TM
H81xx
INSTALLATION GUIDE
PRODUCT IDENTIFICATION
120 VAC - 240 VAC (nom.)
Amps
One CT
Two CTs
Three CTs
Voltage
Output
100 Micro H8150-0100-0-1
H8150-0100-0-2
H8150-0100-0-3
90-132VAC L-N Display Only
200 Mini
H8150-0200-1-1
H8150-0200-1-2
H8150-0200-1-3
300 Small H8150-0300-2-1
H8150-0300-2-2
H8150-0300-2-3
400 Med
H8150-0400-3-2
H8150-0400-3-3
800 Med
H8150-0800-3-2
H8150-0800-3-3
800 Lg
H8150-0800-4-3
1600 Lg
H8150-1600-4-3
2400 Lg
H8150-2400-4-3
120 VAC - 480 VAC (nom.)
Amps
One CT
Two CTs
Three CTs
Voltage
Output
100 Micro
H8163-0100-0-1 H8167-0100-0-1 H8163-0100-0-2
H8167-0100-0-2
H8163-0100-0-3
H8167-0100-0-3
90-300VAC L-N
Pulse, Phase
Loss, and
Display
200 Mini
H8163-0200-1-1 H8167-0200-1-1 H8163-0200-1-2
H8167-0200-1-2
H8163-0200-1-3
H8167-0200-1-3
300 Small
H8163-0300-2-1 H8167-0300-2-1 H8163-0300-2-2
H8167-0300-2-2
H8163-0300-2-3
H8167-0300-2-3
400 Med
H8163-0400-3-2
H8167-0400-3-2
H8163-0400-3-3
H8167-0400-3-3
800 Med
H8163-0800-3-2
H8167-0800-3-2
H8163-0800-3-3
H8167-0800-3-3
800 Lg
H8163-0800-4-3
H8167-0800-4-3
1600 Lg
H8163-1600-4-3
H8167-1600-4-3
2400 Lg
H8163-2400-4-3
H8167-2400-4-3
Optional Comm Board (sold separately)
Model
Description
H8163-CB
Modbus® Communications Board for H81xx Series
H8186-CB
BACnet® Communications Board for H81xx Series
H8126-CB
Metasys® N2 Communications Board for H81xx Series (consult factory if ordering this item)
Optional Accessory
Model
Description
AH06
Mounting Bracket Kit (fits the Small, Medium, and Large CTs only)
PRODUCT OVERVIEW
The H81xx Series energy meter combines industrial-grade split-core current
transformers and precision microprocessor-based metering electronics. It can detect
phase reversal, which eliminates load orientation concerns. The meter and current
transformers are calibrated as a set, so the installer must match their serial numbers
at the time of installation. The H8150 provides a control power voltage range of
90-132 VAC. The H8163 and H8167 provide an extended input control power voltage
range (90-300 VAC).
The H8163 and H8167 models also have a pulse output compatible with building
control systems, a phase loss output to protect equipment. All models include a slot
to install a Modbus, BACnet, or Metasys communication board (sold separately).
When equipped with this board and connected to a data acquisition system, the
H8163 and H8167 can report energy and power diagnostic variables, including kWh,
kW, PF, kVAR, Volts, and Amps.
QUICK INSTALL
1. Verify that the serial numbers on the meter and the current transformers (CTs)
match (if using 100A CTs, serial number matching does not apply).
2. Mount the meter housing.
3. Attach the CT(s) to the conductor.
4. Connect the voltage leads. Use color coding to connect the CT leads to the input
terminals and the voltage leads to the phase conductors (e.g. red to red).
5. Connect the Pulse and Phase Loss output terminals to the controller (H8163 and
H8167).
6. Set the backlight and display data jumpers as desired.
7. Set the Pulse Rate selection switch as desired (H8163 and H8167).
8. Secure the cover and apply power to the meter.