H8186-CB Energy Meter Communication Board is an optional field-installable board 
for the H8163 Energy Meter that provides a simple, cost-effective way to network the 
H8163 Energy Meter to an existing control/data acquisition systems via BACnet-
MS/TP communications capability. The H8186-CB is designed as a plug-and-play 
accessory for the H8163 energy meter. 

The H8186-CB features field selectable parity (odd/even/none). It works with 2-wire 
and 4-wire systems, and it has a field selectable baud rate (9600, 19200, 38400). 

oPeration

configuration

Product diagram

ON

1 2 3 4 5 6

ON

1 2 3 4 5 6

1

2

TX

RX

3

RX

4

TX

5

6

7

8

9

ALIVE

LITHIUM BATTERY

1. 

RS-485 LED (TX): 

 Red LED; blinks to indicate that the H8186-CB is transmitting 

data to the master.

2. 

RS-485 LED (RX):

  Red LED; blinks to indicate that the H8186-CB is receiving data 

from the master.

3. 

LED from Main Board (RX):

  Green LED; blinks to indicate that the H8186-CB is 

receiving data from the main board.

4. 

LED from Main Board (TX):

  Green LED; blinks to indicate that the H8186-CB is 

transmitting data to the main board.

5. 

“ALIVE” LED:

  Green LED; should blink once per second to indicate normal 

operation of the H8186-CB.

6. 

Network Address DIP Switches:

  Use these DIP switches to set the network 

address for the H8186-CB. 

7. 

Connection to Energy Meter:

  Install the H8186-CB in the energy meter by 

inserting this connector into the connection slot at the top of the energy meter. 

8. 

Communication DIP Switches:

  Use these DIP switches to set the H8186-CB 

wiring type, baud rate, and parity. 

9. 

RS-485 Communication Terminals:

  Insert the RS-485 connector into these 

terminals. See the Wiring Diagram section of this guide for instructions on wiring 
the connector for 2-wire or 4-wire communications. 

CAUTION! Danger of Explosion if battery is incorrectly 

replaced. Replace only with the same or equivalent type 

recommended by   the manufacturer. Dispose of used 

batteries according to the manufacturer’s instructions.

This section describes the communications settings you must make to the H8186-CB. 
When daisy-chaining devices, follow these guidelines:

You can connect up to 63 H8186-CB devices on a single daisy chain. 

• 

Each H8186-CB device on the daisy chain must have a unique address. 

• 

Before connecting the H8186-CB to the RS-485 communication wires, 
set the address according to directions in “Selecting the Network Address 
DIP Switches” on this page. If you assign the same address to two devices, 
neither device will communicate.
Set the wiring type, baud rate, and parity according to directions in 

• 

“Selecting Wiring Type, Baud Rate, and Parity—Communication DIP 
Switches” on this page. The settings for each H8186-CB must match the 
other devices on its daisy chain.
For RS-485 cables, use shielded, twisted-pair wire (Belden Cable 1120A or 

• 

equivalent).
Terminate the last device on the daisy chain. If the H8186-CB is the last 

• 

device, per the RS-485 standard (120 ohm nominal impedence).

Selecting The Network Address – DIP Switches

Use the Network Address DIP switches to select the network address. Each H8186-CB 
on a daisy chain must have a unique network address (from 0–63). Devices with the 
same address will be unable to communicate.

Always set the address before you install the H8186-CB in the energy meter and 
before you connect the energy meter to the daisy chain.

Each of the six DIP switches has a unique address value, page 8 lists DIP switch posi-
tions for specific addresses.

 

Network Address DIP Switch Values

 

Switch 

Value

 

1

 

2

 

4

 

8

 

16

 

32

8 + 32 = 40

In this example, the network address for the 
device is 40. Switch 4 and 6 offer the only 
combination of values that total 40.
This figure illustrates how to set the 
switches. Up is ON; down is OFF.

Archived Document

Содержание H8126-CB

Страница 1: ...UJPOT 0QFSBUJPO PG UIJT FRVJQNFOU JO B SFTJEFOUJBM BSFB JT MJLFMZ UP DBVTF IBSNGVM JOUFSGFSFODF JO XIJDI DBTF UIF VTFS XJMM CF SFRVJSFE UP DPSSFDU UIF JOUFSGFSFODF BU IJT PXO FYQFOTF PEJmDBUJPOT UP UI...

Страница 2: ...for 2 wire or 4 wire communications CAUTION Danger of Explosion if battery is incorrectly replaced Replace only with the same or equivalent type recommended by the manufacturer Dispose of used batteri...

Страница 3: ...daisy chain The RS 485 interface will support daisy chains that fall within the specifications shown below Baud Rate Maximum Distances 1 16 Devices 17 32 Devices 9600 10000 ft 3048 m 4000 ft 1219 m 1...

Страница 4: ...TX RX TX TX TX SHLD TX RX TX RX TX MASTER SLAVE ON 1 2 3 4 5 6 ON 1 2 3 4 5 6 TX RX RX ALIVE SHLD TX RX TX RX TX TX TX SHLD TX RX TX RX TX TX SHLD RX RX TX TX SHLD TX RX TX RX TX SHIELD RX RX TX TX M...

Страница 5: ...TION SLOTS 4 Insert the communication terminal onto the RS 485 communication terminals 5 If the demand subinterval feature is used wire into the end of the demand subinterval terminal 6 Replace the vo...

Страница 6: ...Network Address DIP switches for each Network address See Selecting the network Address NETWORK ADDRESS DIP SWITCHES on pages 2 3 for instruction on setting the switches 32 33 34 35 36 37 38 39 40 41...

Страница 7: ...Input Object 14 Voltage Phase A Phase B Volts_AB VOLTS Analog Input Object 15 Voltage Phase B Phase C Volts_BC VOLTS Analog Input Object 16 Voltage Phase A Phase C Volts_AC VOLTS Analog Input Object 1...

Страница 8: ...t Optional Properties Supported Max_Master Max_Info_Frames Description Location Writable Properties Object_Identifier Max_Master Location Property Range Restrictions Location limited to 64 characters...

Отзывы: