Vermont Castings Radiance RADVTBDSB Скачать руководство пользователя страница 4

4

4

20306759

Radiance

®

 Direct Vent Gas Heater 

Proposition 65 Warning:

 Fuels used in gas, wood-burning 

or  oil  fired  appliances,  and  the  products  of  combustion  of 

such fuels, contain chemicals known to the State of California 

to cause cancer, birth defects and other reproductive harm.

California Health & Safety Code Sec. 25249.6

 

Radiance Direct Vent

Certified to:

ANSI Z21.88-2014 / CSA 2.33-2014

Vented Gas Heaters 

Inspection

The state or local gas inspector of the side wall horizontally 

vented gas fueled equipment shall not approve the installa-

tion unless, upon inspection, the inspector observes carbon 

monoxide detectors and signage installed in accordance 

with the provisions of 248 CMR 5.08(2)(a)1 through 4.

Exemptions

The following equipment is exempt from 248 CMR 5.08(2)

(a)1 through 4:
•  The equipment listed in Chapter 10 entitled “Equipment 

Not Required To Be Vented" in the most current edition 

of NFPA 54 as adopted by the Board; and

• 

Product Approved side wall horizontally vented gas fu

-

eled equipment installed in a room or structure separate 

from the dwelling, building or structure used in whole or 

in part for residential purposes.

MANUFACTURER REQUIREMENTS

Gas Equipment Venting System Provided

When the manufacturer of Product Approved side wall hor-

izontally vented gas equipment provides a venting system 

design or venting system components with the equipment, 

the instructions provided by the manufacturer for installation 

of the equipment and the venting system shall include:
•  Detailed instructions for the installation of the venting 

system design or the venting system components; and

•  A complete parts list for the venting system design or 

venting system.

Gas Equipment Venting System NOT Provided

When the manufacturer of a Product Approved side wall 

horizontally vented gas fueled equipment does not provide 

the parts for venting the flue gases, but identifies “special 

venting systems", the following requirements shall be sat-

isfied by the manufacturer:

•  The referenced “special venting system" instructions 

shall be included with the appliance or equipment in-

stallation instructions; and

•  The “special venting systems" shall be Product Ap-

proved by the Board, and the instructions for that sys-

tem shall include a parts list and detailed installation 

instructions.

A copy of all installation instructions for all Product 

Approved side wall horizontally vented gas fueled equip

-

ment, all venting instructions, all parts lists for venting 

instructions, and/or all venting design instructions shall 

remain with the appliance or equipment at the completion 

of the installation.

IMPORTANT SAFETY INFORMATION
REQUIREMENTS FOR THE 

COMMONWEALTH OF MASSACHUSETTS

All gas fitting and installation of this heater shall only be 

done by a licensed gas fitter or licensed plumber.
For all side wall horizontally vented gas fueled equipment 

installed in every dwelling, building or structure used in 

whole or in part for residential purposes, including those 

owned or operated by the Commonwealth and where 

the side wall exhaust vent termination is less than seven 

(7) feet above finished grade in the area of the venting, 

including but not limited to decks and porches, the following 

requirements shall be satisfied:

Installation of Carbon Monoxide Detectors

At the time of installation of the side wall horizontal vented 

gas fueled equipment, the installing plumber or gas fitter 

shall observe that a hard wired carbon monoxide detec-

tor with an alarm  is installed on each additional level of 

the dwelling, building or structure served by the side wall 

horizontal  vented  gas  fueled  equipment.  It  shall  be  the 

responsibility of the property owner to secure the services 

of  qualified  licensed  professionals  for  the  installation  of 

hard wired carbon monoxide detectors.

In the event that the side wall horizontally vented gas fueled 

equipment is installed in a crawl space or an attic, the hard 

wired carbon monoxide detector with alarm and battery 

back-up may be installed on the next adjacent floor level.

In the event that the requirements of this subdivision can 

not be met at the time of completion of installation, the 

owner shall have a period of thirty (30) days to comply with 

the above requirements; provided, however, that during 

said thirty (30) day period, a battery operated carbon mon-

oxide detector with an alarm shall be installed.

Approved Carbon Monoxide Detectors

Each carbon monoxide detector as required in accordance 

with the above provisions shall comply with NFPA 720 and 

ANSI/UL 2034 listed and IAS certified.

Signage

A  metal  or  plastic  identification  plate  shall  be  per

-

manently mounted to the exterior of the building at a 

minimum height of eight (8) feet above grade directly in 

line with the exhaust vent terminal for the horizontally 

vented gas fueled heating appliance or equipment. The 

sign shall read, in print size no less than one-half (1/2) 

inch  in  size,  “GAS  VENT  DIRECTLY  BELOW,  KEEP 

CLEAR OF ALL OBSTRUCTIONS".

Содержание Radiance RADVTBDSB

Страница 1: ...G Improper installation adjustment alteration service or maintenance can cause injury or property damage Refer to this manual For assistance or additional information consult a qualified installer ser...

Страница 2: ...ctions 18 Disassemble Vent Sections 19 Horizontal Termination Cap 19 Divert Roof Run off 20 Vertical Side Wall Installation 20 Vent Termination Below Grade 21 Vertical Through The Roof Application Ins...

Страница 3: ...om the room for com bustion and vent the exhaust vertically through the roof to the atmosphere This appliance is approved for bedroom installations in the U S and Canada This appliance may be installe...

Страница 4: ...vented gas fueled equip ment all venting instructions all parts lists for venting instructions and or all venting design instructions shall remain with the appliance or equipment at the completion of...

Страница 5: ...58 mm 31 787 mm 7 Outer Dia 178 mm Flue Collar L C 4 3 4 120 mm 14 7 8 378 mm R A D I A N C E 28 711 mm 5 127 mm 18 1 4 464 mm Supply Inlet Fig 1 Radiance dimensions RADIANCE DIRECT VENT PRE INSTALLAT...

Страница 6: ...Where family members gather most often The vent system requirements NOTE We do not recommend the use of wallpaper next to this stove Over time radiant heat may cause the wallpaper to shrink or may adv...

Страница 7: ...1448 mm HHT Pipe 55 1399 mm DuraVent Pipe ST131b Fig 5 Minimum wall centerline Direct Vent Only HEARTH REQUIREMENTS The Radiance Heater must be installed on rigid flooring When the heater is installe...

Страница 8: ...0 6m and include a vertical rise of up to 40 12 m Figure 7 Horizontal termination must also meet the criteria shown in Figures 10 through 12 Approved vent systems must terminate above and in cluding t...

Страница 9: ...ag Adjustments can be made by loosening the adjustment screw to allow the restrictor plate to slide up or down Figure 9 A guide for usage is shown in Figure 10 NOTE Some installations may require some...

Страница 10: ...wn in Figure 11 Important All vent clearances must be maintained Check your vent termination clearances against Fig ures 11 and 12 The vent should be placed so that people cannot be burned by accident...

Страница 11: ...liances 10 000 BTU h 3kW and 50 000 BTU h 15kW 12 30cm for appliances 50 000 BTU h 15kW C Clearance to permanently closed window 12 305mm recommended to prevent window condensation 12 305mm recommende...

Страница 12: ...Min 12 305 mm for vinyl sidewalls O 8 2 4 m Min O P V V V 584 15 No of Caps DMin CMax 1 3 914 mm 2 x DActual 2 6 1 8 m 1 x DActual 3 9 2 7 m 2 3 x DActual 4 12 3 7 m 1 2 x DActual DMin of Termination...

Страница 13: ...A F6 Flashing 6 12 12 12 46DVA F12 Steel Chimney Conv Kit A 65 8 85 8 46DVA KCA Steel Chimney Conv Kit B 65 8 101 2 46DVA KCB Steel Chimney Conv Kit C 65 8 13 46DVA KCC Masonry Chimney Conversion Kit...

Страница 14: ...h the rear legs using 3 8 hex head bolts and flat washer supplied Tighten with a 9 16 wrench or socket Remove and discard the large slot head screws using the flat blade screwdriver 3 Carefully tip th...

Страница 15: ...et Snapstat Extension Assembly Rheostat Assembly ST473a Blower Assembly Fig 15 Fan kit components 2 Remove the rear shroud panel Fig 16 and fasten the blower assembly to the firebox back with the two...

Страница 16: ...ese models are approved to use HHT direct vent pipe components and HHT termination kits and Du raVent components No other venting system compo nents may be used Horizontal runs must be supported every...

Страница 17: ...12 4 99 djt Align Seams Rotate ST211 Fig 20 Connect the inner starter with the next section of inner vent pipe alignment with the wall thimble opening 6 Attach the Inner Vent Assembly to the stove 7...

Страница 18: ...ues of the slip section can be cut to the desired length Fig 24 Screws into Slip Section Fig 23 Slip Section Pilot Holes SECURE THE VENT SECTIONS Vertical sections of SLP pipe must be supported every...

Страница 19: ...ng the termination to the pipe When this connection has been made slide the wall thimble up to the interior wall surface and attach with screws provided Secure termination cap to exterior wall using p...

Страница 20: ...wn Figure30 Noncombustible Walls Hole opening must be 7 178 mm in diameter 4 Using appropriate length of pipe section s attach to stove by twisting collar 5 Measure the horizontal length requirement i...

Страница 21: ...ing system is installed below grade a window well must be installed with adequate and proper drainage Figure 35 NOTE Be sure to maintain side wall clearances and vent run restrictions Refer to Page 7...

Страница 22: ...plane the maximum horizontal length must be reduced by 18 450 mm Example Maximum horizontal length No elbows 10 3 m 1 x 45 elbow 8 5 2 6 m 2 x 45 elbows 7 2 1 m A minimum of an 8 2 5 m vertical rise...

Страница 23: ...Storm Collar Roof Flashing Horizontal overhang 12 X 20 in 508 mm Lowest Discharge Opening Termination Cap Roof Pitch is X 12 Vertical wall H min Minimum height from roof to lowest discharge opening 2...

Страница 24: ...lass frame by following the steps below S T141 pull glass latch 10 99 ST141 Fig 41 Release the latches to remove the glass frame DANGER HOT GLASS WILL CAUSE BURNS DO NOT TOUCH GLASS UNTIL COOLED NEVER...

Страница 25: ...Spot for Front Left Log Rib and Flat Spot for Front Right Log LG487 Fig 43 Ribs for Logs 3 Install the front left and right logs Figure 44 by plac ing them on the ribs shown in Figure 43 Make sure th...

Страница 26: ...SIT VALVE Valve Thermopile ON OFF Switch or Millivolt Thermostat FP1909a signature command valve alternate view 8 08 Pressure Inlet Pressure Outlet Pilot Adjust ment Screw FP1909a Fig 48 Signature Com...

Страница 27: ...cable into the command center Snap on wall cover provided and screw to junction box WALL SWITCH INSTALLATION The wall switch wire connection is located off the 2 ft wire harness from the control box t...

Страница 28: ...are provided with each kit and in this manual THIS APPLIANCE SHOULD BE CONNECTED TO THE GAS SUPPLY ONLY BYA QUALIFIED GAS SERVICE TECHNICIAN FOLLOW ALL LOCAL CODES THERE MUST BE A GAS SHUT OFF BETWEE...

Страница 29: ...or Sparker Conversion NG LP Plug in Connector Control Board to Command Center OFF LO LED ON HI Master Switch Command Center Optional Wall Switch Plug in Connector Stepper Motor to Control Board NOTE W...

Страница 30: ...er becomes damaged the bar rier shall be replaced with the manufacturer s barrier for this appliance Any safety screen guard or barrier removed for servicing the appliance must be replaced prior to op...

Страница 31: ...ct turn the heater off Contact your dealer or a qualified gas technician for assistance Do not operate the heater until the pilot flame is correct Follow regular maintenance procedures as described in...

Страница 32: ...avier than air and will settle on the floor WHAT TO DO IF YOU SMELL GAS Do not try to light any stove Do not touch any electric switch Do not use any phone in your building Immediatelycallyourgassuppl...

Страница 33: ...not supplied must be used to conduct this test Pilot burning no gas to main burner 1 Wall switch or wires defective 1 Check wall switch and wires for proper connections Jumper wire across termi nals...

Страница 34: ...er s instructions If you cannot reach your gas supplier call the fire department C Use only your finger to push in the master switch Never use tools If the switch will not function by hand do not try...

Страница 35: ...hin eight 8 seconds it will beep once This indicates the system is ready 5 Press ON button Sparker will spark and pilot flame will light 6 Once pilot flame is established the main burner flame will li...

Страница 36: ...Child Proof Lock out LCD Backlight Security Codes 16 Countdown 6 hr Timer Standard Thermostatic Control Mode Smart Mode Thermostat Auto Flame Blower Modula tion Three Brightness Settings for Lights T...

Страница 37: ...ittent pilot After the above operation one beep for standing pilot or two beeps for intermittent pilot will be given as con firmation Six hour Safety Shutdown Option Default ON The system comes preset...

Страница 38: ...press the OFF t button 3 times OR for Memory Off hold the OFF t button 3 seconds or turn off wall switch Flame Height Up Press the ON s button once to turn on the stove with maximum flame height Flame...

Страница 39: ...gnature Com mand System FP2646 TSFSC display Information Bar Touch Area Logo Bar Menus Adjustment Controls Fig 59 Functional areas of LCD Display FP2607 install battery Battery Door Tabs Fig 60 Replac...

Страница 40: ...e OFF button on the transmitter to learn Another two beeps will be given to confirm a successful learning Figure 63 Resetting the Transmitter If the transmitter is not working properly reinstall the b...

Страница 41: ...TIMER mode and shut off the stove Thermostat Mode Figure 65 NOTE The Command Center buttons will disable when thermostat is being used Press the THERMO button to set the transmitter in thermostat mod...

Страница 42: ...n button to increase decrease the blower speed Press the fan button again to confirm the speed setting If the stove is on the blower speed will take effect right away if the stove is off the receiver...

Страница 43: ...er will not operate with low bat tery voltage Change the batteries before the batteries become too weak for normal operations Power On Initialization After the power on initialization the transmitter...

Страница 44: ...AC mains Repair or replace the AC Board Replace the AC Board Replace the Control Board or Command Center Sparking is happening elsewhere under the pilot re install replace the pilot Re install the Co...

Страница 45: ...e pilot flame must always be present when the stove is in operation Figure 71 The pilot flame has three distinct flames one engulfing the sensor one engulfing the thermopile and the other reaching to...

Страница 46: ...shown in Figure 76 rotate the screw clockwise and tighten until snug NOTE Do not over tighten the screw Recom mended to grip the wrench by the short side H I LO CO138 remove screw 6 07 Fig 73 H I LO...

Страница 47: ...for the gas type ST350 Jefferson air shutter adj 3 20 00 djt Pilot ST916 Fig 78 Locate pilot Pilot Orifice Conversion Locate pilot Figure 78 Replace pilot orifice Remove pilot hood by lifting up Figur...

Страница 48: ...142 air shutter meas 6 07 Orifice Bracket Orifice Air Shutter CO142 Fig 84 The air shutter setting is 1 2 13 mm from the orifice bracket to the edge of the air shutter FUEL CONVERSION Fig 86 Burner Or...

Страница 49: ...nt Restore gas to system and relight appliance according to Lighting Instructions on Page 32 RADVT models or Page 35 RADVTSC models Leak check the system using a gas leak detector solution Relight the...

Страница 50: ...U h Model Kit Orifice Part Minimum Maximum RADVT 20012729 51 20008557 25 000 36 000 RADVTSC 20308379 Conversion to Natural Gas Input BTU h Model Kit Orifice Part Minimum Maximum RADVT 20012899 33 0 11...

Страница 51: ...sh and be sure to cover the logs burner and valve assembly glass and frame assembly Apply the paint sparingly two light coats of paint will give better results than a single heavy coat Clean porcelain...

Страница 52: ...d side of the glass panel back into the steel frame Pinch the rounded inside facing gasket material to bulk it up 5 Replace the glass frame and front panel as previously described INSPECT THE VENT SYS...

Страница 53: ...t Gas Valve St124b on off switch wiring 1 11 00 djt TP TH TP TH Thermostat Optional Thermopile Black Black Millivolt Gas Valve St124c Thermostat wiring 1 11 00 djt TP TH TP TH FAN JUNCTION BOX FAN POW...

Страница 54: ...itor Sparker Conversion NG LP Plug in Connector Control Board to Command Center OFF LO LED ON HI Master Switch Command Center Optional Wall Switch Plug in Connector Stepper Motor to Control Board NOTE...

Страница 55: ...3 32 34a b 9 22 23 13 21 11 12 52 20 45 3 5 4 26 53 36 19 17 18 25 39 1 1c 1b 1e 1d 2 47 48 49 41 56 55 60 24 50 50a 54 HHT reserves the right to make changes in design materials specifications prices...

Страница 56: ...1203702 16 Glass GFP Firebox 1601290 17 Wood Handle 1600664 18 Pan Hd Sl 1 4 20 x 3 Z 1201310 19 Brushed Nickel Insert 30002714 20 Control Door Handle Assembly 30002730 21 Washer Flat 1 4 Blk 266 x 62...

Страница 57: ...mand Center 80D0005 57 Wire Valve Control not shown 80D0010 58 Wire AC Module not shown 80D0009 59 Wire Command Center not shown 80D0008 60 AC Module SCSACM Ref Description RADVT RADVTSC RADIANCE DIRE...

Страница 58: ...RADVT The remote control allows you to turn the heater on or off from anywhere in the room Refer to Page 53 for wiring diagrams These remote controls are for use with standard millivolt models ON OFF...

Страница 59: ...r charges relating to the cost and expenses of replacing or repairing defective components under the Limited Lifetime Warranty are not covered except as provided for under the Basic One Year Warranty...

Страница 60: ...EFFICIENCY RATINGS MODEL ENERGUIDE RATINGS STOVE EFFICIENCY PERCENTAGE D O E AFUE PERCENTAGE RADVT Series 66 0 68 4 RADVTSC Series 66 0 68 4 www vermontcastings com...

Отзывы: