Do not use this fireplace if any part of it has
been under water. Immediately call a qualified
service technician to inspect the fireplace and
replace any part of the control which has been
under water.
Cold climate installation recommendation:
When installing this unit against a non-
insulated exterior wall or chase, it is
mandatory that the outer walls be insulated
to conform to applicable insulation codes.
HEARTH
A hearth is not mandatory but it is recommended for
aesthetic purposes. We recommend a non-combustible
hearth which does not obstruct louvre opening.
GAS INLET & MANIFOLD PRESSURES
Input Minimum
Input Maximum
Manifold Pressure
NATURAL
LP (Propane)
11" wc
13" wc
10" wc
4.5" wc
7" wc
3.5" wc
GAS SPECIFICATIONS
MAX.
MIN.
INPUT
INPUT
MODEL
FUEL
GAS CONTROL
B.T.U.H
B.T.U.H.
BHDT36 RN
Natural Gas
Millivolt Hi/Lo
18,000
12,600
BHDT36 RP Propane Gas
Millivolt Hi/Lo
18,000
13,500
CERTIFIED TO
ANSI Z21.88a-1998 / CSA 2.33a-M98
Vented Gas Fireplace Heaters.
The installation of your Majestic Fireplace
must conform with local codes, or in the
absence of local codes, with National Fuel
Gas Code, ANSI Z223.1 latest edition, or CAN
1 B1-149.1 and .2 Installation Code.
(EXCEPTION: Do not derate this appliance
for altitude. Maintain the manifold pressure
at 3.5 inches W.C. for Natural Gas and 10
inches W.C. for LP gas.)