background image

pag. 3

Freecooling

 

--

  (Fig. 11 and Fig. 12)

When the outdoor temperature  is lower  than the  indoor one, 

the integrated modulating damper does open/close to cool the 

room with external air: compressor is off. The exhaust warmer 

air is automatically  rejected outside through the unit, without 

any additional louver (e.g. overpressure damper).  The para-

meters  can  be  adjusted. A  dedicated temperature  sensor is 

present  in  the  air  delivery  section  to  prevent  the  air  from 

enter-ing  the  room  at  too  low  temperatures  (adjustable 

parameter).  The  unit  is  further  equipped  with  a  washable 

metal  filter  next  to  the  outside  air  suction  inlet.  When  the 

expected conditions oc-cur, the servocontrol, managed by the 

microprocessor  control,  opens  the  movable  damper 

separating the flows of the inside and outside air.  In this way 

the outside air, sucked by the fan, flows inside the room and 

is  discharged  through  the  openings  of  the  freecooling 

compartment.  The  opening  degree  of  the  damper  is 

determined as a function of the set point value to be kept and 

of the intake air temperature (see Chap. 6).

5.1

 

---

 

Adjustment

 

of

 

the

 

condenser

 

fan 

speed

 (optional)

A sensor is positioned so as to detect constantly the 

condens-ing pressure of the refrigeration gas. On the basis 

of this in-formation, an electronic device (

Variex

) modulates 

the fan ro-tation speed in order to keep the condensing 

pressure within the allowed values. In this way, besides 

optimizing the com-pressor operation, you can have a 

remarkable reduction of the sound  pressure  level  (mainly 

during  the  night),  an  easier start---up of the compressor at 

low temperatures and some en-ergy saving.

For the calibration of the speed adjuster refer to chap. 7.

5.2

 

---

 

Emergency

 

cooling

 (optional)

5.2.1

 

--

 

Emergency

 

cooling

 

48VDC

The 48 VDC emergency cooling provides for the evaporating 

fans, the freecooling damper and the control to be always sup-

plied at 48 VDC, while the compressor, the condensing fan 

and the heaters are connected with the AC mains. If the AC 

main  supply  fails,  the  conditioner  does  not  stop  but 

continues  to  ventilate,  activating  the  integrated  Freecooling 

as  soon  as  the  relevant  conditions  are  reached, 

automatically  optimized  in emergency.

Important!

  For proper operation, the unit must be always 

fed by 48VDC.

CAUTION:

  For  safety  reasons  disconnect  the  QF1  and 

QF3 switches  (only  QF1  for  units  in  “no  emergency  cooling 

ver-sion”) when you want to stop the unit.

5.2.2

 

--

 

Emergency

 

cooling

 

230VAC--

 

50Hz

In  case  of  AC  mains  failure,  the  treating  fans,  the  control 

and  the  damper  servomotor  are  supplied  by  the  second 

line  at 230V/1Ph/50Hz arranged by the user (UPS/generator), 

ensur-ing the operation as in the 48 VDC version.

6

 

---

 

Operating

 

logics

The units, in the different versions, are featured by the auto-

matic operating logics specified here below.

6.1

 

---

 

Cooling

 

only

 

unit

6.1.1

 

--

 

Control

 

logic

The control algorithm is based on a one---step adjustment for 

the mechanical cooling with compressor: the control manages 

all  the  activation  delays,  so  as  to  ensure  the  correct 

operation and extend the operating life as much as possible.

Fig.

 

a)

 

Operation

 

of

 

the

 

cooling

 

only

 

unit

Set

Cooling

°

C

Cooling only unit

P Band

6.2

 

---

 

Unit

 

with

 

electrical

 

heating

6.2.1

 

--

 

Control

 

logic

For the hot and cold version the control algorithm is based on a 

one---step  adjustment  for  the  compressor---aided  electric 

heating and mechanical cooling. The control manages all its 

lags  in  the  activation  of  the  compressor,  as  previously  de-

scribed, so as to guarantee its correct operation and to make it 

function as long as possible.

6.2.2

 

--

 

Dead

 

band

In  this  version  the  parameter  “Dead  band”,  in  the  “optional 

devices” menu of themicroprocessor control is very important, 

and  enables  to  transfer  the  heating  semi---band  inserting  a 

non---sensitive  area  (ventilation  only)  between  the  set  point 

temperature  and  the  start  of  the  heating  semi---bands  (see 

Fig. b). In this way, without having to modify the proportional 

band, the electric heating can be activated at lower temperat-

ures (according to the value set for the dead band) compared 

to the standard setting, consequently reducing the power con-

sumption of the heaters and optimizing their operation accord-

ing to the site requirements.

Fig.

 

b)

 

Unit

 

operation

 

with

 

electrical

 

heating

Heating

Cooling 

°C

P Band

Dead Band

Set point

Cooling

Heating

°

C

1

/

Band

1

/

Band

1

/

Band

1

/

Band

Set point

Cooling and

heating unit

Cooling and

heating unit

with Dead

band

6.3

 

---

 

Unit

 

with

 

freecooling

6.3.1

 

--

 

Control

 

logic

The control algorithm is based on a single---stage adjustment 

for the heating and cooling with the compressor and on an 

ad-justment of  the proportional---

integrative type for the cooling in   the Freecooling mode, with 

setting of the set point and propor-tional band (P) (Fig. c).

The control manages all activation delays of the compressor, 

as we have seen in the 2 previous cases, in order to 

guarantee the proper operation and to extend its life as much 

as possible. The activation of the Freecooling mode occurs as 

a function of the difference (that can  be set) between  

the inside temperature   and the outside temperature.

This means that if the difference between the two temperatures 

increases  beyond  a  certain  value,  the  unit  automatically 

passes to the Freecooling function: the compressor is de---

ac-tivated and the analog output controls the 3---point 

servomotor of the damper. The damper opening is 

determined as a functionof thedifferencebetween 

theoutsideand insidetemperat-ures and as a function of the 

intake air temperature, which can-not be lower than a preset 

safety value. If the inside temperat-ure exceeds the 

proportional band by more than 20% for over 10 minutes, the 

unit shifts to the compressor---aided cooling and the 

Freecooling mode remains de---activated for 

1

/

hour. If  the 

inside  temperature  exceeds  the proportional  band by

Содержание Liebert HPW Series

Страница 1: ...Liebert HPW Outdoor Package Cooling System for Mobile Network Access Nodes User Manual English cod 265883 rev 31 01 2019...

Страница 2: ......

Страница 3: ...nce or spare parts read the identification label placed on the outside and inside of the unit IMPORTANT This manual may be subject to modification for complete and up to date information the user shou...

Страница 4: ...g pag 2 4 1 First start up or after a long halt pag 2 4 2 Start up with low outside temperature pag 2 5 Operation pag 3 5 1 Adjustment of the condenser fan speed optional pag 3 5 2 Emergency cooling o...

Страница 5: ...cabinet is made of heavy gauge galva nised steel panels painted on both sides with RAL7035 poly ester powder insulated with polyurethane foam fire proof class 1 Fixed panels are secured by water tight...

Страница 6: ...hes to ensure a suitable power supply it is possible to start and stop the unit following the instructions here below On the user interface check that the fans are working correctly make sure that the...

Страница 7: ...only unit 6 1 1 Control logic The control algorithm is based on a one step adjustment for the mechanical cooling with compressor the control manages all the activation delays so as to ensure the corre...

Страница 8: ...3 1 1 2 2 3 Freecooling mode P Band Set Compressor cooling mode P Band _C Cooling Heating 6 5 Alarm control The two alarm contacts available on the terminal board of the electric board are 1 General...

Страница 9: ...for units in emergency cooling ver sion 2 Remove the panels necessary for inspecting the refrigerat ing circuit 3 Connect a high efficiency vacuum pump to the needle valves Schr der on the gas and liq...

Страница 10: ...sible and do not entail disproportionate cost a Prevent leakage of these gases and as soon as possible repair any detected leakage b Ensure that they are checked for leakage by certified per sonnel c...

Страница 11: ...tions connected by refrigerant piping the label information will be on that part of the equipment which is initially charged with the refrigerant In case of a split system separate indoor and outdoor...

Страница 12: ...10 0 10 0 10 Evaporator fan DC operative current OA 2 A 2 6 2 6 2 6 2 6 Evaporator fan DC max current FLA 3 A 2 6 2 6 2 6 2 6 Evaporator fan DC starting current LRA A 0 1 0 1 0 1 0 1 Electric heating...

Страница 13: ...1 6 1 6 1 6 1 6 7 4 7 4 Evaporator fan DC power input 2 kW 0 10 0 10 0 28 0 45 0 45 0 45 Evaporator fan DC operative current OA 2 A 2 6 2 6 5 8 9 4 9 5 9 5 Evaporator fan DC max current FLA 3 A 2 6 2...

Страница 14: ...erative current OA 2 A 9 5 9 5 17 2 16 3 Evaporator fan DC max current FLA 3 A 9 6 9 6 19 2 19 2 Evaporator fan DC starting current LRA A 0 1 0 1 0 1 0 1 Electric heating optional Heating capacity kW...

Страница 15: ...rator fan AC power input 2 kW 0 14 0 14 0 14 0 14 Evaporator fan AC operative current OA 2 A 0 7 0 7 0 7 0 7 Evaporator fan AC max current FLA 3 A 0 7 0 7 0 7 0 7 Evaporator fan AC starting current LR...

Страница 16: ...fan AC starting current LRA A 1 6 1 6 1 6 1 6 7 4 7 4 Evaporator fan AC power input 2 kW 0 15 0 15 0 47 0 48 0 48 0 48 Evaporator fan AC operative current OA 2 A 0 7 0 7 2 3 2 3 2 3 2 3 Evaporator fan...

Страница 17: ...put 2 kW 0 49 0 49 0 78 0 80 Evaporator fan AC operative current OA 2 A 2 4 2 4 3 9 3 9 Evaporator fan AC max current FLA 3 A 2 4 2 4 4 8 4 8 Evaporator fan AC starting current LRA A 9 6 9 6 19 2 19 2...

Страница 18: ...oling unit version Differential current protection switch I nn 0 03A Minimum cable sizing 2 poles 4 poles Main line power supply 230V 1Ph 50Hz 400V 3Ph N 50Hz Unit EFC DC line power supply 48VDC main...

Страница 19: ...e switch HP STOP 28 0 bar START 20 0 bar fixed settings Manual reset pressing the push button Fan speed controller BV optional SET CUT OFF 21 2 bar standard factory set 15 0 bar optional set MAX SPEED...

Страница 20: ...230 60 50 15 828 15 858 100 380 380 380 380 70 370 45 TOP VIEW FRONT VIEW REAR VIEW SX SIDE VIEW DX SIDE VIEW 450 N 5 5 holes 8 for conditioner fixing Electrical supply Conditioned air inlet Condition...

Страница 21: ...8 15 828 15 858 60 50 460 1230 100 380 380 380 380 70 450 N 5 5 holes 8 for conditioner fixing TOP VIEW FRONT VIEW REAR VIEW SX SIDE VIEW DX SIDE VIEW Conditioned air inlet Conditioned air outlet Cond...

Страница 22: ...960 15 990 1401 445 50 445 100 390 390 390 390 241 1901 N 5 5 holes 8 for conditioner fixing Lift with eye bolts Electrical supply TOP VIEW FRONT VIEW REAR VIEW SX SIDE VIEW DX SIDE VIEW Conditioned...

Страница 23: ...60 990 50 640 43 370 970 370 148 100 390 390 390 390 241 N 5 5 holes 8 for conditioner fixing Electrical supply Lift with eye bolts TOP VIEW FRONT VIEW REAR VIEW SX SIDE VIEW DX SIDE VIEW Conditioned...

Страница 24: ...nd Operational B E areas 90o D A C E HPW Shelter PROTECTIVE ROOF F HPW A mm B mm C mm D mm E mm F mm S Models min 900 min 3500 800 450 min 500 0 M Models min 900 min 900 932 640 min 2000 0 No minimum...

Страница 25: ...pag 21 Fig 6 Lifting system Liebert HPW Liebert HPW WM05 06SO SD Liebert HPW WM06 08 10 13 15MO MD SHACKLES NOT SUPPLIED EYE BOLTS NOT SUPPLIED...

Страница 26: ...pag 22 Fig 7 Holes on the wall Liebert HPW models WM05 06SO SD 33 390 17 40 40 140 49 760 49 390 770 390 min 200 mm Installation of 1 unit Installation of 2 units SECTION...

Страница 27: ...3 Fig 8 Holes on the wall Liebert HPW models WM06 08 10 13 15MO MD 50 890 50 390 950 390 33 390 40 350 190 min 200 mm Installation of 1 unit Installation of 2 units SECTION 350 107 WM 13 15 57 WM 06 0...

Страница 28: ...pag 24 Fig 9 Sealing Liebert HPW models Insulating rubber mounted between the unit and the shelter External sealing with silicone after you have fixed the unit...

Страница 29: ...pag 25 Fig 10 Correct procedure for the bending of the air inlet and outlet duct...

Страница 30: ...agram Liebert HPW models WM05 06SO SD OUTSIDE INSIDE OUTSIDE INSIDE OUTSIDE INSIDE OUTSIDE INSIDE Freecooling Compressor cooling Freecooling Compressor cooling Exhaust air outlet from left lateral pan...

Страница 31: ...m Liebert HPW models WM06 08 10 13 15MO MD Upflow version OUTSIDE Freecooling Compressor cooling OUTSIDE OUTSIDE OUTSIDE Freecooling Compressor cooling Exhaust air outlet from left lateral panel INSID...

Страница 32: ...5 6 HP LP 11 POS DESCRIPTION POS DESCRIPTION 1 Compressor 7 Thermostatic expansion valve 2 High pressure switch HP 8 Evaporating coil 3 Condenser fan 9 Evaporator fan 4 Condensing coil 10 Low pressur...

Страница 33: ...rd Le Fabricant d clare que ce produit est conforme aux directives Europ ennes El Fabricante declara que este producto es conforme a las directivas Europeas O Fabricante declara que este produto est e...

Страница 34: ...red trademarks of Vertiv Co All other names and logos referred to are trade names trademarks or registered trademarks of their respective owners While every precaution has been taken to ensure accurac...

Отзывы: