MSS
Installation Procedure
User Manual 10H52252UMA0 - Rev. 2 - 09/2019
13
With the configuration MMS FRAME and TCE or MSS connections to customers, the bars that are to be
connected directly to the module and tightened to the torque as per the following table:
Table 2 - Connections for MSS + TCE/Customer cabinets
Connections type
Grease type
(P/N 10H46591)
Tightening
torque (Nm
± 20%)
Screw type
Busbar
type
Cu busbar on
Al heatsink
(MSS 2000-3000)
AFL: 2-EJC
42,5
M12x30
+ flat large
150x8
Cu busbar on
Cu heatsink
(MSS 4000-5000)
Electrolube: 2G
(CG52B)
or
GLUESSER:
GLEB1
50
M12x40
+ flat
150x12
Fe connections
between cabinet
/
10
M6x25
+ flat
/