5
Chateau™ Decorative Gas Appliance
20009543
Top of Unit to Ceiling ................................ 36” (914 mm)
Front of Unit to Combustibles
(both sides)
... 36” (914 mm)
Appliance
Top Standoffs .............................................. 0” (0 mm)
Bottom ......................................................... 0” (0 mm)
Side Standoffs ............................................. 0” (0 mm)
Back Standoffs ............................................ 0” (0 mm)
Venting
Horizontal Termination through-a-side wall:
Vertical Sections:
Sides ................................................ 2
¹⁄₂
” (64 mm)
Horizontal Sections:
Top .................................................. 3
¹⁄₂
” (89 mm)
Bottom ............................................. 1
¹⁄₂
” (38 mm)
Sides ................................................ 2
¹⁄₂
” (64 mm)
Vertical Vent Application:
Sides ............................................... 1
¹⁄₂
” (38 mm)
A hearth is not mandatory but is recommended for
aesthetic purposes. We recommend a noncombustible
hearth which projects out 12” (305 mm) or more from
the front of the fireplace. The hearth cannot exceed 1
¹⁄₂
”
(38 mm) in height from bottom of fireplace for ease of
door accessibility. (Fig. 4)
Cold climate installation recommendation:
When installing this unit against a non-
insulated exterior wall or chase, it is
mandatory the outer walls be insulated to
conform to applicable insulation codes.
Hearth
Clearance to Combustibles
Mantels
The height that a combustible mantel is fitted above the
fireplace is dependent on the depth of the mantel. This
also applies to the distance between the mantel leg (if
fitted) and the fireplace.
For the correct mounting height and widths refer to
Figs. 3a and 3b, the following Mantel Charts.
Noncombustible mantels and legs may be installed at
any height and width around the appliance.
When using paint or lacquer to finish the mantel, such
paint or lacquer must be heat resistant to prevent
discoloration.
�
�
�
�
�
�
�
�
�
�������
�������
������������
�
Fig. 3a
Combustible mantel minimum installation.
Mantel Chart
Mantel Shelf
Mantel from Top
Ref. or Breast Plate Ref. of Comb. Chamber
Depth
V
10” (254 mm)
A
10” (254 mm)
W
9”
(229 mm)
B
9” (229 mm)
X
8”
(203 mm)
C
8” (203 mm)
Y
7”
(178 mm)
D
7” (178 mm)
Z
6”
(152 mm)
E
6” (152 mm)
CFM146d
Combustible
Framing and
Finish Wall Above
Standoffs
Standoff
Top of Sheet Metal
Noncombustible Finish Material
(Such as Dura Rock)
Fireplace Front
May use com-
bustible facing
material in this
area
�
�
�
�
�
�������
���������������
�������
�������������
Mantel Leg
CFM164c
������
�����������������
����
�������������
�
�
�
�
�
CFM170a
Fig. 3b
Combustible mantel leg minimum installation.
Mantel
Mantel Leg from Side
Ref.
Leg Depth
Ref.
of Comb. Opening
F
12” (305 mm)
K
12” (305 mm)
G
9” (229 mm)
L
9”
(229 mm)
H
6” (152 mm)
M
6”
(152 mm)
I
4” (102 mm)
N
4”
(102 mm)
J
3” (76 mm)
O
3”
(76 mm)
Side of Fireplace
Noncombustible
Finish Material