background image

6%2)3).$5342)%3

inStALLAtion guiDe

XPSD1

 ZL0059-0B 

PAGE 2 

©2008 Veris Industries   USA 800.354.8556 or 503.598.4564  / [email protected] 

8251-0024C 

05082

operation

troubleshooting

Problem

Solution

LED off

Fault. Check line voltage, breakers, and connections. If 

OK, replace unit.

The XPSD1 surge protective device provides surge protection for electrical and 
automation cabinets. It mounts onto 35 mm DIN rail near the incoming power source 
to isolate the cabinet from the outside environment.

Note:  this device must be installed with proper supplementary protection (MGSP or 
equivalent; see specifications).

MGSP

L3

N

L2

L1

G

L1 L2 L3

N

Load Breakers

*

* max. 30A per NEC or as per local code

Wiring Diagram

NC

NO

Normally Closed

Common

Normally Open

3

3

2

1

2

1

remote monitoring option

The XPSD1 includes a three-pin socket and plug 
to allow the customer to wire one set of normally 
open (N.O.) and normally closed (N.C.) dry 
contacts to a remote monitoring indicator. The 
customer must provide power for the indicator 
(0.3A @ 125VAC, 110VDC; 1.0A @ 30VDC). In the 
event of an alarm, the N.O. contact closes, and 
the N.C. contact opens.

Dimensions

2.6”

(65 mm)

3.4”

(86 mm)

3.7”

(92 mm)

1.8”

(45 mm)

3.5”

(89 mm)

Three phase, 4-wire 208Y/120VAC

Diagnostics

ON = OK
OFF = Fault

Отзывы: