480V User Manual |
16
Figure 5
Battery cabinet terminal detail, 1200mm cabinet; 50-250kVA UPS
for additional details.
Table 2
Interconnect wiring for UPS to battery cabinet
Ru
n
From
To
Conductors
A
UPS Battery Busbar
External Battery Cabinet
Busbar
Positive, Negative
B
Battery Cabinet Terminal
Block TB1
UPS Static Bypass
Assembly J22
Battery Breaker Shunt and Aux
Contacts
1.65" (42mm)
(2 Typically)
1.75"
(45mm)
1.75"
(45mm)
Ø 0.56"
(14mm)
6 Places
Ø 0.56"
(14mm)
6 Places
0.85"
(22mm)
0.85"
(22mm)
Negative Busbar
NEGATIVE AND
POSITIVE BUSBARS
Positive Busbar
Negative
Busbar
Positive
Busbar
Ground Bus
GROUND BUS
Battery
Breaker
Alber BDSUi
(Optional)
LEFT SIDE
Panel Removed
RIGHT SIDE
Panel Removed
FRONT
Door Removed
1. Control wiring and power wiring must be run in separate conduits.
2. Vertiv recommends using only copper cables.
3. All wiring must be in accordance with national and local electrical codes.
4. Vertiv will supply the interconnect cables if the battery cabinet is attached to the UPS.
EXM46004
Rev. 0
Bolt Shaft Size: M12
Torque: 428 lb-in (48Nm)
See Table 2 for interconnect wiring
from UPS to battery cabinet.
Содержание Liebert EXM 480V
Страница 1: ...Liebert EXM 480V External Battery Cabinet User Manual...
Страница 34: ...Vertiv Liebert EXM EBC 480V User Manual 30 Figure 14 Battery cabinet outline and main components 1200mm cabinet...
Страница 46: ...Vertiv Liebert EXM EBC 480V User Manual 42 NOTES...
Страница 47: ...Vertiv Liebert EXM EBC 480V User Manual 43...
Страница 48: ...Vertiv Liebert EXM EBC 480V User Manual 44...
Страница 49: ......