Installation Drawings
Vertiv
Large System, 3-Phase UPS Battery System Installation Manual
32
Figure 29
Liebert attached junction cabinet—terminal details
Positive
Bus
Ground
Bus
1.25" x 0.5"
(32 x 13mm)
Slot 8 Places
Typical
Mounting Slots
8 Places
Typical
Negative
Bus
Positive Bus Bottom
Negative Bus Bottom
Ground Bus
1.75"
(44mm)
Typ
0.56"
(14mm)
Typ.
4.4" (112mm)
49.1"
(1248mm)
37.3"
(948mm)
26"
(661mm)
1.75" (44mm) Typ.
2"
(51mm) Typ.
2"
(51mm) Typ.
7"
(178mm)
11.4"
(290mm)
1.75" (44mm) Typ.
Ø 0.56" (14mm) Typ
Ø 0.56" (14mm) Typ
Ø 0.56" (14mm) Typ.
Positive
Bus Top
Negative
Bus Top
Bus Detail
Front View
Right Side
DO NOT DOUBLE-STACK LUGS
(two lugs on same side of
busbar). This is to prevent
the cables from coming into
contact with other busbars.
DUAL LUG
CONNECTION DETAIL
Lugs
Busbar
Bolt
CB1-3
CB1-3