9 - 41
Refrigerant, Hydraulic and Electrical Connections
Liebert CRV - PD - 265086 - 11.01.2018
9.2 CW electrical field connections descriptions - 50 Hz
STANDARD ELECTRICAL CONNECTIONS
1.
Primary high voltage entrance Quantity (2) 28mm diameter concentric knockouts located in bottom of
box
2.
Secondary high voltage entrance Quantity (2) 35mm diameter concentric knockouts located in top of box
3.
Primary low voltage entrance Quantity (1) 18mm diameter knockouts located in bottom of unit
4.
Secondary low voltage entrance “ Quantity (2) 22mm diameter knockouts located in top of box
5.
Earth ground - Terminal for field supplied earth grounding wire(0.25 ÷ 6mm
2
).
6.
Remote unit shutdown - Replace existing jumper between terminals 52 & 53 with field supplied normally
closed switch having a minimum 75VA, 24VAC rating. Use field supplied Class 1 wiring.
7.
Customer alarm inputs - Terminals for field supplied, normally closed contacts, having a minimum 75VA,
24VAC rating, between terminals 61 & 63. Use field supplied Class 1 wiring.
8. General alarm - On any alarm, normally open dry contact is closed across terminals 400,401 for remote
indication. 2 AMP, 24VAC max load. Use Class 1 field supplied wiring.
9. Warning alarm - On any alarm, normally open dry contact is closed across terminals 300,301 for remote
indication. 2 AMP, 24VAC max load. Use Class 1 field supplied wiring.
10. Fan motor on - On any call for fans operation, normally open dry contact is closed across terminals 70 &
71. 2 AMP, 24VAC max load. Use Class 1 field supplied wiring.
OPTIONAL ELECTRICAL CONNECTIONS
11.
Smoke sensor alarm (with smoke sensor option)- The smoke sensor is factory installed ,and senses the
delivery air;it is connected across terminals 51 - 53 and send a visual and an audible alarm.
This smoke sensor is not intended to function as, or replace, any room smoke detection system that
may be required by local or national codes. 1 AMP, 24VAC max load. Use Class 1 field supplied wiring.
12.
Condensate alarm (with condensate pump option) : On pump high water indication, Normally open dry
contact is connected to a purple wire installed inside of the box near the pump. This contact is closed in
case of a high water indication thus remote High Water indication is provided. 1AMP, 24Vac max load;
use class 1 field supplied wiring.
OPTIONAL LOW VOLTAGE TERMINAL PACKAGE CONNECTIONS
13.
Flooding alarm (liquistat) – The flooding alarm detects the presence of water and activate an alarm.
The sensor is connect across terminals 105 & 106 and up to 5 sensors can be connected to the same
flooding alarm device,to control many points in the bottom of the unit.