Mechanical Installation
19
2.7.4. Parallel Connecting Cabinets
If the Vertiv™ Liebert® XDC is installed between the rows, it needs to be combined with the server rack. There are
connecting parts which helps in connecting the cabinet in parallel to the server racks, where users can easily fix them with
adjacent cabinets.
Note: Ensure to level the cabinets, before connecting the cabinets in parallel. For the adjustment method, refer
Section
Leveling the Cabinets.
Following are the steps for connecting the cabinets in parallel
1. Remove the L-shape combined cabinet part from the unit accessories kit.
shows position A (left) of the
L-shape combined cabinet parts.
2. Use M5 countersunk screws to fix the cabinet parallel connecting parts (L-shaped) on the unit frame (hinge side) and
the installation holes of the adjacent server rack, as shown in
3. Repeat the Step 1 and Step 2 for all other cabinets.
ITEMS
DESCRIPTION
ITEMS DESCRIPTION
1
Mounting screw GB819_1_2000_M5 x 12
2
Parallel kit
Figure 2-13 Connecting the Unit and Server Racks in Parallel