Mechanical Installation
Vertiv
Large System, 3-Phase UPS Battery System Installation Manual
6
1.4.2
Clearances
The Liebert battery system has no ventilation grilles at either side or at the rear of the battery system equipment.
It is important to leave a distance of 24" (610mm) between the top of the cabinet and the ceiling of the room
where it is installed to permit adequate circulation of air coming out of the unit and for service access.
Clearance around the front of the equipment should be sufficient to enable free passage of personnel with the
doors fully opened.
1.4.3
Raised Floor Mounting
If the equipment is to be placed on a raised floor, it should be mounted on a pedestal suitably designed to accept
the equipment point loading. Refer to the base view to design this pedestal.
1.5
S
YSTEM
C
OMPOSITION
A battery system can consist of a number of equipment cabinets, depending on the individual system design
requirements, e.g., Battery Cabinet, Junction Cabinet. Refer to
for the positioning of
the cabinets described below.