VERLINDE reserves the right to alter or amend the above information without notice.
11/2008
The customer must supply the power supply cable, the fuses and the main isolator switch
(refer to the wiring diagram).
Check that the mains system is correct for the hoist.
Check that the voltage does not vary by more than + 5% from the nominal value.
Neutralize the electric sources.
Make sure that the main hoist electric power switch is off.
Do not use binding posts (luster terminals, etc.) to connect the power supply cable to the hoist.
Do not use rigid cable or cable with a section different to that indicated below to supply the hoist.
Never shunt the isolators, the power switches or the limitation or prevention equipment.
Never block, adjust or remove the limit stops or switches to go higher or lower than these allow.
8.1.2 Connection
:
•
- Connect phases L1 - L2 - L3 and the ground on the power supply plug.
•
- Connect the plug on the cubicle. Don’t forget to add the sealing join with screws
•
- Check the hoist operation
•
Minimum cable sections :
Power supply :
1,50 mm2
Auxiliary current :
0,75 mm2
Control box/hoist :
1,00 mm2
Fuses (low voltage) :
See electric
power supply (
customer supply
) :
Drawing
)
The electrical configuration can be different according to the specifications of the hoist. See
electrical drawing
,
Do not change the travel direction labels in the control box or in the hoist internal wiring.
PS :
Power supply - PB :
Control box connection - TR :
Trolley connection
PS
TR
PB