Enclosure B - Technical data table
B - 1
Liebert
®
PDX, EconoPhase Version - UM - 265133 - 29.08.2019
Tab. 1 - Electrical data with premium fan module
* ATTENTION
Only universal (type B, B+) RCD protective devices are permitted.
NOTES:
•
The cables have to be sized in compliance with local standards and according to the type and characteristics (e.g. Amperes) of installation.
•
The data in the tables do not consider the absorbed current from the condensate pump and for other options not explicitly described.
•
The specific energy allowed to flow from the circuit breakers, installed by the user, must be lower than 300.000A
2
x s.
•
Prescriptions on the differential relay required to the user:
•
for special places (healthcare facilities, etc...) comply with the local regulations;
•
For ordinary places, a low sensitivity is suggested (300 mA) coordinated with the value of the ground heater (IEC 364): Ra 50/Ia (Art. 413.1.4.1, CEI 648 or IEC60364445);
•
In case of frequent over-voltages with mains impulse, it is advisable to install a selective differential and to evaluate the need for adopting other devices;
•
The FLA is for units without the options of condensate pump and condensing unit;
•
The FLA is for units with AUTOMATIC FUNCTIONS only: in manual mode operation the FLA must be lower than the max. current of the main switch.
Configuration
Model
Power supply
DIGITAL SCROLL Cooling System
min./max. Cu
cable size
FLA
[A]
LRA
[A]
Residual- Current Circuit Breakers
Inn = 0.3A (400V)*
Cooling Fan(s) +
Compressor(s)
PX082
400 V /
3 Ph + N /
50 Hz
+ earth
73
148
100A “C”
10..70mm
2
PX094
73
174
100A “C”
10..70mm
2
PX104
77
172
100 A “C”
10..70mm
2
PX120
101
219
125 A “C”
10..70mm
2
PX150
142
250
160 A “C”
10..70mm
2
PX165
160
300
200 A “C”
10..70mm
2
C Electrical
heaters (Dehumidification)
Fan(s) + Compressor(s)
+ Electrical heaters
PX082
400 V /
3 Ph + N /
50 Hz
+ earth
76
148
100A “C”
10..70mm
2
PX094
76
174
100A “C”
10..70mm
2
PX104
78
172
100A “C”
10..70mm
2
PX120
101
219
125A “C”
10..70mm
2
PX150
174
283
200A “C”
10..70mm
2
PX165
192
332
200A “C”
10..70mm
2
C Electrical
h Humidification
Fan(s) + Compressor(s)
+ electrode or infrared
humidifier
PX082
400 V /
3 Ph + N /
50 Hz
+ earth
87
148
100A “C”
10..70mm
2
PX094
87
174
100A “C”
10..70mm
2
PX104
91
172
125A “C”
10..70mm
2
PX120
115
219
125A “C”
10..70mm
2
PX150
156
264
160 A “C”
10..70mm
2
PX165
173
313
200 A “C”
10..70mm
2
Tab. 2 - EC fan connections
NOTE:
The EC fan settings can be modified acting on the control display (see Control manual).
(*) Setting for Nominal Airflow at standard conditions, Filters class F5, ESP: Downflow Up 20 Pa; Downflow Frontal 0 Pa.
Model
EC Fan signal [VDC]*
Downflow Up
Downflow Down
STD
Dehumidification
STD
Dehumidification
version with premium fan module
PX082 A
8,3
7,3
8
7
PX094 A
9
8
8,6
7,6
PX104 A
9,4
8,4
8,9
7,9
PX120 A
9,4
8,4
8,9
7,9
PX150 A
7,9
6,9
7,5
6,5
PX165 A
9,6
8,6
8,9
7,9
Tab. 3 - Electrical data (standard components)
Component
EC Fan (400V / 3Ph / 50Hz)
Model
Downflow Up
Downflow Down
OA* [A] FLA [A]
LRA
[A]
Nominal power*
[kW]
OA* [A] FLA [A] LRA [A] Nominal power*
[kW]
version with
premium fan
module
PX082 A
3x2.63
3x5
3x0.1
3x1.73
3x2.35
3x5
3x0.1
3x1.54
PX094 A
3x3.21
3x5
3x0.1
3x2.13
3x2.87
3x5
3x0.1
3x1.9
PX104 A
3x3.54
3x5
3x0.1
3x2.35
3x3.16
3x5
3x0.1
3x2.1
PX120 A
3x3.55
3x5
3x0.1
3x2.36
3x3.16
3x5
3x0.1
3x2.1
PX150 A
4x3,18
4x7,4
4x0,1
4x2,06
4x2,82
4x7,4
4x0,1
4x1,81
PX165 A
4x5,72
4x7,4
4x0,1
4x3,76
4x4,66
4x7,4
4x0,1
4x3,09
(*) At standard operating conditions, Filters class F5, ESP: Downflow Up 20 Pa; Downflow Frontal 0 Pa.
(**)At nominal operating conditions: Condensing temperature 45
0
C - Room conditions 24 C / 50% RH