TM

H81xx

INSTALLATION GUIDE

 

Disconnect and lock out all power sources during  

 

 

installation and configuration.

 

If making connections to the meter through more than  

 

one metallic conduit, use a bonding plate (Veris part   

 

number AH11 or equivalent) to prevent electric shock. 

1.  Verify that the serial number on the meter matches the serial numbers on the 

current transformers (CTs). These are calibrated as a set, and mixing transformers 
with non-matching meters may damage the device when power is applied. The 
meter’s serial number is printed on the label affixed to the inside of the front 
cover, and the CT serial number is on the CT label. If using 100A CTs, serial number 
matching does not apply.

2.   Mount the meter.

3.  Attach the CTs to the conductors. Local code requirements may require a mounting 

bracket. For maximum accuracy, run the conductor through the center of the 
current transformer window.

4.  

Optional step, per NEC and local regulations:

  Attach external fuses (not included 

with the H81xx devices). Verify that the fuse rating is adequate for the applied 
voltage, with a current rating of ½ Amp (T) slow blow. Select fuses with a fault 
current rating that matches the power source rating.

INSTALLATION

VERIS INDUSTRIES

1-800-354-8556

Accessory bonding

plate or equivalent 

required when more 

than one metallic

conduit will be used.

Bond multiple

metallic conduit

runs with available

bonding plate

(Veris AH11 or equivalent)

CONTROLLER

Shock Hazard!

ØA

ØB

ØC
N

Installer Supplied Fuses

1/2A (T) SLO-BLO

Match serial numbers 

between meters and CTs. 

Serial number matching does 

not apply if using 100 A CTs.

Use fuses compatible with this meter:

Single phase  

Veris AH02

Two phase   

Veris AH03

Three phase   

Veris AH04

www.

GlobalTestSupply

.com

Find Quality Products Online at:

[email protected]

Содержание H81xx

Страница 1: ...e to follow these instructions will result in death or serious injury A qualified person is one who has skills and knowledge related to the construction and operation of this electrical equipment and...

Страница 2: ...CTs only PRODUCT OVERVIEW The H81xx Series energy meter combines industrial grade split core current transformers and precision microprocessor based metering electronics It can detect phase reversal...

Страница 3: ...29mm E 8 1 207mm F 5 9 150mm MINI 200Amp MICRO 100Amp MEDIUM 400 800Amp A 3 8 95mm B 1 5 38mm C 1 3 32mm D 1 1 29mm E 4 2 107mm F 4 8 121mm SMALL 300Amp LARGE 800 1600 2400Amp F E D C B A A 1 6 40 mm...

Страница 4: ...ontrol data acquisition systems H8163 and H8167 6 Phaselossoutputalarm Alarm trips to protect equipment if phase voltage drops 25 H8163 and H8167 7 Pulserateselectionswitch Set the pulse output at 0 1...

Страница 5: ...quire a mounting bracket For maximum accuracy run the conductor through the center of the current transformer window 4 Optionalstep perNECandlocalregulations Attach external fuses not included with th...

Страница 6: ...T leads to the input terminals e g red labeled lead to red terminal Polarity is indicated in the wiring diagrams but the meter is not polarity sensitive See the Wiring section 6 Use color coding to co...

Страница 7: ...phase The displayed message indicates the problem phase Amps Over The measured current is greater than 110 of the transformer range The display message indicates the problem phase Volts Over Volts A C...

Страница 8: ...ween the terminals No Pulse output H8163 and H8167 Verify power is supplied in the range of 5 24VAC DC with a max load of 100 mA The pulse output internal is 200 msec verify the controller accepts thi...

Отзывы: