2 - 6
Application of Liebert
®
CRV
Liebert CRV - PD - 265086 - 11.01.2018
Fig. 2c Liebert
®
CRV – Two Rows Placement
Cooling unit location within a row becomes less critical when deployed in SmartAisle™ containment,
but it is recommended that the Liebert
®
CRV be evenly spaced in each row. Using room barriers, such
as walls shown in Fig. 2.d and Fig. 2.e, it can be very effective in simulating aisle containment.
When the depths of a Liebert
®
CRV and neighboring server rack are not the same, it is important to
align the front edges of the Liebert
®
CRV with the front edges of the neighboring server racks to allow
for proper air distribution.
Fig. 2d Simulated aisle containment using room barriers – single row
Cold Supply Air – Cold Aisle
Rack Rack Rack Rack
Rack Rack
Hot Return Air – Hot Aisle
Rack Rack
Rack Rack Rack Rack
Hot Return Air – Hot Aisle
C
R
V
C
R
V
C
R
V
C
R
V
C
R
V
C
R
V
Cold Supply Air
Hot Return Air
1.8m Maximum
Distance to Barrier
Rack Rack Rack Rack Rack
C
R
V