1.6. Environmental Requirements
1.6.1. Operating Environment
The operating environment of the Vertiv™ Liebert® XDC main unit meets the requirements of GB4798.3-2007,
.
Table 1-2 Operating Environment Requirements
Items
Requirements
Ambient temperature
Indoor
18 °C to 40 °C, RH<60%
Outdoor
-15 °C to 45 °C (Please contact Vertiv when outdoor
temperature below -15 °C)
Main unit protection level
IP20
Altitude
<1000m, more than 1000m, please contact Vertiv Technology
Operating voltage range
380 V to 415 V (-10% to +6%) V, 3 N~, 50 Hz/60 Hz
Pollution level
Level II
1.6.2. Storage Environment
The storage environment of the Liebert XDC main unit meets the requirements of GB4798.1-2005,
see
for details.
Table 1-3 Storage Environment Requirements
Items
Requirements
Storage environment
Indoor, clean (no dust)
Environment humidity
<95%RH
Ambient temperature
-25°C to +55°C
Storage time
The total transportation and storage time does not exceed 6 months, and the
performance needs to be re-calibrated after 6 months