- 14 -
TROUBLE SHOOTING THE GAS CONTROL SYSTEM
SIT NOVA 820 MILLIVOLT VALVE
Note: Before trouble shooting the gas control system, be sure external gas shut off is in the "On" position.
WARNING: BEFORE DOING ANY GAS CONTROL SERVICE WORK, REMOVE GLASS FRONT.
SYMPTOM
POSSIBLE CAUSES
CORRECTIVE ACTION
1. Spark ignitor will not light
A. Defective or misaligned
Using a match, light pilot. If pilot lights, turn off pilot and
electrode at pilot.
push the red button again. If pilot will not light - check gap
at electrode and pilot-should be 1/8" to have a strong spark.
B. Defective ignitor (Push Button)
Push Piezo Ignitor Button. Check for spark at electrode and
pilot. If no spark to pilot, and electrode wire is properly
connected, replace ignitor.
2. Pilot will not stay lit after
A. Defective pilot generator
1. Check pilot flame. Must impinge on thermocouple/
carefully following lighting
(thermocouple), remote wall
thermopile. Note: this pilot burner assembly utilizes both
instructions.
switch.
a thermocouple and a thermopile. The thermocouple
operates the main valve operation (On and Off). Clean
and or adjust pilot for maximum flame impingement on
thermopile and thermocouple.
B. Defective automatic valve
Turn valve knob to "Pilot". Maintain flow to pilot; millivolt
operator.
meter should read greater than 10 mV. If the reading is
okay and the pilot does not stay on, replace the gas
valve. Note: An interrupter block (not supplied) must be
used to conduct this test.
3. Pilot burning, no gas to
A. Wall switch or wires
Check wall switch and wires for proper connections. Jumper
burner, Valve knob "ON",
defective.
wire across terminals at wall switch, if burner comes on,
Wall Switch "ON".
replace defective wall switch. If okay, jumper wires across
wall switch wires at valve, if burner comes on, wires are
faulty or connections are bad.
B. Thermopile may not be
1. Be sure wire connections from thermopile at gas valve
generating sufficient
terminals are tight and thermopile is fully inserted into pilot
millivoltage.
bracket.
2. One of the wall switch wires may be grounded. Remove
wall switch wires from valve terminals if pilot now stays lit,
trace wall switch wiring for ground. May be grounded to
fireplace or gas supply.
3. Check thermopile with millivolt meter. Take reading at
thermopile terminals of gas valve. Should read 250-300
millivolts (minimum 150) while holding valve knob de-
pressed in pilot position and wall switch "Off". Replace
faulty thermopile if reading is below specified minimum.
C. Plugged burner orifice.
Check burner orifices for debris and remove.
D. Defective automatic valve
Turn valve knob to "On", place wall switch to "On" millivolt
operator.
meter should read greater than 100 mV. If the reading is
okay and the burner does not come on, replace the gas
valve.
4. Frequent pilot flare outage
A. Pilot flame may be too low
Clean and/or adjust pilot flame for maximum flame
problem.
or blowing (high) causing the
impingement on thermopile and thermocouple.
pilot safety to drop out.
B. Vent safety shutdown.
Check the vent system for blockage. Check all connections
on vent safety switch.