Parallel Power Extend Converter Installation
NOTE!
Mounting bracket kit P/N 565391 with distribution panel 582127000 List AA is used in the
following procedure. Other kits and distribution panels similar.
To install a single power extend converter, refer to the procedure “Single Power Extend Converter Installation”
starting on page 23.
Procedure
[ ] 1.
If the power extend converters are to be installed for a newly connected load, connect the load and
load return cables to the distribution panel for the position to be occupied by the power extend
converters. At the same time, connect the power extend converters return wire faston tabs (P/N
565990) provided with the power extend converters to the distribution panel return busbar (use the
same location and hardware used for the return lead to the load). At the same time, connect the
power extend converters paralleling busbar (P/N 60016097 for paralleling two converters, P/N
514717 for paralleling three converters) ordered separately to the distribution panel load busbars
(use the same location and hardware used for the return lead to the load). See
. Torque
[ ] 2.
If the power extend converters are to replace an existing circuit breaker in the distribution panel,
remove the circuit breaker and verify the load and return cables to the distribution panel for the
position to be occupied by the power extend converters are wired and labeled correctly. (It may be
advantageous, depending on the size and location of the return cables for each circuit to be
powered by the power extend converter, to loosen and temporarily move the load side cables for
easier access to the hardware on the return landing position studs.) Connect the power extend
converters return wire faston tabs (P/N 565990) provided with the power extend converters to the
distribution panel return busbar (use the same location and hardware used for the return lead to the
load). At the same time, connect the power extend converters paralleling busbar (P/N 60016097 for
paralleling two converters, P/N 514717 for paralleling three converters) ordered separately to the
distribution panel load busbars (use the same location and hardware as the load lead to the load).
See
. Torque as indicated