Preliminary

 

operations

1.1

 

---

 

Foreword

The following manual describes the installation, operation and 

maintenance of Air Conditioners, series 

Liebert

 

HPW

.

Important:

Also consult the manual for the microprocessor control sup-

plied with the machine (if installed).

1.2

 

---

 

Check

 

operating

 

limits

The units are designed to operate within working ranges (see 

from  Tab. 1  to  Tab. 6).  These  limits are  referred to  new 

ma-chines or for those that have been correctly installed and 

ser-viced. The warranty clauses are no longer valid for any 

dam-age or malfunction that may occur during or due to 

operation outside the application values.

1.3

 

---

 

Check

 

sound

 

pressure

 

levels

From  Tab.  1  to  Tab.  6  shows,  for  the  internal  and  the 

external  side,  the  sound  pressure  levels  of  the  units  in 

standard config-uration, in continuous operation, at 2 m from 

the front surface of  the  machine,  at  1  m  height  in  free  field 

conditions.

1.4

 

---

 

Site

 

preparation

Liebert

 

HPW

 shall be mounted on a flat vertical surface. 

Prepare cut---outs on the wall for air supply and intake, electric-

al connections and unit fixing, according to the attached 

tem-plate (see Fig. 7 and Fig. 8). Wall cut outs shall be 

taped or sealed to prevent air or moisture entering the wall 

cavity.

1.5

 

---

 

Conditioner

 

inspection

On receiving the equipment immediately inspect its condition; 

report any damage to the transport company at once.

1.6

 

---

 

General

 

description

Liebert

 

HPW

 can be configured in over flow (

Liebert

 

HPW

 --- -

O) or down flow (

Liebert

 

HPW

---D) version, resulting  as

ex-tremely adaptive to different site layout; whatever is the

chosen delivery air version wall cuts are the same, the

condenser sec-tion is always positioned on the top part of

the unit reducing critical environment impact on condenser

efficiency and per-mitting easier and more effective

maintenance activities.

Liebert

 

HPW

, equipped withe the Emergency Cooling feature, 

does  not  stop  the  operation  even  in  case  of  mains  failure: 

fed  by  48  V  DC  emergency  supply  from  back  up  systems, 

Liebert

 

HPW

  autosets  its  parameters  to  ventilate  and 

maximise  the  freecooling  to  keep  the  indoor  temperature 

below  the  shut  down  limit,  reliablity  of  the  site  means  also 

reliability  of  the  unit.  Downflow  model  allows  to  start  the 

Emergengy  Freecooling  at  a  higher  external  temperature, 

reducing  the  site  shut  down risks.
No piping or refrigeration work is requested on site: just pre-

pare cut---outs in the wall, according to the template, andmake 

power  available.  As  soon  the  unit  is  fixed  and  sealed  on 

the wall,  place the  remote display  in  a  suitable position  and 

feed the unit.
Installation can be further speeded up using the fast plug con-

nector option (available on request): no wiring is requested on 

site and the connection can be performed even by non skilled 

personnel. In case of unit  replacement, the  fast plugs  allow 

re-placement ina few minutes.
The unit is designed to be installed outdoor, coping with the 

worst weather conditions.

The self ---supporting cabinet is made of heavy gauge galva-

nised steel panels, painted on both sides with RAL7035  poly-

ester  powder,  insulated  with  polyurethane  foam,  fire---proof 

class 1. Fixed panels are secured by water---tight, aluminum 

rivets.  All  external  screws  are  anti---vandalism  type,  to  be 

opened with a special tool supplied with the unit. Metal safety 

grids rated IP20  ---  protect the machine and prevent contact 

with sensitive/dangerous components.

The refrigeration compressor is a hermetic, scroll type, com-

plete with internal protection against over heating. A crankcase 

heater maintains a minimum refrigerant temperature to 

allow reliable start---up and operation even in very cold 

climate. Thecircuitispre---

chargedwithrefrigerantandincludesather-mostatic expansion 

valve, filter dryer and sight glass, low pres-sure and high 

pressure switches and two access valves. The compressor is 

housed in a compartment separated from the air flow and 

protected by an insulated panel closed with anti---vandalism 

screws,  accessible  from  the  front  side  for complete 

maintenance.
The electrical board is housed in a compartment isolated from 

the air stream and closed by a screwed on panel. It is built in 

accordance with EN 60204---1 recommendations.

1.7

 

---

 

Transport

Always keep the unit vertically upright.

If  possible  transport  the  unit  using  a  fork  lift  truck; 

otherwise use a crane with belts or cables,  avoiding the 

exerting of pressure on the top edges of the packing.

Unpack the unit as close as possible to its installation posi-

tion. Once unpacked, avoid stress being transmitted to its 

internal components.

For lifting the unit, the eyebolts available as accessory can 

be used.

Attention:

--- use eyebolts with thread M10;

--- screw the eyebolt completely;

--- always use 4 eyebolts at the same time.

1.8

 

---

 

Positioning

 

of

 

air

 

conditioner

S  The air Conditioner shall be installed in any 

environment

not affected by chemical agents (i.e. acid vapours).

Position the air conditioner so as to optimise the indoor air

distribution and avoid hot spots.

1.9

 

---

 

Service

 

area

The unit must be provided with a suitable Service Area, as 

fol-lows (see Fig. 5):

All 

ordinary

 

maintenance

  can  be  performed  from  the 

front.

Avoid possible obstacles hindering the air flows on the unit 

outer side.

2

 

---

 

Mounting

For a correct installation proceed as follows:

Apply an insulating anti---vibration rubber between the unit 

and the wall (see Fig. 9).

Before  installing  the  unit  open  the  integrated  ducts  for 

the air distribution (fins) in the openings of the rear panel, 

as in-dicated  in  the  following  points  (1)  and  (2)  and  in 

Fig. 10.

1

2

Secure  the  unit  to  the  wall  with  5+5  fasteners,  flat---

head type  with  washer  and  nut  on  the  indoor  side  (see 

from  Fig.  1  to  Fig.  4).  Hallow  wall  anchors  or  lag  bolts 

are suit-able as dictated by the wall constructions.

Seal the external boundary of the unit as preference 

(see Fig. 9).

Caution:

  The units are designed to keep the room to be 

conditioned as plenum, to prevent external dirt  and 

con-taminating agents from entering.

Plenum  may  reach high values in very sealed sites or if 

the filters are not correctly serviced. In this way, doors and 

win-dows  are  less  functional  and  the  unit  efficiency  is 

de-

Содержание Liebert HPW Series

Страница 1: ...Liebert HPW Outdoor Package Cooling System for Mobile Network Access Nodes User Manual English cod 265883 rev 31 01 2019...

Страница 2: ......

Страница 3: ...nce or spare parts read the identification label placed on the outside and inside of the unit IMPORTANT This manual may be subject to modification for complete and up to date information the user shou...

Страница 4: ...g pag 2 4 1 First start up or after a long halt pag 2 4 2 Start up with low outside temperature pag 2 5 Operation pag 3 5 1 Adjustment of the condenser fan speed optional pag 3 5 2 Emergency cooling o...

Страница 5: ...cabinet is made of heavy gauge galva nised steel panels painted on both sides with RAL7035 poly ester powder insulated with polyurethane foam fire proof class 1 Fixed panels are secured by water tight...

Страница 6: ...hes to ensure a suitable power supply it is possible to start and stop the unit following the instructions here below On the user interface check that the fans are working correctly make sure that the...

Страница 7: ...only unit 6 1 1 Control logic The control algorithm is based on a one step adjustment for the mechanical cooling with compressor the control manages all the activation delays so as to ensure the corre...

Страница 8: ...3 1 1 2 2 3 Freecooling mode P Band Set Compressor cooling mode P Band _C Cooling Heating 6 5 Alarm control The two alarm contacts available on the terminal board of the electric board are 1 General...

Страница 9: ...for units in emergency cooling ver sion 2 Remove the panels necessary for inspecting the refrigerat ing circuit 3 Connect a high efficiency vacuum pump to the needle valves Schr der on the gas and liq...

Страница 10: ...sible and do not entail disproportionate cost a Prevent leakage of these gases and as soon as possible repair any detected leakage b Ensure that they are checked for leakage by certified per sonnel c...

Страница 11: ...tions connected by refrigerant piping the label information will be on that part of the equipment which is initially charged with the refrigerant In case of a split system separate indoor and outdoor...

Страница 12: ...10 0 10 0 10 Evaporator fan DC operative current OA 2 A 2 6 2 6 2 6 2 6 Evaporator fan DC max current FLA 3 A 2 6 2 6 2 6 2 6 Evaporator fan DC starting current LRA A 0 1 0 1 0 1 0 1 Electric heating...

Страница 13: ...1 6 1 6 1 6 1 6 7 4 7 4 Evaporator fan DC power input 2 kW 0 10 0 10 0 28 0 45 0 45 0 45 Evaporator fan DC operative current OA 2 A 2 6 2 6 5 8 9 4 9 5 9 5 Evaporator fan DC max current FLA 3 A 2 6 2...

Страница 14: ...erative current OA 2 A 9 5 9 5 17 2 16 3 Evaporator fan DC max current FLA 3 A 9 6 9 6 19 2 19 2 Evaporator fan DC starting current LRA A 0 1 0 1 0 1 0 1 Electric heating optional Heating capacity kW...

Страница 15: ...rator fan AC power input 2 kW 0 14 0 14 0 14 0 14 Evaporator fan AC operative current OA 2 A 0 7 0 7 0 7 0 7 Evaporator fan AC max current FLA 3 A 0 7 0 7 0 7 0 7 Evaporator fan AC starting current LR...

Страница 16: ...fan AC starting current LRA A 1 6 1 6 1 6 1 6 7 4 7 4 Evaporator fan AC power input 2 kW 0 15 0 15 0 47 0 48 0 48 0 48 Evaporator fan AC operative current OA 2 A 0 7 0 7 2 3 2 3 2 3 2 3 Evaporator fan...

Страница 17: ...put 2 kW 0 49 0 49 0 78 0 80 Evaporator fan AC operative current OA 2 A 2 4 2 4 3 9 3 9 Evaporator fan AC max current FLA 3 A 2 4 2 4 4 8 4 8 Evaporator fan AC starting current LRA A 9 6 9 6 19 2 19 2...

Страница 18: ...oling unit version Differential current protection switch I nn 0 03A Minimum cable sizing 2 poles 4 poles Main line power supply 230V 1Ph 50Hz 400V 3Ph N 50Hz Unit EFC DC line power supply 48VDC main...

Страница 19: ...e switch HP STOP 28 0 bar START 20 0 bar fixed settings Manual reset pressing the push button Fan speed controller BV optional SET CUT OFF 21 2 bar standard factory set 15 0 bar optional set MAX SPEED...

Страница 20: ...230 60 50 15 828 15 858 100 380 380 380 380 70 370 45 TOP VIEW FRONT VIEW REAR VIEW SX SIDE VIEW DX SIDE VIEW 450 N 5 5 holes 8 for conditioner fixing Electrical supply Conditioned air inlet Condition...

Страница 21: ...8 15 828 15 858 60 50 460 1230 100 380 380 380 380 70 450 N 5 5 holes 8 for conditioner fixing TOP VIEW FRONT VIEW REAR VIEW SX SIDE VIEW DX SIDE VIEW Conditioned air inlet Conditioned air outlet Cond...

Страница 22: ...960 15 990 1401 445 50 445 100 390 390 390 390 241 1901 N 5 5 holes 8 for conditioner fixing Lift with eye bolts Electrical supply TOP VIEW FRONT VIEW REAR VIEW SX SIDE VIEW DX SIDE VIEW Conditioned...

Страница 23: ...60 990 50 640 43 370 970 370 148 100 390 390 390 390 241 N 5 5 holes 8 for conditioner fixing Electrical supply Lift with eye bolts TOP VIEW FRONT VIEW REAR VIEW SX SIDE VIEW DX SIDE VIEW Conditioned...

Страница 24: ...nd Operational B E areas 90o D A C E HPW Shelter PROTECTIVE ROOF F HPW A mm B mm C mm D mm E mm F mm S Models min 900 min 3500 800 450 min 500 0 M Models min 900 min 900 932 640 min 2000 0 No minimum...

Страница 25: ...pag 21 Fig 6 Lifting system Liebert HPW Liebert HPW WM05 06SO SD Liebert HPW WM06 08 10 13 15MO MD SHACKLES NOT SUPPLIED EYE BOLTS NOT SUPPLIED...

Страница 26: ...pag 22 Fig 7 Holes on the wall Liebert HPW models WM05 06SO SD 33 390 17 40 40 140 49 760 49 390 770 390 min 200 mm Installation of 1 unit Installation of 2 units SECTION...

Страница 27: ...3 Fig 8 Holes on the wall Liebert HPW models WM06 08 10 13 15MO MD 50 890 50 390 950 390 33 390 40 350 190 min 200 mm Installation of 1 unit Installation of 2 units SECTION 350 107 WM 13 15 57 WM 06 0...

Страница 28: ...pag 24 Fig 9 Sealing Liebert HPW models Insulating rubber mounted between the unit and the shelter External sealing with silicone after you have fixed the unit...

Страница 29: ...pag 25 Fig 10 Correct procedure for the bending of the air inlet and outlet duct...

Страница 30: ...agram Liebert HPW models WM05 06SO SD OUTSIDE INSIDE OUTSIDE INSIDE OUTSIDE INSIDE OUTSIDE INSIDE Freecooling Compressor cooling Freecooling Compressor cooling Exhaust air outlet from left lateral pan...

Страница 31: ...m Liebert HPW models WM06 08 10 13 15MO MD Upflow version OUTSIDE Freecooling Compressor cooling OUTSIDE OUTSIDE OUTSIDE Freecooling Compressor cooling Exhaust air outlet from left lateral panel INSID...

Страница 32: ...5 6 HP LP 11 POS DESCRIPTION POS DESCRIPTION 1 Compressor 7 Thermostatic expansion valve 2 High pressure switch HP 8 Evaporating coil 3 Condenser fan 9 Evaporator fan 4 Condensing coil 10 Low pressur...

Страница 33: ...rd Le Fabricant d clare que ce produit est conforme aux directives Europ ennes El Fabricante declara que este producto es conforme a las directivas Europeas O Fabricante declara que este produto est e...

Страница 34: ...red trademarks of Vertiv Co All other names and logos referred to are trade names trademarks or registered trademarks of their respective owners While every precaution has been taken to ensure accurac...

Отзывы: