Vertiv
| Liebert
®
EXM
™
EBC
™
480V User Manual |
10
5.
Connect the system battery cables from the UPS battery terminals (+, -) to battery cabinet breaker BCB
(+, -) as shown in
. Be sure that the battery connections are made with the right polarity, and
tighten the connections to the torque specified in
. Do not close the battery circuit breaker before
the equipment has been commissioned.
6.
Connect TB1 from battery cabinet to J22 on the UPS according to
Figure 2
Bolting the Liebert EXM Battery Cabinet to the Liebert EXM UPS
NOTE
The shunt trip drive capability for the battery breaker is 220VDC at 2.4A.
Table 1
Control wiring for Liebert EXM to battery cabinet
From
To
Liebert EXM UPS Bypass
Module (J22)
Battery Cabinet
Terminal Strip (TB1)
J22.15
TB1-12
J22.13
TB1-11
J22.11
TB1-10
J22.1
TB1-6
J22.3
TB1-7
J22.5
TB1-8
J22.7
TB1-9
DETAIL B
Liebert EXM
Battery
Cabinet
Liebert EXM
UPS
3
Washer
Split, M10
Flat Washer
M10
Hex Head
Bolt
M10 x 30mm
1
2
B