H81xx

INSTALLATION GUIDE

Typical 120 VAC, 2-Wire, 1Ø Installation

N

A

+ A – + B –

+ C –

B

C

N

A B

C

Red

Black

Yello

w

Red Black

W

hit

e

Yello

w

RED CT

WHITE

Ø A

N

*

* External fuse provided by installer (optional, per 
NEC and local regulations).

For 1600A or larger models in contact with a power conductor for use over the full ambient 
temperature load range, use 90

°

C wire insulation or derate the accuracy appropriately. 

Typical 208/480VAC, 

**

 4-Wire, 3Ø Installation

N

A

+ A Р+ B Ð

+ C Ð

B

C

N

A B

C

RED CT

WHITE

ØA

ØB

N

BLACK CT

ØC

YELLOW CT

W

hit

e

Red Black Yello

w

Red Black Yello

w

*

*

*

Typical 240/120 VAC, 3-Wire, 1Ø Installation

N

A

+ A – + B –

+ C –

B

C

N

A B

C

RED CT

WHITE

ØA

ØB

N

BLACK CT

W

hit

e

Red Black Yello

w

Red Black Yello

w

*

*

WIRING

N

A

+ A D + B D

+ C D

B

C

N

A B

C

+ - + - + -

Display

Plain

Full

Black

Black

Yellow

Yellow

Red

Red

Pulse Output 

Terminal

Phase Loss 

Output 

Terminal

Backlight Enable Jumper

20 seconds per cycle 

90 seconds per cycle 

kW

max. kW

PF

Volts L-L

Amps

kW

max. kW

PF

Volts  L-L

Amps

kVAR

kW  Phase  A

kW  Phase  B

kW  Phase  C

PF  Phase  A

etc.

** 480 VAC only applies to the H8163 and H8167

Connect white wire to (-). 

Connect red/black/yellow wire to (+).

5.  Use color coding to attach current transformer (CT) leads to the input terminals 

(e.g. red labeled lead to red terminal). Polarity is indicated in the wiring diagrams, 
but the meter is not polarity sensitive. See the Wiring section.

6.  Use color coding to connect voltage leads to phase conductors (e.g. red 

transformer lead to red terminal). The meter is powered from the monitored 
source, so connect the voltage leads to a circuit that is normally left on. See the 
Wiring section.

7.  

H8163 and H8167:

  Connect the output terminals to the control/data acquisition 

system. The Pulse Output is normally open. For the H8163, the Phase Loss Output 
is normally open, and for the H8167, it is normally closed. Both are rated for 24 
VAC/VDC@100 mA maximum. Ensure that the installation method and insulation 
ratings conform to local and national electrical codes.

8.  Set the backlight enabling jumper as desired. Remove the jumper to disable the 

backlight.

9.  Set the Display Data jumper for either Plain or Full settings. Plain mode cycles 

the display through five data elements (kW, max. kW since last reset, average PF, 
line-to-line voltage, and amps) for four seconds each. Full mode cycles through all 
of the data available in the meter. See the Information Reporting section for more 
details.

www.

GlobalTestSupply

.com

Find Quality Products Online at:

[email protected]

Содержание H81xx

Страница 1: ...e to follow these instructions will result in death or serious injury A qualified person is one who has skills and knowledge related to the construction and operation of this electrical equipment and...

Страница 2: ...CTs only PRODUCT OVERVIEW The H81xx Series energy meter combines industrial grade split core current transformers and precision microprocessor based metering electronics It can detect phase reversal...

Страница 3: ...29mm E 8 1 207mm F 5 9 150mm MINI 200Amp MICRO 100Amp MEDIUM 400 800Amp A 3 8 95mm B 1 5 38mm C 1 3 32mm D 1 1 29mm E 4 2 107mm F 4 8 121mm SMALL 300Amp LARGE 800 1600 2400Amp F E D C B A A 1 6 40 mm...

Страница 4: ...ontrol data acquisition systems H8163 and H8167 6 Phaselossoutputalarm Alarm trips to protect equipment if phase voltage drops 25 H8163 and H8167 7 Pulserateselectionswitch Set the pulse output at 0 1...

Страница 5: ...quire a mounting bracket For maximum accuracy run the conductor through the center of the current transformer window 4 Optionalstep perNECandlocalregulations Attach external fuses not included with th...

Страница 6: ...T leads to the input terminals e g red labeled lead to red terminal Polarity is indicated in the wiring diagrams but the meter is not polarity sensitive See the Wiring section 6 Use color coding to co...

Страница 7: ...phase The displayed message indicates the problem phase Amps Over The measured current is greater than 110 of the transformer range The display message indicates the problem phase Volts Over Volts A C...

Страница 8: ...ween the terminals No Pulse output H8163 and H8167 Verify power is supplied in the range of 5 24VAC DC with a max load of 100 mA The pulse output internal is 200 msec verify the controller accepts thi...