80
User Manual 10H52267UM60 - Rev. 1 - 09/2018
EXS
Chapter 10
Specifications
This section lists the UPS specifications.
10.1
Conformity and standards
Table 10-1 Conformance and standards
Item
standard
Conduction emission
IEC/EN62040-2
The standard product meets Class C3, the product with the C2 option installed meets
Class C2
EFT
IEC/EN62040-2: AC port pulse burst withstand rating of 4 KV/5 KHz
Current harmonics
IEC/EN62040-2, 16A<I
≤
75A
Input Voltage Surge
IEC/EN62040-2, 16A<I
≤
75A
Immunity to electrostatic discharges
IEC/EN62040-2: Level 3
Radiation immunity
IEC/EN62040-2: Level 3
PFMF
IEC/EN62040-2: Level 4
Surge protection
Meets IEC/EN62040-2: live line to earth withstand level 4 (4kV); withstand level 3
between live lines (2kV)
Safety
IEC/EN62040-1
SPD test
Meets ANSI C62.41: live line to earth withstand 6kV/3kA
Meets YD/T944: live line to earth withstand 5kA
10.2
Environmental Characteristics
Table 10-2 Environmental characteristics
Item
Unit
Meaning
Noise at 1m (measured frontally)
dB (A)
<58
Altitude
m
≤
1500, no derating;
≥
1500 (derate power by 1% per 100m); up to 3000
Relative humidity
%RH
5 ~ 95%, non condensing
Operating temperature
°C
0 ~ 40°C (Note: Battery life is halved for every increase of 10°C above 20°C)
UPS storage and transportation
temperatures
°C
-40°C ~ +70°C (battery excluded), -20°C ~ +30°C (battery included)
Over-voltage level
Overvoltage level 2
Pollution level
Pollution level 2
10.3
Mechanical Specifications
Table 10-3 Mechanical specifications
Item
Unit
Rated power (kVA)
30
40
Internal battery
excluded
Internal battery
included
Internal battery
excluded
Internal
battery
included
Dimensions (W × D × H)
mm
440×750×1600
Net weight
kg
200
496
200
576
Gross weight
kg
250
546
250
626
Colour
Black
Protection rating
IP20 (front door open or closed)