pag. 8
Tab. 1 -- 50Hz Technical data for “48Vdc EMERGENCY FREECOOLING” unit versions (EFC--DC)
Model: HPW
WM05SD
WM05SO
WM06SD
WM06SO
Operating limits
Main power supply voltage
230V
±
10% / 1Ph / 50Hz
Emergency power supply voltage
48Vdc
±
17%
(with emergency cooling)
(*)
Outdoor conditions
from
10
°
C
(**)
from
---30
°
C
(***)
to
49
°
C
(****)
49.5
°
C
(****)
47
°
C
(****)
47.5
°
C
(****)
Indoor conditions with compressor running
(*****)
from
20
°
C, 30---
80% R.H.
21
°
C, 30---80% R.H.
22
°
C, 30---
80% R.H.
to
35
°
C, 40% R.H.
Storage conditions
from
---40
°
C, 5% R.H.
to
55
°
C, 90% R.H.
Sound pressure level
Outdoor sound pressure level
(1)
dB(A)
52.5
52.5
54.0
54.0
Indoor sound pressure level
(1)
dB(A)
57.0
57.0
57.0
57.0
Standard electrical features
Compressor --- AC power input
(2)
kW
1.26
1.25
1.63
1.63
Compressor --- AC operative current (OA)
(2)
A
5.8
5.7
7.6
7.6
Compressor --- AC max. current (FLA)
A
10.0
10.0
11.4
11.4
Compressor --- AC starting current (LRA)
A
35.0
35.0
47.0
47.0
Condenser fan --- AC power input
(2)
kW
0.24
0.24
0.24
0.24
Condenser fan --- AC max. power input
kW
0.24
0.24
0.24
0.24
Condenser fan --- AC operative current (OA)
(2)
A
1.1
1.1
1.1
1.1
Condenser fan --- AC max. current (FLA)
A
1.4
1.4
1.4
1.4
Condenser fan --- AC starting current (LRA)
A
1.6
1.6
1.6
1.6
Evaporator fan --- DC power input
(2)
kW
0.10
0.10
0.10
0.10
Evaporator fan --- DC operative current (OA)
(2)
A
2.6
2.6
2.6
2.6
Evaporator fan --- DC max. current (FLA)
(3)
A
2.6
2.6
2.6
2.6
Evaporator fan --- DC starting current (LRA)
A
0.1
0.1
0.1
0.1
Electric heating (optional)
Heating capacity
kW
1.5
Heating --- max. current
A
6.5
Weight
kg
170
175
OA:
Standard Operating Ampère
FLA:
Full Load Ampère
LRA:
Locked Rotor Ampère
Notes:
(*)
The emergency cooling option (EFC) is required.
(**)
If ON/OFF condensing fan control option has been chosen.
(***)
If modulating condensing fan control (Variex) option has been chosen.
(****)
Maximum outdoor temperature referred to:
---
30
°
C / 39.5% R.H. at the evaporating suction side, for WM05 ---06SD models;
---
27
°
C / 47% R.H. at the evaporating suction side, for WM05 ---06SO models.
(*****)
Conditions referred to the evaporating suction side; the min. indoor temperature is referred to 30% of indoor relative humidity and to the min. outdoor
temperature; for higher relative humidity and/or outdoor temperatures, the min. indoor temperature is lower than the table data.
(1)
Measured with 35° C outdoor temperature at 2m far from the unit; free field conditions.
(2)
Electrical features are referred to 35
°
C outdoor temperature, to nominal power supply and to the following Indoor conditions:
---
30
°
C / 39.5% R.H. at the evaporating suction side, for WM05 ---06SD models;
---
27
°
C / 47% R.H. at the evaporating suction side, for WM05 ---06SO models.
(3)
It refers to nominal speed (Factory setting).