Figure 2
NetBackup 5330 Expansion Storage Shelf Expansion canisters
To remove a RAID or an Expansion canister
Warning:
If you perform this procedure with the power turned on, you must complete it within 15
minutes to prevent the possibility of overheating the equipment.
Do not remove both canisters from the storage shelf at the same time. One canister must be functioning
at all times.
1
Locate and identify the storage shelf that has the faulty canister as follows
•
On a NetBackup 5330 Primary Storage Shelf or an Expansion Storage Shelf, the serial number
is located on a label on the front, lower right corner of the shelf.
2
Before you begin service on the affected canister, verify that the component is in the Service
Action Allowed mode.
Check that the LED is blue.
Each canister contains one of these LEDs. Be sure to work on the canister that has the blue LED.
Primary Storage Shelf RAID canister Service Action Allowed LEDs
5
HSP 133 RAID or Expansion canister replacement