System description
1.1 - Liebert
®
PDX EconoPhase System
Liebert
®
PDX EconoPhase
System is designed to provide
precision air conditioning to computer racks in a data center or
computer room as efficiently and effectively as possible.
A
Liebert
®
PDX EconoPhase
System is composed of:
•
Liebert
®
PDX EconoPhase
version -
High Efficiency
, Digital
Scroll, floor-mounted indoor unit
•
Liebert
®
MC™ Condenser EconoPhase
version - Air-cooled
microchannel condenser, premium version
•
Liebert
®
PDX EconoPhase
-
Liebert
®
PDX EconoPhase
pump refrigerant module
The
Liebert
®
PDX EconoPhase
is an add-on module for use with an
air-cooled Liebert
®
PDX system. The
Liebert
®
PDX EconoPhase
will allow the system to switch to
Liebert
®
PDX EconoPhase
operation when the outdoor temperature is low enough to provide
the required temperature difference between the inside air and the
outside air, providing significant energy savings because there is
no need to operate the compressor. At lower temperatures, the
system switches one or both circuits from Compressor Mode to
Pump Mode. The pump consumes roughly 1/10th of the power
consumed by the compressor.
The
Liebert
®
PDX EconoPhase
system maintains this energy
efficiency by employing the heat absorption properties of a liquid
(pumped refrigerant) through a phase change. Refrigerant is
pumped as a liquid, becomes a gas within the Liebert
®
PDX
evaporator and then is returned to the Liebert
®
MC where it
condenses to a liquid. The subcooled liquid refrigerant from the
condenser is then run directly into the
Liebert
®
PDX EconoPhase
pumps and is circulated back to the Liebert
®
PDX unit (see Figure
1). The system will operate as a typical air-cooled direct expansion
system when outdoor ambient conditions are unfavorable
to EconoPhase operation. The pumps in the
Liebert
®
PDX
EconoPhase
pump module are turned off and bypassed during
compressor operation.
Condenser (Pump Mode)
Condenser (DX Mode)
Indoor Unit
r
o
p
a
V
x
i
M
r
o
p
a
V
/
d
i
u
q
i
L
Liquid
Pr
essur
e
Enthalpy
Tradtional Vapor Compression Cycle
EconoPhase Cycle
Fig.1 - Pressure enthalpy diagram, pumped refrigerant Liebert
®
EconoPhase