Modbus over IP configuration
MSS
40
User Manual 10H52252UMA0 - Rev. 2 - 09/2019
P/N
LENGTH
(L=m)
10H46934P010
10
10H46934P020
20
10H46934P030
30
10H46934P040
40
For different lengths than standard, contact the Customer Service.
2.3
Connectivity Panel
MSS is equipped with the following interfaces:
•
XS3 - Slot for Connectivity Products (X3 will be switched to XS3 to parameterize Connectivity
Products);
•
XS6 - Slot for LIFE.net modem;
•
X3 - Serial Interface for Service;
•
X6 - Serial Interface for external LIFE.net;
•
XT1/2 - 4-pole screw connector; not used;
•
X9 - RJ-45 Ethernet Interface to set-up Modbus over IP and SNMP;
•
XT3/8 - Not used;
•
XT4 - Not used;
•
TB1 - 2x16-pole screw connector for input and output contacts;
•
X19A/B - 2x15-pole connectors for parallel MSS connection;
•
X20 - RJ-45 Interface for synchronization with external signal;
•
XT1 - 2-pole screw connector for backfeed output contact;
•
XP10 - EPO connector;
•
XP11 - INPUT connector;
•
XP12 - OUTPUT connector;
•
X12 - RJ-45 Secondary Ethernet Interface (ex: for Modbus application).
Figure 2-5 Connectivity panel
2.3.1
Slot for Connectivity Products - XS3
This slot is the recommended interface for the SNMP Adapter Manage UPS NET. This adapter provides
an independent external network interface for communication with connectivity products.
When an SNMP Adapter is inserted into XS3, the interface X3 is connected to the XS3 slot to allow the
parameterization of the SNMP Adapter, if necessary. The normal performance of X3 for service and
placement into service may be reduced by this.
The slot is SELV - isolated from UPS primary circuits.