Weight: 5.5 lbs.
•
Dimensions (H x W x D): 1.63” (41.4mm) x 4.88” (124mm) x 14.96” (380mm).
•
Local Controls: None.
•
Local Status and Alarm Indicators:
a)
Power (Green)
b)
Protection (Yellow)
c)
Alarm (Red)