background image

22

20306748

MLDV Series Gas Fireplace

VENTING INSTALLATION 

Figure 34 - 
If Area Above is a Room, Install Firestop 
above Framed Hole as Shown 

Firestop 

Nails

FP1969

10

1

/

2

"

10

1

/

2

"

Figure 33 - 
If Area Above is Not a Room, Install Firestop 
above Framed Hole as Shown 

Nails

Firestop 

FP1970

Otherwise, install 

fi

 restop below the framed hole. The 

fi

 restop should be installed with no less than three (3) 

nails per side. 

Figure 34. 

2.  Assemble the desired lengths of pipe and elbows nec-

essary to reach from the burner system 

fl

 ue up through 

the 

fi

 restop. Be sure pipe and elbow connections are 

fully twist-locked. 

Page 18, Figure 15.

3.  Cut a hole in the roof using the locating hole as a center 

point. (Cover any exposed open vent pipes before 
cutting hole in roof). The 10

1

2

" x 10

1

2

" (267 x 267 mm) 

hole must be measured on the horizontal. Actual length 
may be larger depending on the pitch of the roof. There 
must be a 1" minimum clearance from the vent pipe to 
combustible materials. (Insulation should be considered 
a combustible material). Frame the opening as shown 
on 

Page 18, Figure 16.

4.  Connect a section of pipe and extend up through the 

hole.

NOTE:

 If an offset is needed to avoid obstructions, you 

must support the vent pipe every three (3) feet. Use wall 
straps for this purpose. 

Figure 32

. Whenever possible, use 

45° elbows instead  of 90° elbows. The 45° elbow offers 
less restriction to the 

fl

 ow of the 

fl

 ue gases and intake air.

5. Place 

the 

fl

 ashing over the pipe section(s) extending 

through the roof. Secure the base of the 

fl

 ashing  to 

the roof and framing with roo

fi

 ng nails. Be sure roo

fi

 ng 

material overlaps the top edge of the 

fl

 ashing. There 

must be a 1" clearance from the vent pipe to combus-
tible materials.  

6.  Continue to add pipe sections until the height of the 

vent cap meets the minimum requirements below.

NOTE:

 You must increase vent height for steep roof 

pitches. Nearby trees, adjoining roof lines, steep pitched 
roofs, and other similar factors may cause poor draft or 
down-drafting in high winds. Increasing the vent height 
may solve this problem.

NOTE:

 If the vent pipe passes through any occupied areas 

above the 

fi

 rst 

fl

 oor, including storage spaces and closets, 

you must enclose pipe. You may frame and sheetrock the 
enclosure with standard construction material. Make sure 
to meet the minimum allowable clearances to combustibles. 
Do not 

fi

 ll any of the required clearance spaces with 

insulation.  

2 ft. 
Min.

2 ft. Min.

X

12

H*

FP1971

Figure 35 - 
Minimum Chimney Clearance

Horizontal Overhang

Vertical Wall

Termination 
Vent

Storm Collar

Flashing

Concentric 
Vent Pipe

1" Minimum Clearance to 
Combustibles

Lowest 
Discharge 
Opening

 

Roof Pitch 

H (feet)

 

Flat to 6/12 

1.0

  Over 6/12 to 7/12 

1.25

  Over 7/12 to 8/12 

1.5

  Over 8/12 to 9/12 

2.0

  Over 9/12 to 10/12 

2.5

  Over 10/12 to 11/12 

3.25

  Over 11/12 to 12/12 

4.0

*H - Minimum height from roof to 
lowest discharge opening of vent

Содержание MLDV500NSCSB

Страница 1: ... supplier from a neighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department Installation and service must be performed by a qualified installer service agency or the gas supplier WARNING Improper installation adjustment alteration service or maintenance can cause injury or property damage Refer to this manual For assistance or additional ...

Страница 2: ...ype 26 Installing Gas Piping to Fireplace Location 26 Installing Items Needed 26 Check Gas Pressure Millivolt 27 Electrical Installation Millivolt 28 Electrical Wiring 28 Remote Wall Mounted Switch 28 Optional Fan Blower BLOTBLDV 28 Operating Instructions Millivolt 31 For Your Safety 31 Lighting Pilot for the First Time 31 Lighting Pilot 32 Lighting Burner 33 Check Gas Pressure 34 Electrical Insta...

Страница 3: ... for future reference IMPORTANT SAFETY INFORMATION This fireplace is a vented product This fireplace must be properly installed by a qualified service person The glass door must be properly seated and sealed If this unit is not properly installed by a qualified service person with glass door properly seated and sealed combustion leakage can occur CARBON MONOXIDE POISONING Early signs of carbon mon...

Страница 4: ...replace with glass door removed cracked or broken CODE APPROVAL Direct Vent type appliances draw all combustion air from outside of the dwelling through the vent pipe These appliances have been tested by CSA and found to comply with the established standards for DIRECT VENT GAS FIREPLACE HEATERS in the USA and Canada as follows LISTED VENTED GAS FIREPLACE HEATER TESTED TO ANSI Z21 88 2014 CSA 2 33...

Страница 5: ...ilot On Knob Hi Lo Knob On Off RS Switch Ignitor 5 8 Nailing Flange 1 2 Nailing Flange Insulation Board HIGH ELEVATIONS Input ratings are shown in BTU per hour and are cer tified without deration for elevations up to 4 500 feet 1 370 m above sea level For elevations above 4 500 feet 1 370 m in USA installation must be in accordance with the currentANSI Z223 1 NFPA 54 and or local codes having juri...

Страница 6: ...and under the floor on which the appliance rests if the floor is above ground level NOTE Refer to cold climate pilot information on Page 44 for more information on standing pilot vs intermittent pilot options 33 838 mm 41 1041 mm 36 914 mm 30 6 784 mm 20 6 524 mm 2256M 565 mm 1 2 or 5 8 Min Rough Opening Height 27 6QE 694 mm Min Rough Opening Width 4256O 91080 mm Min Rough Opening Depth 50 6 1292 ...

Страница 7: ... extending the full width and depth of the enclosure FIREPLACE LOCATION Plan for the installation of your appliance This includes determining where the unit is to be installed the vent configuration to be used framing and finishing details and whether any optional accessories i e blower wall switch or remote control are desired Consult your local building code agency to ensure compliance with loca...

Страница 8: ...er combustible material other than wood flooring If installed on carpet or vinyl flooring the appliance shall be installed on a metal wood or noncombustible material panel extending full width and depth of the appliance WARNING NOTE When eyebrow canopy is used minimum clearance to combustibles is 21 4 maximum out from fireplace front at 71 2 minimum from opening Figure 5a When eyebrow is not used ...

Страница 9: ...DO NOT REMOVE INSULATION BOARD FINISHING MATERIAL NOTE Any remote wiring i e remote control wall switch and optional fan must be done prior to final finishing to avoid costly reconstruction Only noncombustible materials i e brick tile slate steel or other materials with a UL fire rating of Zero may be used to cover the black painted face of the appliance It is permissible to bring combustible wall...

Страница 10: ...f the installa tion layout requires the unit to be a top vent configuration the appliance can be converted by following the steps below When removing and refitting the plates and adapter be sure the associated gaskets are undamaged and refitted as required 1 Remove the eight 8 screws securing the flue pipe adapter to the fireplace body Figure 7 2 Set the flue pipe adapter aside complete with the g...

Страница 11: ...rews Flue Pipe FP1993 Figure 9 Attach Flue Pipe to Top Vent Configuration Aminimum of 3 clearance to the top is required along horizontal length until flue pipe penetrates outside wall A minimum 1 clearance to combustibles permitted all around flue at outside wall 3 1 1 1 1 3 Figure 10 Combustible Clearances for Vent Pipe ...

Страница 12: ...ed A 1 minimum clearance all around the pipe must be maintained at outside wall and on vertical runs Do not pack the open air spaces with insulation or other materials This could cause high temperatures and may present a fire hazard Unless the vertical run is 71 2 feet or higher top vent units only the clearances for the horizontal run is 1 at the top Never run the vent pipe down This may cause ex...

Страница 13: ...30kW 6 15cm for appliances 10 000 BTU h 3kW 9 23cm for appliances 10 000 BTU h 3kW and 50 000 BTU h 15kW 12 30cm for appliances 50 000 BTU h 15kW C Clearance to permanently closed window 12 305mm recommended to prevent window condensation 12 305mm recommended to prevent window condensation D Vertical clearance to ventilated soffit located above the terminal within a hor izontal distance of 2 610 m...

Страница 14: ...om the finished outside wall to the center of the pipe on the fireplace Vertical Dimension From the Floor of Unit to the Center of the Horizontal Vent Pipe NOTE Termination in an alcove space spaces open only on one side and with an overhang is permitted with the dimensions specified for vinyl or non vinyl siding and soffits 1 There must be a 3 914 mm min imum between termination caps 2 All mechan...

Страница 15: ...2 267 mm 101 2 267 mm 81 2 216 mm Figure 16 Exterior Wall Framing Dimensions Combustible Wall Noncombustible Wall FP1954 2 Refer to venting and termination instructions for further instructions 3 Locate and cut the vent opening in the wall For com bustible walls first frame in opening Combustible Interior Walls Cut a 121 2 x 101 2 hole through the interior wall Combustible Exterior Walls Cut a 101...

Страница 16: ... insert the vent pipe into the horizontal termination The pipe overlap should be a minimum of 11 4 Apply silicone to the outer pipe connection Fasten all vent connections with screws provided 8 Slide the wall thimble against the interior wall surface and attach with screws Figure 19 HORIZONTAL WITH VERTICAL RISE THROUGH THE WALL TERMINATION CONFIGURATIONS Since it is very important that the ventin...

Страница 17: ...l rise Figure 22 Example According to the vent graph Page 17 the maximum horizontal vent length in a system with a 7 5 vertical rise is 20 6 m and if a 90 elbow is required in the horizontal vent it must be reduced to 17 5 2 m In Figures 22 and 23 dimension A plus B must not be greater than 17 5 2 m Figure 23 Maximum Vent Run with Elbows A B 17 Maximum Horizontal 90 Elbow 3 Reduction 7 6 10 7 A B ...

Страница 18: ...58 reducer must be used when 4 x 7 venting is preferred Reducer must be installed directly onto unit at the fireplace collar before vertical rise WARNING You may use a reducer from 5 x 8 to 4 x 65 8 or 4 x 7 for horizontal with vertical rise applications ONLY use framing instructions below when using 4 x 65 8 or 4 x 7 venting If the reducer is installed at the rear of the unit you must immediately...

Страница 19: ...lish vent hole through the wall 2 Remove soil to a depth of approximately 16 below base of snorkel Install drain pipe Install window well not supplied Refill hole with 12 of coarse gravel leaving a clearance of approximately 4 below snorkel Figure 27 3 Install vent system 4 Ensure a watertight seal is made around the vent pipe coming through the wall 5 Apply high temperature sealant caulking suppl...

Страница 20: ...e Collar Figure 29 Install Restrictor Disc into Fireplace Collar This Gas Fireplace has been approved for Vertical installations up to 40 12 m in height Up to a 10 3 m horizontal vent run can be installed within the vent system using a maximum of two 90 elbows Figure 30 10 3 m Maximum 10 3 m Maximum Maximum Height 40 12 m Minimum Height 8 2 m Support Straps Every 3 914 mm Figure 30 Support Straps ...

Страница 21: ... and any maximum horizontal offset limitations Offsets must fall within the parameters shown on Page 17 Figure 13 Figure 32 Offset with Wall Strap and 45 Elbows Roof Flashing Wall Strap 45 Elbows Ceiling Firstop FP1669 1 2 3 4 1 2 3 4 Figure 31 Maximum Elbow Usage Example Elbow 1 90 Elbow 2 45 Elbow 3 45 Elbow 4 90 Total Angular Variation 270 FP1179 2 Set fireplace in desired location Drop a plumb...

Страница 22: ...e 45 elbow offers less restriction to the flow of the flue gases and intake air 5 Place the flashing over the pipe section s extending through the roof Secure the base of the flashing to the roof and framing with roofing nails Be sure roofing material overlaps the top edge of the flashing There must be a 1 clearance from the vent pipe to combus tible materials 6 Continue to add pipe sections until...

Страница 23: ...the flexible vent 5 Flexible vent spacers are to be installed at inter vals prescribed by the flexible vent manufacturer and in such a way as to maintain concentric inner and outer vent spacing FLEX VENT INSTALLATION 1 Flexible UL1777 listed venting may be used in any venting application where rigid direct vent components can be used All restrictions clearances and allow ances that pertain to the ...

Страница 24: ... equi distant just above gear clamp Gear Clamp UL1777 Flex Vent 13 4 Flexible Pipe and Collar Overlap Vermont Castings Group Horizontal Vent Termination Figure 40 Typical Horizontal Flex Vent Installation Termination Cap Storm Collar Roof Support Flashing Rigid Pipe Length Flex to Pipe Adapter Firestop UL1777 Flex PIpe Screws 3 Places equidistant just above gear clamp Rigid Pipe Length Flex to Pip...

Страница 25: ... UL1777 Flex PIpe Screws 3 Places equidistant just above gear clamp 4 x 7 Rigid Pipe Length Flex to Pipe Adapter DVFFA 8 Gear Clamp 13 4 Flexible Pipe and Adapter Outer Collar Overlap UL1777 Flex Vent Figure 43 Typical Pipe Connection Gear Clamp 7TDVP58 5 x 8 to 4 x 7 Reducer Figure 41 Typical 4 x 7 Appliance Connection UL1777 Flex Vent Screws 3 places equidistant just above gear clamp 13 4 Flexib...

Страница 26: ...s control inlet is 3 8 NPT WARNING A qualified installer or service person must connect appliance to gas supply Follow all local codes CAUTION For propane LP units never connect fireplace directly to the propane LP supply This burner system requires an external regulator not supplied Install the external regulator between the burner system and propane LP supply External Regulator 100 gallon min Pr...

Страница 27: ...ent trap collects moisture and contami nants and keeps them from going into the burner system gas controls If sediment trap drip leg is not installed or is installed wrong burner system may not run properly CHECK GAS PRESSURE 1 Check gas type The gas supply must be the same as stated on the appliance s rating decal If the gas supply is different from the fireplace STOP Do not install the appliance...

Страница 28: ... 48 Wiring Diagram for Wall Switch ON OFF OPTIONAL REMOTE WALL SWITCH ON OFF OPTIONAL REMOTE WALL SWITCH PILOT HI LO ON OFF TH TP TH TP ON OFF RS OPTIONAL FAN BLOWER SYSTEM BLOTBLDV Installation Instructions Wiring 1 Before installing the blower wire the receptacle into an electrical circuit This should be done before framing the fireplace Wire with minimum 60 C wire in accor dance with prevailing...

Страница 29: ...n bottom of each blower before installing Figure 50 9 The blowers are to be inserted flat through the engine cutout in the firebox floor Slide each blower over to the sidewall location Figure 51 10 Turn blowers with discharge vent facing up Slide the discharge vent so that it is facing up Slip discharge vent flange under the flange bracket flush against the sidewall Slide blower side tabs over int...

Страница 30: ...rder of removal 15 Plug in the blower 16 Re install firebrick grate logs and glass door in re verse order of removal 17 To test blower operation set the variable speed blow er on the LOW setting Turn the fireplace on high The blower should turn on within 10 minutes 18 If the blower does not turn on turn the fireplace off and allow cooling Unplug the blower Using a jewel er s style screwdriver turn...

Страница 31: ...lified service technician Force or attempted repair may result in a fire or explosion D Do not use this appliance if any part of it has been under water Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas control that has been under water INITIAL LIGHTING Purge air from the supply line as follows Open main shutoff valve...

Страница 32: ...ion Check for gas leaks in each of the following locations Pipe from the gas supply line connection to the gas valve Burner connections Field made joints gas shutoff valve Pilot Factory made joints Each joint or connection All joints on valve and control body LIGHTING PILOT FOR THE FIRST TIME CONT D OPERATING INSTRUCTIONS MILLIVOLT WARNING If using a soap and water solution to test for leaks DO NO...

Страница 33: ...the button is in the ON position to light the main burner LIGHTING THE BURNER Depress and turn the knob counterclockwise to the ON position It will take less than four 4 seconds for the burner to ignite PILOT POSITION Depress and turn knob to pilot position to keep burner off while main taining the pilot light Depress and turn knob clockwise to OFF position Off Position Pilot Position PILOT O F F ...

Страница 34: ... which operates on 6 volts The 6 volt DC adapter plugs into the fireplace junction box A C power supply Four 4 AA batteries are used for back up during power outages 2 The Signature Command System can also be operated without A C power The system can run on four 4 AA batteries for approximately six 6 months under normal use 3 A C power must be used to power the A C module blowers lights and AUX ac...

Страница 35: ...xtend beyond the 15 ft wire cable provided If a longer distance is required the 15 ft may be extended up to 30 ft maximum by using two 2 SCSWEK cables plugged together Route the wire from junction box to lower control area at bottom of fireplace Unplug the 12 cable from the com mand center Attach the connector to the pins from wire by pushing in to connector making sure to follow the color code on...

Страница 36: ...nnector Control Board to Command Center OFF LO LED ON HI Master Switch Command Center Optional Wall Switch Plug in Connector Stepper Motor to Control Board DC Power Green Ground Plug in Connector Control Board to Solenoid Gas In Gas Out Pilot Gas Tubing Valve ELECTRICAL INSTALLATION SIGNATURE COMMAND CAUTION Electrical connections should only be performed by a qualified licensed electrician Main p...

Страница 37: ...or the control will not work correctly WARNING Electrical connections should only be performed by a qualified licensed electrician Main power supply must be turned off before connecting the fan to the main electrical power supply or performing service BLOTSDVSC SIGNATURE COMMAND BLOWER Electrical Grounding Instructions This appliance is equipped with a three prong grounding plug for your protectio...

Страница 38: ...trol OPTIONAL FAN BLOWER SYSTEMS SIGNATURE COMMAND BLOTSDV AUTOMATIC THERMOSTAT BLOWER Figure 60 BLOTSDV Blower Wiring Diagram FP2685 Before installing the blower wire the receptacle into an electrical circuit This should be done before framing the fireplace Wire with minimum 60 C wire in accordance with prevailing codes ...

Страница 39: ...s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department C Use only your finger to push in the master switch Never use tools If the switch will not function by hand do not try to repair it Call a qualified service technician Force or attempted repair may result in a fire or explosion D Do not use this appliance if any part of it has been under w...

Страница 40: ...ge 38 If you do not smell gas go to next step 4 Press the master switch to the ON position Within eight 8 seconds it will beep once This indi cates the system is ready 5 Press ON button Sparker will spark and pilot flame will light 6 Once pilot flame is established the main burner flame will light automatically 7 If the pilot will not stay lit after several tries turn the master switch to OFF and ...

Страница 41: ...tat Auto Flame Blower Modulation X X Three Brightness Settings for Lights X Three Speed Control for Blower X On Off Auxiliary X Programmable Timer X SIGNATURE COMMAND SYSTEM OPERATION INSTRUCTIONS RF Receiver ON OFF NG LP Conversion To Thermopile To Sensor To Sparker To Command Center To Stepper Motor To Valve Battery Door Master Switch ON LED OFF Control Board Command Center Figure 61 Signature C...

Страница 42: ...on Remote Transmitter Learn Function Default OFF 1 The RF receiver button located on the Control Board must be in the on position before the learn function can begin Use paper clip to depress button One beep for RF receiver ON or two beeps for RF receiver OFF will be given as confirmation Refer to Figure 62 for location 2 After the RF receiver is on holding the OFF button on the Command Center whi...

Страница 43: ...ing the Fireplace Off There are three ways to turn the fireplace off 1 Flip the master switch to the off O position This will turn the entire system OFF 2 Press the OFF button to Medium Low then Off 3 Hold the OFF button anytime for three seconds or by turning off the wall switch These two commands of OFF are Memory Off the system will remember all last settings before turning off The next time th...

Страница 44: ...ard the tops 3 Slide the right panel into place and secure the panel using one of the brackets provided with the kit and one of the screws removed earlier 4 Repeat step 2 for the left panel Clamps EYEBROW CANOPY INSTALLATION 1 Remove glass frame 2 Hold eyebrow canopy with groove facing up and tabs for screws facing down Figure 63 3 Install by placing eyebrow under bottom lip of facing Hook bottom ...

Страница 45: ...EMENT 1 Place log 1 by setting the log over the rear bracket over the two pins Figure 65 2 Place log 2 at angle across the burner by setting the logs over the two pins located on top of the burner Figure 66 3 Place log 3 at an angle over log 2 toward the back by matching the rectangular notch on the bottom of this log with the rectangular protrusion on log 2 Then set the notch located on the botto...

Страница 46: ...set the notch on the bottom of this log over the very far left tong on the grate Figure 69 6 Place log 6 at an angle over log 5 toward the back by matching the rectangular notch on the bottom of this log with the rectangular protrusion on log 5 Then set the notch located on the bottom of this log toward the back over the metal bracket located to the left side of the burner Figure 70 7 Place log 7 ...

Страница 47: ...ANGER HOT GLASS WILL CAUSE BURNS DO NOT TOUCH GLASS UNTIL COOLED NEVER ALLOW CHILDREN TO TOUCH GLASS A barrier designed to reduce the risk of burns from the hot viewing glass is provided with this appliance and shall be installed CERTIFIED SAFETY BARRIER 1 Remove screen from packaging 2 Align the four tabs on the sides of the screen frame two top two bottom Figure 72 with the correspond ing slots ...

Страница 48: ... a brush or vacuum BURNER FLAME The flames from the burner should be visually checked as soon as the heater is installed and periodically during normal operation In normal operation at full rate and after operating for about 15 to 30 minutes the flame should be yellow and slightly taller than the rear log Figure 75 If the flame is blue and only in the center turn off unit and let cool After unit i...

Страница 49: ... als may be used Handle glass door with care to avoid striking or scratch ing it on hard objects To clean glass door follow Glass Removal procedure outlined in the Final Installation section Film deposit on the inside of the glass should be cleaned off using a nontoxic non corrosive non abrasive mild cleaning solution Simply apply an adequate amount to the glass and wipe off with a damp cloth Afte...

Страница 50: ...V replace pilot assembly B If thermocouple is producing more than 15 mV replace faulty valve 3 Pilot burning valve knob turned to ON switch is turned to ON or RS but burner will not ignite A Defective switch wall switch remote control or wire B Pilot flame too small C Defective or malfunc tioning thermopile D Defective valve A Check switch and wire for proper connection Place jumper wires across t...

Страница 51: ...el or downward C Check for proper installation and freedom from debris or blockage 6 Glass Soots A Flame impingement on logs A Install log set per the instructions Inspect the injector and air intake area Make sure this area does not have any blockage from debris and clean Check gas supply 7 Flame burn blue and lifts off burner ghosting A Insufficient oxygen being supplied A Ensure that the vent c...

Страница 52: ...upply Go through Battery polarity wrong LED on the Command Center does not show solid green The 5 pin connector on the AC board broken or bent AC plug is plugged to AC mains Battery voltage low Using battery Check valve connections Check power supply go through A E Check grounding Go through B Go through C The sensor on the pilot is not in the flame pilot flame too small ACTION Re install batterie...

Страница 53: ...16 4 Insulation Board 1 75D0008 5 Eyebrow 1 20302777 6 Safety Barrier 1 20306653K Accessories Field Installed Options 7 Decorative Mesh Glass Cover not shown 1 MLDV500SD 8 Firebrick Walls Cottage Clay 1 FBMLDV500CC 8 Firebrick Walls Cottage Red 1 FBMLDV500CR 8 Firebrick Walls Vintage Brown Herringbone not shown 1 FBMLDV500VB 9 T stat Blower w Speed Control not shown 1 BLOTBLDV 9 SCS Blower Kit w T...

Страница 54: ...6748 MLDV Series Gas Fireplace LOGS REPLACEMENT PARTS Item Description Qty MLDV500 1 Log 1 1 75D0536 2 Log 2 1 75D0537 3 Log 3 1 75D0538 4 Log 4 1 75D0539 5 Log 5 1 75D0540 6 Log 6 1 75D0541 7 Log 7 1 75D0542 ...

Страница 55: ...D0550 4 Flex Hose w Shutoff Valve 1 69D0030 69D0030 5 Rocker Switch 1 41D0048 41D0048 6 Piezo Igniter 1 14D0503 14D0503 7 Injector 1 56D0613 20H3153 8 Burner Assembly 1 75D1008 75D1008 9 Venturi 1 45D0600 45D0600 10 Wire Assembly 1 44D0500 44D0500 10 Wire Assembly 1 44D0501 44D0501 Accessories 11 Thermostatic Remote Control 1 RCST RCT WWTD RCSTEB RCSITE 12 On Off Remote Control 1 RCB RCBE RCMT WMT...

Страница 56: ...11 Wire Command Center Control Box 2 feet not shown 1 80D0008 80D0008 12 A C Adapter 6 Volt 1 80D0041 80D0041 Accessories 13 Hand Held Remote Control w HI LO and Timer RMSC 14 Hand Held Remote Control w Hi lo And Tstat RTSC 15 Touch Screen Remote w Optional Light Auxiliary and Blower Control TSFSC 16 Touch Screen Remote Hi Lo and Timer TSMSC 17 Touch Screen Remote Hi Lo and TStat TSTSC 18 SCS Wall...

Страница 57: ...or the venting components referenced above please contact the component manufacturer Selkirk Corporation www selkirkcorp com or 800 992 8368 Duravent www duravent com or 800 835 4429 HOT 1 2 3 4 5 6 9 7 8 11 10 VENTING COMPONENTS See pages 60 and 61 for part number legend for 4 x 65 8 and 5 x 7 venting ...

Страница 58: ...Pipe Length galvanized 46DVA 09 907 4DT 09 3 6 12 Pipe Length galvanized 46DVA 12 906 4DT 1 3 6 24 Pipe Length galvanized 46DVA 24 904 4DT 4 3 6 36 Pipe Length galvanized 46DVA 36 903 4DT 36 3 6 48 Pipe Length galvanized 46DVA 48 902 4DT 48 4 6 81 2 Pipe Extension galvanized 46DVA 08A 4DT AJ 4 6 16 Pipe Extension galvanized 46DVA 16A 4DT AJ14 5 6 45 Elbow galvanized 46DVA E45 945 4DT EL45 6 6 90 E...

Страница 59: ...Pipe Length 58DVA 12 1206 5DT 12 5D12 3 4 24 Pipe Length 58DVA 24 1204 5DT 24 5D24 3 4 36 Pipe Length 58DVA 36 1203 5DT 36 5D36 3 4 48 Pipe Length 58DVA 48 1202 5DT 48 5D48 4 4 81 2 Pipe Extension 58DVA 08A 5DT AJ 4 4 16 Pipe Extension 58DVA 16A 5 4 45 Elbow 58DVA E45 1245 5DT EL45 5D456 5 4 45 Swivel Elbow 5DT EL45 6 4 90 Elbow 58DVA E90 1290 5DT EL90S 5D906 6 4 90 Swivel Elbow 1290G 5DT EL90S 7 ...

Страница 60: ...restop Cool 7FDVSCTK Touch Termination w Siding Shield and 2 ea Clamp Bands Twist Lock Pipe 20 Termination Pipe 8 pack 7TDVP20 8 10 16 Adjustable Termination Pipe 4 pack 7TDVPA 4 12 18 Adjustable Vent Length 7TDVP1218 35 64 Adjustable Vent Length 7TDVP3564 8 Vent Pipe 4 pack 7TDVP8 4 12 Vent Pipe 4 pack 7TDVP12 4 24 Vent Pipe 4 pack 7TDVP24 4 36 Vent Pipe 7TDVP36 36 Vent Pipe 30 pack 7TDVP36 30 48...

Страница 61: ...7TDVP20 30 Flex Pipe single pack 7FDVP30 12 18 Adjustable Vent Length 7TDVP1218 35 64 Adjustable Vent Length 7TDVP3564 8 Vent Pipe 4 pack 7TDVP8 4 12 Vent Pipe 4 pack 7TDVP12 4 24 Vent Pipe 4 pack 7TDVP24 4 36 Vent Pipe 7TDVP36 36 Vent Pipe 30 pack 7TDVP36 30 48 Vent Pipe 7TDVP48 48 Vent Pipe 30 pack 7TDVP48 30 5 x 8 to 4 x 7 Adapter 7TDVP58 Flex Adapter Starter Kit DVFFA 8 Twist Lock Elbows 45 El...

Страница 62: ...to comply with the above requirements provided however that during said thirty 30 day period a battery operated carbon monoxide detector with an alarm shall be installed MASSACHUSETTS RESIDENTS ONLY 2 Approved Carbon Monoxide Detectors Each carbon monoxide detector as required in accordance with the above provisions shall comply with NFPA 720 and be ANSI UL 2034 listed and IAS certified 3 Signage ...

Страница 63: ...so be void if the appliance is not operated and maintained according to the operating instructions supplied with the appliance and does not extend to 1 firebox burner assembly damage by accident neglect misuse abuse alterations negligence of others including the installation thereof by unqualified installers 2 the costs of removal reinstallation or transportation of defective parts on the applianc...

Страница 64: ...sed on CSA P 4 1 09 Efficiency Ratings Model EnerGuide Ratings D O E Fireplace Efficiency AFUE MLDV500NV 70 5 67 1 MLDV500PV 76 4 67 3 149 Cleveland Drive Paris Kentucky 40361 www vermontcastingsgroup com ...

Отзывы: