28
User Manual 10H52267UM60 - Rev. 1 - 09/2018
EXS
Connect the power cables to the respective terminals and secure the PE cables to the PE terminal, as illustrated in
Figure 3-1. Fit shielding to protect the power cable from external damage. Refer to Table 3-1 for the tightening torque
values.
4. Make sure that the cables are connected securely and correctly, then replace the rear protective cover.
This completes the power cable connection procedure.
Guard ring
iN
iN
oA
oB
oC
oN
BAT+
BAT_N
BAT-
PE
oN
mA
bB
bA
mC
mB
bC
Figure 3-2
Power cable terminal connections and routing methods (separate bypass configuration, external battery connection)
Procedures:
1. Remove the protective cover from rear of the cabinet.
2. Remove the three common input configuration shorting cables, as shown in Figure 3-1. Remember to replace the
power cable retaining bolts correctly. Refer to Table 3-1 for the tightening torque values.
3. As shown in Figure 3-2, feed the main input cables (mA, mB, mC, iN), bypass input cables (bA, bB, bC, iN) and a PE
cable into the cabinet via cable gland 1, feed the output cables (oA, oB, oC, oN) and a PE cable into the cabinet via
cable gland 2, and then feed the external battery cables (BAT+, BAT_N, BAT-) and a PE cable into the cabinet via cable
gland 3.
Connect the power cables to the respective terminals and secure the PE cables to the PE terminal, as illustrated in
Figure 3-2. Fit shielding to protect the power cable from external damage. Refer to Table 3-1 for the tightening torque
values.
4. Make sure that the cables are connected securely and correctly, then replace the rear protective cover.