Radiance

®

 Direct Vent Gas Heater 

CONVERSION PRECAUTIONS

Before proceeding, turn control knob on valve to OFF and 

turn gas supply OFF. Turn OFF any electricity that may be 

going to the appliance.

CONVERSION PROCEDURE

•  Remove stove front. Lift stove front up and then swing 

bottom out and away to disengage from the stove body. 

•  Undo the right and left latches at the top of the glass 

frame. 

•  Pull the top edge of the glass and frame assembly away 

from  the  firebox  face.  Place  the  assembly  out  of  the 

way on a flat, padded surface such as a counter pro

-

tected by a towel.

• 

Remove the logset from the firebox.

VALVE CONVERSION

RADVT Series Models (Millivolt)

•  Turn control knob to the OFF position, and shut off the 

gas supply to the valve.

•  Allow the valve to cool to room temperature.
•  Remove the black protection cap by hand. (Figure 73)

•  Insert a 5/32" or 4 mm Allen wrench into the hexagonal 

key-way of the screw (Figure 74), rotate it counterclock-

wise until it is free and extract it.

•  Check that the screw is clean and if necessary remove 

dirt. Flip the screw. (Figure 75)

•  Using the Allen wrench as shown in Figure 76, rotate 

the screw clockwise and tighten until snug.

NOTE: Do not over-tighten the screw. Recom-

mended to grip the wrench by the short side.

H

I

LO

CO138
remove screw
6/07

Fig. 73

HI

LO

CO139
Allen wrench
6/07

HI

LO

CO140
turn screw
6/07

Fig. 75

HI

LO

CO139
Allen wrench
6/07

Fig. 76

FUEL CONVERSION

WARNING

This  conversion  kit  shall  be  installed  by  a  qualified 

service agency in accordance with the manufacturer’s 

instructions and all applicable codes and requirements 

of the authority having jurisdiction. If the information in 

these instructions is not followed exactly, a fire, explosion 

or production of carbon monoxide may result causing 

property damage, personal injury or loss of life. The 

qualified service agency is responsible for the proper 

installation of this kit. The installation is not proper and 

complete until the operation of the converted appliance 

is checked as specified in the manufacturer’s instruc

-

tions supplied with the kit.

CAUTION

The gas supply shall be shut off prior to disconnecting 

the electrical power, before proceeding with the conver-

sion (Figure 72).

Fig. 74

ST226
attach gas line
12/8/99   djt

PILOT

ON

OFF

PILOT ADJ

LO

HI

Gas Supply Inlet

ST226a

Fig. 72  Attach the gas line to the right side of the valve.

Main 

Gas 

Line

Shut 

off 

Valve

Содержание Radiance RADVTBDSB

Страница 1: ...G Improper installation adjustment alteration service or maintenance can cause injury or property damage Refer to this manual For assistance or additional information consult a qualified installer ser...

Страница 2: ...ctions 18 Disassemble Vent Sections 19 Horizontal Termination Cap 19 Divert Roof Run off 20 Vertical Side Wall Installation 20 Vent Termination Below Grade 21 Vertical Through The Roof Application Ins...

Страница 3: ...om the room for com bustion and vent the exhaust vertically through the roof to the atmosphere This appliance is approved for bedroom installations in the U S and Canada This appliance may be installe...

Страница 4: ...vented gas fueled equip ment all venting instructions all parts lists for venting instructions and or all venting design instructions shall remain with the appliance or equipment at the completion of...

Страница 5: ...58 mm 31 787 mm 7 Outer Dia 178 mm Flue Collar L C 4 3 4 120 mm 14 7 8 378 mm R A D I A N C E 28 711 mm 5 127 mm 18 1 4 464 mm Supply Inlet Fig 1 Radiance dimensions RADIANCE DIRECT VENT PRE INSTALLAT...

Страница 6: ...Where family members gather most often The vent system requirements NOTE We do not recommend the use of wallpaper next to this stove Over time radiant heat may cause the wallpaper to shrink or may adv...

Страница 7: ...1448 mm HHT Pipe 55 1399 mm DuraVent Pipe ST131b Fig 5 Minimum wall centerline Direct Vent Only HEARTH REQUIREMENTS The Radiance Heater must be installed on rigid flooring When the heater is installe...

Страница 8: ...0 6m and include a vertical rise of up to 40 12 m Figure 7 Horizontal termination must also meet the criteria shown in Figures 10 through 12 Approved vent systems must terminate above and in cluding t...

Страница 9: ...ag Adjustments can be made by loosening the adjustment screw to allow the restrictor plate to slide up or down Figure 9 A guide for usage is shown in Figure 10 NOTE Some installations may require some...

Страница 10: ...wn in Figure 11 Important All vent clearances must be maintained Check your vent termination clearances against Fig ures 11 and 12 The vent should be placed so that people cannot be burned by accident...

Страница 11: ...liances 10 000 BTU h 3kW and 50 000 BTU h 15kW 12 30cm for appliances 50 000 BTU h 15kW C Clearance to permanently closed window 12 305mm recommended to prevent window condensation 12 305mm recommende...

Страница 12: ...Min 12 305 mm for vinyl sidewalls O 8 2 4 m Min O P V V V 584 15 No of Caps DMin CMax 1 3 914 mm 2 x DActual 2 6 1 8 m 1 x DActual 3 9 2 7 m 2 3 x DActual 4 12 3 7 m 1 2 x DActual DMin of Termination...

Страница 13: ...A F6 Flashing 6 12 12 12 46DVA F12 Steel Chimney Conv Kit A 65 8 85 8 46DVA KCA Steel Chimney Conv Kit B 65 8 101 2 46DVA KCB Steel Chimney Conv Kit C 65 8 13 46DVA KCC Masonry Chimney Conversion Kit...

Страница 14: ...h the rear legs using 3 8 hex head bolts and flat washer supplied Tighten with a 9 16 wrench or socket Remove and discard the large slot head screws using the flat blade screwdriver 3 Carefully tip th...

Страница 15: ...et Snapstat Extension Assembly Rheostat Assembly ST473a Blower Assembly Fig 15 Fan kit components 2 Remove the rear shroud panel Fig 16 and fasten the blower assembly to the firebox back with the two...

Страница 16: ...ese models are approved to use HHT direct vent pipe components and HHT termination kits and Du raVent components No other venting system compo nents may be used Horizontal runs must be supported every...

Страница 17: ...12 4 99 djt Align Seams Rotate ST211 Fig 20 Connect the inner starter with the next section of inner vent pipe alignment with the wall thimble opening 6 Attach the Inner Vent Assembly to the stove 7...

Страница 18: ...ues of the slip section can be cut to the desired length Fig 24 Screws into Slip Section Fig 23 Slip Section Pilot Holes SECURE THE VENT SECTIONS Vertical sections of SLP pipe must be supported every...

Страница 19: ...ng the termination to the pipe When this connection has been made slide the wall thimble up to the interior wall surface and attach with screws provided Secure termination cap to exterior wall using p...

Страница 20: ...wn Figure30 Noncombustible Walls Hole opening must be 7 178 mm in diameter 4 Using appropriate length of pipe section s attach to stove by twisting collar 5 Measure the horizontal length requirement i...

Страница 21: ...ing system is installed below grade a window well must be installed with adequate and proper drainage Figure 35 NOTE Be sure to maintain side wall clearances and vent run restrictions Refer to Page 7...

Страница 22: ...plane the maximum horizontal length must be reduced by 18 450 mm Example Maximum horizontal length No elbows 10 3 m 1 x 45 elbow 8 5 2 6 m 2 x 45 elbows 7 2 1 m A minimum of an 8 2 5 m vertical rise...

Страница 23: ...Storm Collar Roof Flashing Horizontal overhang 12 X 20 in 508 mm Lowest Discharge Opening Termination Cap Roof Pitch is X 12 Vertical wall H min Minimum height from roof to lowest discharge opening 2...

Страница 24: ...lass frame by following the steps below S T141 pull glass latch 10 99 ST141 Fig 41 Release the latches to remove the glass frame DANGER HOT GLASS WILL CAUSE BURNS DO NOT TOUCH GLASS UNTIL COOLED NEVER...

Страница 25: ...Spot for Front Left Log Rib and Flat Spot for Front Right Log LG487 Fig 43 Ribs for Logs 3 Install the front left and right logs Figure 44 by plac ing them on the ribs shown in Figure 43 Make sure th...

Страница 26: ...SIT VALVE Valve Thermopile ON OFF Switch or Millivolt Thermostat FP1909a signature command valve alternate view 8 08 Pressure Inlet Pressure Outlet Pilot Adjust ment Screw FP1909a Fig 48 Signature Com...

Страница 27: ...cable into the command center Snap on wall cover provided and screw to junction box WALL SWITCH INSTALLATION The wall switch wire connection is located off the 2 ft wire harness from the control box t...

Страница 28: ...are provided with each kit and in this manual THIS APPLIANCE SHOULD BE CONNECTED TO THE GAS SUPPLY ONLY BYA QUALIFIED GAS SERVICE TECHNICIAN FOLLOW ALL LOCAL CODES THERE MUST BE A GAS SHUT OFF BETWEE...

Страница 29: ...or Sparker Conversion NG LP Plug in Connector Control Board to Command Center OFF LO LED ON HI Master Switch Command Center Optional Wall Switch Plug in Connector Stepper Motor to Control Board NOTE W...

Страница 30: ...er becomes damaged the bar rier shall be replaced with the manufacturer s barrier for this appliance Any safety screen guard or barrier removed for servicing the appliance must be replaced prior to op...

Страница 31: ...ct turn the heater off Contact your dealer or a qualified gas technician for assistance Do not operate the heater until the pilot flame is correct Follow regular maintenance procedures as described in...

Страница 32: ...avier than air and will settle on the floor WHAT TO DO IF YOU SMELL GAS Do not try to light any stove Do not touch any electric switch Do not use any phone in your building Immediatelycallyourgassuppl...

Страница 33: ...not supplied must be used to conduct this test Pilot burning no gas to main burner 1 Wall switch or wires defective 1 Check wall switch and wires for proper connections Jumper wire across termi nals...

Страница 34: ...er s instructions If you cannot reach your gas supplier call the fire department C Use only your finger to push in the master switch Never use tools If the switch will not function by hand do not try...

Страница 35: ...hin eight 8 seconds it will beep once This indicates the system is ready 5 Press ON button Sparker will spark and pilot flame will light 6 Once pilot flame is established the main burner flame will li...

Страница 36: ...Child Proof Lock out LCD Backlight Security Codes 16 Countdown 6 hr Timer Standard Thermostatic Control Mode Smart Mode Thermostat Auto Flame Blower Modula tion Three Brightness Settings for Lights T...

Страница 37: ...ittent pilot After the above operation one beep for standing pilot or two beeps for intermittent pilot will be given as con firmation Six hour Safety Shutdown Option Default ON The system comes preset...

Страница 38: ...press the OFF t button 3 times OR for Memory Off hold the OFF t button 3 seconds or turn off wall switch Flame Height Up Press the ON s button once to turn on the stove with maximum flame height Flame...

Страница 39: ...gnature Com mand System FP2646 TSFSC display Information Bar Touch Area Logo Bar Menus Adjustment Controls Fig 59 Functional areas of LCD Display FP2607 install battery Battery Door Tabs Fig 60 Replac...

Страница 40: ...e OFF button on the transmitter to learn Another two beeps will be given to confirm a successful learning Figure 63 Resetting the Transmitter If the transmitter is not working properly reinstall the b...

Страница 41: ...TIMER mode and shut off the stove Thermostat Mode Figure 65 NOTE The Command Center buttons will disable when thermostat is being used Press the THERMO button to set the transmitter in thermostat mod...

Страница 42: ...n button to increase decrease the blower speed Press the fan button again to confirm the speed setting If the stove is on the blower speed will take effect right away if the stove is off the receiver...

Страница 43: ...er will not operate with low bat tery voltage Change the batteries before the batteries become too weak for normal operations Power On Initialization After the power on initialization the transmitter...

Страница 44: ...AC mains Repair or replace the AC Board Replace the AC Board Replace the Control Board or Command Center Sparking is happening elsewhere under the pilot re install replace the pilot Re install the Co...

Страница 45: ...e pilot flame must always be present when the stove is in operation Figure 71 The pilot flame has three distinct flames one engulfing the sensor one engulfing the thermopile and the other reaching to...

Страница 46: ...shown in Figure 76 rotate the screw clockwise and tighten until snug NOTE Do not over tighten the screw Recom mended to grip the wrench by the short side H I LO CO138 remove screw 6 07 Fig 73 H I LO...

Страница 47: ...for the gas type ST350 Jefferson air shutter adj 3 20 00 djt Pilot ST916 Fig 78 Locate pilot Pilot Orifice Conversion Locate pilot Figure 78 Replace pilot orifice Remove pilot hood by lifting up Figur...

Страница 48: ...142 air shutter meas 6 07 Orifice Bracket Orifice Air Shutter CO142 Fig 84 The air shutter setting is 1 2 13 mm from the orifice bracket to the edge of the air shutter FUEL CONVERSION Fig 86 Burner Or...

Страница 49: ...nt Restore gas to system and relight appliance according to Lighting Instructions on Page 32 RADVT models or Page 35 RADVTSC models Leak check the system using a gas leak detector solution Relight the...

Страница 50: ...U h Model Kit Orifice Part Minimum Maximum RADVT 20012729 51 20008557 25 000 36 000 RADVTSC 20308379 Conversion to Natural Gas Input BTU h Model Kit Orifice Part Minimum Maximum RADVT 20012899 33 0 11...

Страница 51: ...sh and be sure to cover the logs burner and valve assembly glass and frame assembly Apply the paint sparingly two light coats of paint will give better results than a single heavy coat Clean porcelain...

Страница 52: ...d side of the glass panel back into the steel frame Pinch the rounded inside facing gasket material to bulk it up 5 Replace the glass frame and front panel as previously described INSPECT THE VENT SYS...

Страница 53: ...t Gas Valve St124b on off switch wiring 1 11 00 djt TP TH TP TH Thermostat Optional Thermopile Black Black Millivolt Gas Valve St124c Thermostat wiring 1 11 00 djt TP TH TP TH FAN JUNCTION BOX FAN POW...

Страница 54: ...itor Sparker Conversion NG LP Plug in Connector Control Board to Command Center OFF LO LED ON HI Master Switch Command Center Optional Wall Switch Plug in Connector Stepper Motor to Control Board NOTE...

Страница 55: ...3 32 34a b 9 22 23 13 21 11 12 52 20 45 3 5 4 26 53 36 19 17 18 25 39 1 1c 1b 1e 1d 2 47 48 49 41 56 55 60 24 50 50a 54 HHT reserves the right to make changes in design materials specifications prices...

Страница 56: ...1203702 16 Glass GFP Firebox 1601290 17 Wood Handle 1600664 18 Pan Hd Sl 1 4 20 x 3 Z 1201310 19 Brushed Nickel Insert 30002714 20 Control Door Handle Assembly 30002730 21 Washer Flat 1 4 Blk 266 x 62...

Страница 57: ...mand Center 80D0005 57 Wire Valve Control not shown 80D0010 58 Wire AC Module not shown 80D0009 59 Wire Command Center not shown 80D0008 60 AC Module SCSACM Ref Description RADVT RADVTSC RADIANCE DIRE...

Страница 58: ...RADVT The remote control allows you to turn the heater on or off from anywhere in the room Refer to Page 53 for wiring diagrams These remote controls are for use with standard millivolt models ON OFF...

Страница 59: ...r charges relating to the cost and expenses of replacing or repairing defective components under the Limited Lifetime Warranty are not covered except as provided for under the Basic One Year Warranty...

Страница 60: ...EFFICIENCY RATINGS MODEL ENERGUIDE RATINGS STOVE EFFICIENCY PERCENTAGE D O E AFUE PERCENTAGE RADVT Series 66 0 68 4 RADVTSC Series 66 0 68 4 www vermontcastings com...

Отзывы: