background image

TM

H81xx

INSTALLATION GUIDE

PRODUCT IDENTIFICATION 

120 VAC - 240 VAC (nom.)

Amps

One CT

Two CTs

Three CTs

Voltage

Output

100 Micro H8150-0100-0-1

H8150-0100-0-2

H8150-0100-0-3

90-132VAC L-N Display Only

200 Mini

H8150-0200-1-1

H8150-0200-1-2

H8150-0200-1-3

300 Small H8150-0300-2-1

H8150-0300-2-2

H8150-0300-2-3

400 Med

H8150-0400-3-2

H8150-0400-3-3

800 Med

H8150-0800-3-2

H8150-0800-3-3

800 Lg

H8150-0800-4-3

1600 Lg

H8150-1600-4-3

2400 Lg

H8150-2400-4-3

120 VAC - 480 VAC (nom.)

Amps

One CT

Two CTs

Three CTs

Voltage

Output

100 Micro

H8163-0100-0-1 H8167-0100-0-1 H8163-0100-0-2

H8167-0100-0-2

H8163-0100-0-3

H8167-0100-0-3

90-300VAC L-N

Pulse, Phase 

Loss, and 

Display

200 Mini

H8163-0200-1-1 H8167-0200-1-1 H8163-0200-1-2

H8167-0200-1-2

H8163-0200-1-3

H8167-0200-1-3

300 Small

H8163-0300-2-1 H8167-0300-2-1 H8163-0300-2-2

H8167-0300-2-2

H8163-0300-2-3

H8167-0300-2-3

400 Med

H8163-0400-3-2

H8167-0400-3-2

H8163-0400-3-3

H8167-0400-3-3

800 Med

H8163-0800-3-2

H8167-0800-3-2

H8163-0800-3-3

H8167-0800-3-3

800 Lg

H8163-0800-4-3

H8167-0800-4-3

1600 Lg

H8163-1600-4-3

H8167-1600-4-3

2400 Lg

H8163-2400-4-3

H8167-2400-4-3

Optional Comm Board (sold separately)

Model

Description

H8163-CB

Modbus® Communications Board for H81xx Series

H8186-CB

BACnet® Communications Board for H81xx Series

H8126-CB

Metasys® N2 Communications Board for H81xx Series (consult factory if ordering this item)

Optional Accessory

Model

Description

AH06

Mounting Bracket Kit (fits the Small, Medium, and Large CTs only)

PRODUCT OVERVIEW

The H81xx Series energy meter combines industrial-grade split-core current 
transformers and precision microprocessor-based metering electronics. It can detect 
phase reversal, which eliminates load orientation concerns. The meter and current 
transformers are calibrated as a set, so the installer must match their serial numbers 
at the time of installation. The H8150 provides a control power voltage range of 
90-132 VAC. The H8163 and H8167 provide an extended input control power voltage 
range (90-300 VAC). 

The H8163 and H8167 models also have a pulse output compatible with building 
control systems, a phase loss output to protect equipment. All models include a slot 
to install a Modbus, BACnet, or Metasys communication board (sold separately). 
When equipped with this board and connected to a data acquisition system, the 
H8163 and H8167 can report energy and power diagnostic variables, including kWh, 
kW, PF, kVAR, Volts, and Amps.

QUICK INSTALL

1.  Verify that the serial numbers on the meter and the current transformers (CTs) 

match (if using 100A CTs, serial number matching does not apply).

2.  Mount the meter housing.

3.  Attach the CT(s) to the conductor. 

4.  Connect the voltage leads. Use color coding to connect the CT leads to the input 

terminals and the voltage leads to the phase conductors (e.g. red to red).

5.  Connect the Pulse and Phase Loss output terminals to the controller (H8163 and 

H8167).

6.  Set the backlight and display data jumpers as desired.

7.  Set the Pulse Rate selection switch as desired (H8163 and H8167).

8.  Secure the cover and apply power to the meter.

www.

GlobalTestSupply

.com

Find Quality Products Online at:

[email protected]

Содержание H81xx

Страница 1: ...e to follow these instructions will result in death or serious injury A qualified person is one who has skills and knowledge related to the construction and operation of this electrical equipment and...

Страница 2: ...CTs only PRODUCT OVERVIEW The H81xx Series energy meter combines industrial grade split core current transformers and precision microprocessor based metering electronics It can detect phase reversal...

Страница 3: ...29mm E 8 1 207mm F 5 9 150mm MINI 200Amp MICRO 100Amp MEDIUM 400 800Amp A 3 8 95mm B 1 5 38mm C 1 3 32mm D 1 1 29mm E 4 2 107mm F 4 8 121mm SMALL 300Amp LARGE 800 1600 2400Amp F E D C B A A 1 6 40 mm...

Страница 4: ...ontrol data acquisition systems H8163 and H8167 6 Phaselossoutputalarm Alarm trips to protect equipment if phase voltage drops 25 H8163 and H8167 7 Pulserateselectionswitch Set the pulse output at 0 1...

Страница 5: ...quire a mounting bracket For maximum accuracy run the conductor through the center of the current transformer window 4 Optionalstep perNECandlocalregulations Attach external fuses not included with th...

Страница 6: ...T leads to the input terminals e g red labeled lead to red terminal Polarity is indicated in the wiring diagrams but the meter is not polarity sensitive See the Wiring section 6 Use color coding to co...

Страница 7: ...phase The displayed message indicates the problem phase Amps Over The measured current is greater than 110 of the transformer range The display message indicates the problem phase Volts Over Volts A C...

Страница 8: ...ween the terminals No Pulse output H8163 and H8167 Verify power is supplied in the range of 5 24VAC DC with a max load of 100 mA The pulse output internal is 200 msec verify the controller accepts thi...

Отзывы: