![Vertiv Liebert NXL 1100 Скачать руководство пользователя страница 33](http://html1.mh-extra.com/html/vertiv/liebert-nxl-1100/liebert-nxl-1100_installation-manual_1008262033.webp)
Installation Drawings
Vertiv
Large System, 3-Phase UPS Battery System Installation Manual
26
Figure 23
Terminal details, top-terminal, 55" (1400mm) wide battery cabinet
R0.28" x
0.75" Long
4.8" (122mm)
1.75" (44mm) Typical
1.75"
(44mm)
7.5"
(190mm)
1.75"
(44mm)
1.75"
(44mm)
1"
(25mm)
21.4"
(545mm)
GROUND
BUSBAR
Ø0.56"
(14mm)
POSITIVE/NEGATIVE
BUS DETAIL
Access Plate
Only
1.3" (33mm)
Outside Panel
1.2" (31mm)
Outside Panel
3.6" (91mm)
Outside Panel
3.1" (79mm)
Outside Frame
5" (127mm)
Outside Frame
5.7"
(144mm)
3" (76mm)
12"
(305mm)
8.9"
(226mm)
Low
Voltage
High
Voltage
FRONT
CONDUIT DETAIL A
Top Conduit Plate)
FRONT
FRONT
CONDUIT DETAIL B
(Bottom Conduit Plate)
Positive
Terminal Bus (+)
Negative
Terminal
Bus (-)
TOP VIEW
TOP VIEW
(Door Open)
RIGHT SIDE VIEW
Cable Entry
Conduit Plate
(See Detail B)
Cable Entry
Conduit Plate
(See Detail A)
63.8"
(1621mm)
NOTES
1. Top and bottom cable entry available
through removable access plates.
2. Control wiring and power wiring must be
run in separate conduit.
3. All wiring must be in accordance with
national and local electrical codes.
BPP12001
Pg. 3, Rev. 0
Содержание Liebert NXL 1100
Страница 2: ...Liebert Large System 3 Phase UPS Battery System Installation Manual...
Страница 69: ...Specifications Vertiv Large System 3 Phase UPS Battery System Installation Manual 62 NOTES...
Страница 70: ...Specifications Vertiv Large System 3 Phase UPS Battery System Installation Manual 63...
Страница 71: ...Specifications Vertiv Large System 3 Phase UPS Battery System Installation Manual 64...