66
User Manual 10H52267UM60 - Rev. 1 - 09/2018
EXS
Figure 6-4
LBS system (UPS module)
LBS
Rectifier
Bypass
Q1
Q2 Q3
UPS 1
UPS 4
Q5
Q1
Q2 Q3
Q5
cable
To load
STS
Rectifier
Parallel
Rectifier
Bypass
Q1
Q2 Q3
UPS 1
UPS 4
Q5
Q1
Q2 Q3
Q5
cable
Rectifier
Parallel
Figure 6-5
LBS system (parallel system)
Note
In a dual-bus system, the two UPS systems must have the same power rating, voltage and frequency, and the load must not
exceed the power rating of a single UPS module system.
6.5.3
Connecting Power Cables
The power cable of dual-bus system is similar to that of single system. Refer to 3.1 Connecting the Power Cables.
The bypass and main input supplies must use the same neutral line input terminal. If the input is fitted with a current
leakage protection device, the device must be fitted upstream of the neutral line input terminal
.