A - 2
Enclosure A - Electrode Humidifier
Liebert
®
PDX, EconoPhase Version - UM - 265133 - 29.08.2019
Important:
For drain water connection see details in Fig. 1:
•
Use a drain hose Ø 32 mm, maximum length 10 m with minimum5% gradient, don’t make siphon on this hose to avoid back pres-
sures in the drain piping. For configuration with bigger length or high head consider the PDX option with condensate pump.
•
Dispose the drain hose into an ordinary drainage network. (the drainage network should have a siphon (see Fig. 1) and must be able
to withstand temperatures up to 100° C and able to drain water flow up to 10l/min.
•
Pay attention in the manual drainage of the steam cylinder if the drainage network isn’t able to drain 10 l/min, risk of water overflow
on the humidifier.
A.2.1 - Electrode humidifier components
1.
chassis
2.
fill tank
2a.
conductivity electrodes
3.
cylinder
3a.
high level electrodes
3b.
immersed electrodes
3c.
filter inside the cylinder
4.
cylinder fastening strap
5.
hose kit
5a.
supply hose
5b.
fill hose
5c.
drain pump and overflow outlet hose
5d.
drain hose
6.
fill solenoid valve
7.
drain pump
8.
drain connection (diameter 32mm)
9.
steam outlet
10.
steam distribution hose
11.
manual valve (not supplied)
12.
mechanical filter (not supplied)
13.
supply hose (not supplied)
14.
connection hose
15.
drain hose with siphon (not supplied)
Fig. 1 - The humidifier and its components
Supply limit