38

78D2082

WDV See-thru Gas Fireplace

TOuch Screen reMOTe cOnTrOl OperaTIOn

ing  to  the  difference  between  the  Set  temperature  and 

the Room temperature. There is no manual flame height 

adjustment. The fan speed will also automatically adjust 

if turned on.

nOTe:

 there will a 10 second delay for the flame adjust-

ment when the fireplace is turned on.
1.  When Set Temp. is 3° F or higher than Room Temp., 

flame height will be on High.

2.  When  Set  Temp.  is  2°  F  higher  than  Room  Temp., 

flame height will be on Medium.

3.  When  Set  Temp.  is  1°  F  higher  than  Room  Temp., 

flame height will be on Low.

4.  When Set Temp. is equal to Room Temp., flame height 

does not change (stays on low).

5.  When Set Temp. is lower than Room Temp., the fire-

place will be shut off.

6.  When  Set  Temp.  is    1°  F  higher  than  Room  Temp., 

again the flame height will be on Low.

7.  the  fan  speed  follows  the  flame  height,  if  the  fan  is 

turned on.

To  exit  Smart  Mode

® 

thermostat  and  shut  off  the  fire-

place;
  a. push and hold the THERMO buttons for 3 sec-

onds, Or

  b. press the OFF button, Or

  c. slide down on the arrow buttons.

To shut off the Smart Mode

® 

thermostat option and return 

to regular thermostat mode, press and hold the THERMO 

button and the ON/UP button at the same time for 3 sec-

onds again.

Blower Speed control

Figure 50

nOTe:

 Blower will only work with 

flame on.
The blower speed control function 

is used to adjust the speed of the 

blower connected to the Signature 

Command System. There are four 

speed  levels,  Off,  Low,  Medium, 

High.
1.  Press the FAN button to enter 

the blower speed control mode. 

The fan icon will start flashing.

2.  Press the ON/up and OFF/down button to increase/de-

crease the blower speed.

3.  Press the fan button again to confirm the speed set-

ting. If the fireplace is on, the blower speed will take 

effect right away; if the fireplace is off, the receiver will 

remember this setting and the blower is still off (see 

blower On Delay and Off Delay in the next section).

4.  After the signal is sent, the ON/up and OFF/down but-

tons become flame height controller again.

5.  When the fan button is flashing, slide up and down on 

the arrow buttons will turn the blower speed to High 

or Off directly without pressing the fan button again to 

confirm.

6.  If the blower  is turned on using  the FAN button, the 

blower  speed  will  adjust  automatically  when  using 

Smart Mode

® 

thermostat (See Smart Mode

® 

thermo-

stat section).

Blower  On  Delay  Time  and  Off 

Delay Time Setup

Figure 51

1.  Hold the FAN button for 3 sec-

onds  until  two  numbers  ap-

pear  on  the  LCD  screen.  The 

left number is blower On Delay 

and the right number is blower 

Off Delay Time.

2.  When the first number is flash-

ing,  use  the  ON/up  button  to 

set the desired On Delay Time 

from 0 to 15 min.

3.  Press the OFF/down button to 

jump to the Off Delay Time setup.

4.  When the second number is flashing, use the ON/up 

button again to set the desired Off Delay Time from 0 

to 15 min.

5.  Press the OFF/down button again to finish the setup 

and the new settings will be transmitted to the receiv-

er.

6.  The  default  settings  are  5  minutes  for  the  On  Delay 

Time and 8 minutes for the Off Delay Time, as shown.

light Brightness control

Figure 52

The light brightness control func-

tion is used to adjust the bright-

ness of the light bulbs connected 

to the AC module on the Signa-

ture  Command  System.  There 

are  four  light  brightness  levels 

defined: Off, Low, Medium, High
1.  Press the LIGHT button to en-

ter the light brightness control 

mode.  The  LIGHT  icon  will 

start flashing.

2.  Press  the  On/up  and  OFF/

down buttons to increase/de-

crease the light brightness (Off-Low-Medium-High).

3.  Press the light button again to confirm the setting. The 

new setting will be transmitted to the receiver.

4.  After the signal is sent, the On/up and Off/down but-

FP2657
Light bright control

Figure 52

FP2656
blower delay setup

Figure 51

FP2655
blower speed control

Figure 50

Содержание WDVST500

Страница 1: ...manual For assistance or additional information consult a qualified installer service agency or the gas supplier This appliance may be installed in an aftermarket permanently located manufactured home...

Страница 2: ...Wiring 25 Command Center Wall Installation 25 Wall Switch Installation 25 SCS Wiring Diagram 26 Thank you and congratulations on your purchase of a Vermont Castings Group Fireplace PLEASE READ THE IN...

Страница 3: ...d by a qualified service person with glass door properly seated and sealed combustion leakage can occur CARBON MONOXIDE POISONING Early signs of carbon monoxide poisoning are similar to the flu with h...

Страница 4: ...Direct Vent type appliances draw all combustion air from outside of the dwelling through the vent pipe These appliances have been tested by CSA and found to comply with the established standards for V...

Страница 5: ...any damage is found Do not install any unit with damaged incomplete or substitute parts Check your packing list to verify that all listed parts have been received You should have the following Firepla...

Страница 6: ...Failure to do so will cause fire and damage to property 1 2 or 5 8 25 6M 654 mm Min Rough Opening Width 51 6M 1314 mm 40 1016 mm 3656 918 mm 17 6 454 mm 29 6QE 751 mm 37 6 956 mm 7556QE 195 mm 156O 38...

Страница 7: ...his manual for allowable venting configurations These units can be installed in a bedroom Refer to the National Fuel Gas Code ANSI Z233 1 NFPA 54 cur rent edition the Uniform Mechanical Code current e...

Страница 8: ...hazard The appliance cannot be installed on a carpet tile or other combustible material other than wood flooring If installed on carpet or vinyl flooring the appliance shall be installed on a metal wo...

Страница 9: ...brick tile slate steel or other materials with a UL fire rating of Zero may be used to cover the black painted face of the appliance It is permissible to bring combustible wall board to the top of the...

Страница 10: ...m 1 25 mm Figure 7 Combustible Clearances for Vent Pipe 12 305 mm Vertical Rise Required Before Horizontal Run FP2748 Venting INSTALLATION INFORMATION Read all instructions completely and thoroughly b...

Страница 11: ...Treatment of firestops and construction of the chase may vary from building type to building type These instructions are not substitutes for the requirements of local building codes You must follow a...

Страница 12: ...the meter regulator assembly 5 m above the meter regulator assy I Clearance to service regulator vent outlet 3 91 cm 3 91 cm J Clearance to nonmechanical air supply inlet 6 15 cm for appliances 10 000...

Страница 13: ...he pipe on the fireplace Vertical Dimension From the Floor of Unit to the Center of the Horizontal Vent Pipe Dimensions in Feet 50 1270 mm From Floor to Center Outside Corner Inside Corner Termination...

Страница 14: ...into position Measure the vertical height X required from the base of the flue collars to the center of the wall opening Figure 12 Step 4 Using appropriate length of pipe section s attach to fire plac...

Страница 15: ...installation is three 3 Figure 14 A minimum of 12 305 mm is required before a 90 elbow If a 90 elbow is fitted directly after 12 305 mm vertical section mounted to the top of the fireplace the maximu...

Страница 16: ...he exterior wall See the Sidewall Venting Graph for extended horizontal run if the vertical exceeds 12 1 Establish vent hole through the wall 2 Remove soil to a depth of approximately 16 below base of...

Страница 17: ...d Pipe Sheet Metal Screws Wall Screws Snorkel WARNING Do not back fill around snorkel A clearance of at least 4 must be maintained between the snorkel and the soil Up to two 45 elbows may be used with...

Страница 18: ...g to the position of the flue exit Mark the center point where the vent will penetrate the ceiling Drill a small locating hole a this point Drop a plumb line from the inside of the roof to the ceiling...

Страница 19: ...o combustible materials 6 Continue to add pipe sections until the height of the vent cap meets the minimum building code requirements NOTE You must increase vent height for steep roof pitches Nearby t...

Страница 20: ...Pull and extend the inner flexible vent 4 Slide the inner vent onto the adapter collar for a minimum 1C v overlap 5 Locate the clamp at approximately 3 4 from the flex end and tighten 6 Secure the cla...

Страница 21: ...are to be installed at inter vals prescribed by the flexible vent manufacturer and in such a way as to maintain concentric inner and outer vent spacing D Attaching flexible venting to vertical termin...

Страница 22: ...r sleet When using copper of flex connectors use only fittings approved for gas connections The gas control inlet is 3 8 NPT The gas control is equipped with a captured screw type pressure test point...

Страница 23: ...of the appliance Union tee and plugged 1 8 NPT pressure tapping point should be installed upstream of the appliance Figure 32 CAUTION Use pipe joint sealant that is resistant to liquid petroleum LP ga...

Страница 24: ...lectrical Wiring General 1 This fireplace is equipped with the Signature Control valve which operates on 6 volts The A C module plugs into the fireplace junction box A C power supply Four 4 AA batteri...

Страница 25: ...ot extend beyond the 15 ft wire cable provided If a longer distance is required the 15 ft may be extended up to 30 ft maximum by using two 2 SCSWEK cables plugged together Route the wire from junction...

Страница 26: ...Command Center Optional Wall Switch Plug in Connector Stepper Motor to Control Board DC Power Green Ground Plug in Connector Control Board to Solenoid Gas In Gas Out Pilot Gas Tubing Valve Light 300...

Страница 27: ...rectly WARNING Electrical connections should only be performed by a qualified licensed electrician Main power supply must be turned off before connecting the fan to the main electrical power supply or...

Страница 28: ...fastening the eight 8 screws securing the front and sides 2 Install the six 6 halogen light bulbs provided Do not touch light bulbs directly with fingers 3 Replace the front floor screen frame Be sure...

Страница 29: ...t Firebox Perimeter Burner Surface Rear Vent FP2434 Example of Stone Placement FP2702 rock and stone place FP2743 GLASS ONLY PLACEMENT NOTE Two 2 bags of glass are supplied with the 500 Series firepla...

Страница 30: ...phone Follow the gas supplier s instruc tions If you cannot reach your gas supplier call the fire department C Use only your finger to push in the master switch Never use tools If the switch will not...

Страница 31: ...gas go to next step 4 Press the master switch to the ON position Within eight 8 seconds it will beep once This indicates the system is ready 5 Press ON button Sparker will spark and pilot flame will l...

Страница 32: ...ut X LCD Backlight X Security Codes 16 X Countdown 6 hr Timer X Standard Thermostatic Control Mode X Smart Mode Thermostat Auto Flame Blower Modulation X Three Brightness Settings for Lights X Three S...

Страница 33: ...ds when the master switch Shutoff on the main burner is off RF Remote Receiver Push the RF receiver On Off button on the control board RF OFF On Off Beep once for ON and beep twice for OFF Learn Remot...

Страница 34: ...anual reset Self Diagnostics Chart The Command Center has a self diagnostic LED en abling you to troubleshoot problems and potentially avoid a service call Please refer to the charts below for indicat...

Страница 35: ...an extended period of time Never leave anything on top of the surface of the transmitter FP2646 TSFSC display Information Bar Touch Area Logo Bar Menus Adjustment Controls Function Areas of the LCD D...

Страница 36: ...he Command Cen ter will flash for 10 seconds WARNING Do not use two 2 or more remote control sys tems in the same area with the same privacy code setting as they will communicate with each other This...

Страница 37: ...it Timer Mode a Push and hold the TIMER button for 3 seconds Or b Use the OFF down buttons to decrease the Set Time to zero Or c Slide down on the arrow buttons to exit TIMER mode and shut off the fir...

Страница 38: ...ill remember this setting and the blower is still off see blower On Delay and Off Delay in the next section 4 After the signal is sent the ON up and OFF down but tons become flame height controller ag...

Страница 39: ...n the light button is flashing slide up and down on the arrow buttons will turn the light brightness to HIGH or Off directly without pressing the light button again to confirm AUX Control Optional The...

Страница 40: ...atteries 3 LCD display shows funny display 3 Reset the transmitter see Resetting the Transmitter section 4 Appliance does not come on 2 The transmitter did not match 1 Make sure the transmitter has wi...

Страница 41: ...ce a year Make sure the burner porting pilot air opening and burner air opening are free of obstructions at all times Pilot Flame The flames from the pilot should be visually checked as soon as the he...

Страница 42: ...cement glass door assemblies MUST be supplied by the fireplace manufacturer No substitute materi als may be used Handle glass door with care to avoid striking or scratch ing it on hard objects To clea...

Страница 43: ...h Battery polarity wrong LED on the Command Center does not show solid green The 5 pin connector on the AC board broken or bent AC plug is plugged to AC mains Battery voltage low Using battery Check v...

Страница 44: ...0 Watt 12 20301100 2 Bulb Socket 12 73D4521K 3 Glass Frame Assembly 2 78D0027K 4 Junction Box Assembly not shown 1 26D2128 5 Panel Access Door 2 78D0040K Accessories Field Installed Options 6 Porcelai...

Страница 45: ...78D2082 45 WDV See thru Gas Fireplace REPLACEMENT PARTS SIGNATURE COMMAND SYSTEM 780012 DVW SG parts 6 09 1 2 3 4 15 5 6 7 8a 9 14 8b...

Страница 46: ...w Shutoff Valve 1 69D0030 69D0030 7 Injector 2 59D0062 69D0226 8a Burner Assembly 1 78D2100 78D2100 8b Burner Assembly 1 78D2101 78D2101 9 Venturi 2 69D1026 69D1026 10 Air Shutter not shown 2 69D1027...

Страница 47: ...tones REPLACEMENT PARTS Item Description 500 Qty 600 Qty Part No 1 White Stone 1 5 5 78D0122 2 Light Gray Stone 2 5 5 78D0123 3 Dark Gray Stone 3 5 10 78D0124 4 Brown Stone 4 5 5 78D0125 5 Sand Stone...

Страница 48: ...48 78D2082 WDV See thru Gas Fireplace HOT 1 2 3 4 5 6 9 7 8 10 730024 KHLDV vent parts VENT components REPLACEMENT PARTS...

Страница 49: ...D6 3 4 9 Pipe Length 58DVA 09 1207 5DT 09 3 4 12 Pipe Length 58DVA 12 1206 5DT 12 5D12 3 4 24 Pipe Length 58DVA 24 1204 5DT 24 5D24 3 4 36 Pipe Length 58DVA 36 1203 5DT 36 5D36 3 4 48 Pipe Length 58DV...

Страница 50: ...ordance with the above provisions shall comply with NFPA 720 and ANSI UL 2034 listed and IAS certified Signage A metal or plastic identification plate shall be permanently mounted to the exterior of t...

Страница 51: ...Limited Lifetime Warranty will also be void if the appliance is not operated and maintained according to the operating instructions supplied with the appliance and does not extend to 1 firebox burner...

Страница 52: ...n CSA P 4 1 09 Efficiency Ratings Model EnerGuide Ratings Fireplace Efficiency WDVST500NTSC 61 0 WDVST500PTSC 59 7 Vermont Castings Group 149 Cleveland Drive Paris Kentucky 40361 www vermontcastingsgr...

Отзывы: